2-CHANNEL, ASTRONOMICAL DIGITAL
TIME PROGRAMMER ZCM-32, ZCM-32P/U
MANUAL INSTRUCTION
ZAMEL
Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamel.com
, e-mail: [email protected]
plik: inst_ext_en_zcm-32_32PU | modyfikacja: 07.04.2016
FEATURES
TECHNICAL DATA
DESCRIPTION
● control depending on current time in the
astronomical cycle,
● night break programme possibility and a
change of the calculated sunrise / sunset
time independently for channel 1 and 2,
● double modular casing with a protective
cover,
● IN control input,
● LCD with backlight,
● mounting on a TH35 rail.
ZCM-32 digital time programmers are
used to realize time functions in automa-
tion and control systems. Switching on /
switching off the device is related to sun-
set and sunrise (official dawn and dusk).
The following information on geograph-
ic coordinates of the clock’s installation
place, current date, and time difference
with regard to the universal time (GMT)
is used to calculate the time of sunrise
and sunset. The system calculates the
so-called official time of sunrise and sun-
set and this is the phase when the upper
edge of the Sun touches the horizon.
The system is equipped with two inde-
pendent channels (outputs). The system
has the function of a programmable night
break and a possibility to change the cal-
culated sunrise/sunset time in the range
of ±120 min for each channel. The de-
vice casing construction allows the sys-
tem to be installed on a TH35 rail and
additionally the casing can be sealed.
The system structure guarantees battery
backup of the settings in case of power
supply failure.
CAUTION:
To protect the programmer’s bat-
tery during storage time, the ZCM-32
series has a ‘storage mode’ default
setting with a minimum current con-
The device is designed for single-phase
installation and must be installed in accor-
dance with standards valid in a particular
country. The device should be connected
according to the details included in this ma-
nual instruction. Installation, connection and control should
be carried out by a qualified electrician staff, who act in ac-
cordance with the service manual and the device functions.
In case of casing dismantling, the guarantee is lost and an
electric shock may occur. Before installation make sure the
connection cables are not under voltage. Improper transport,
storage, and use of the device influence its wrong functio-
ning. It is not advisable to install the device in the following
cases: if any device part is missing or the device is damaged
or deformed. In case of improper functioning of the device
contact the producer.
CAUTION
* not applicable to ZCM-32
** applicable to ZCM-32P/U
Input (supply) terminals: A1, A2
Nominal supply voltage: ZCM-32: 230 V AC~(-15 ÷ +10 %)
ZCM-32xP/U: 24 ÷ 250V AC, 30 ÷ 300 V DC
Nominal frequency: 50 / 60 Hz
Nominal power consumption:
0,8 W / 1,4 VA – stand-by
1,8 W / 3,5 VA - channel 1
and 2 in switched on mode
Number of channels: 2
Programme: astronomical (official dawn and dusk)
Operation modes: automatic, manual
Summer/winter time change: automatic, manual
LCD backlight colour: amber
External input: yes – independent for channel 1 and 2
Cooperation with external memory:
ZCM-32: no
ZCM-32P/U: yes
Time measuring accuracy: max. ± 1 s / 24 h for 25℃
Clock battery backup: 3 years
Programme battery backup: 10 years
Input (release) terminals: IN1, IN1 – for channel 1
IN2, IN2 – for channel 2
Output (load) terminals: 11, 12, 14 – channel 1; 21,
22, 24 – channel 2
Relay contact parameters: 2 NO / NC 16 A / 250 V AC1 4000 VA
Number of connection terminals: 12
Cross-section of connection cables: 0,2 ÷ 2,50 mm²
Operating temperature range: -20 ÷ +60℃
Operating position: free
Casing mounting: TH35 rail (acc. to EN 60715)
Casing protection degree: IP20 (EN 60529)
Protection class: II
Overvoltage category: II
Pollution degree: 2
Dimensions: double modular (35 mm) 90 x 35 x 66 mm
Weight: 0,17 kg
Reference standard: EN 60730-1; EN 60730-2-7,
EN 61000-4-2,3,4,5,6,11
APPEARANCE**
LCD
Relay output terminals
(12, 11, 14)
Control push buttons
External memory*
Input (release) terminals:
(IN, IN, IN, IN)
Input (supply) terminals:
(A1, A2)
Daytime / Night time
Winter time
Manual mode
Automatic mode
Day of the week
Relay mode
Information field / date
Current time (hh:mm:ss)
The symbol means selective collecting of
electrical and electronic equipment.
It is forbidden to put the used equipment
together with other waste.
DESCRIPTION
MAIN MENU
STORAGE MODE
• • The ZCM-32 programmers have a ‘storage mode’ default setting to protect the battery during storage.
• • During battery backup operation, the first programmer activation is realised by means of pressing the ( ) button shortly which causes the storage mode is
changed, next it is required to set the date and time.
• • During rated voltage operation, the first programmer activation is realised by setting the time and date.
• • The programmer can be readjusted to the storage mode by means of carrying out a device reset
• - in order to do it press the ( ) and ( ) buttons simultaneously for a shorter time in the main menu.
Description of elements and messages displayed
Description of buttons
• in the main window - enter the automatic mode;
• in other windows – go up one level without saving the entered data;
• in the main window – enter the manual mode or change the relay mode if the clock is in the manual mode;
• in other windows - go up one level without saving the entered data;
• in the main window –enter the main menu;
• in other windows – enter the submenu or confirm the settings;
• switching between windows / menu options or increasing /decreasing the pre-set parameters;
• right cursor ( ) in the main menu – sunrise and sunset time display.
Press OK to enter from the main menu to the
menu; use cursors ( ) to move in the menu.
It is possible to enter the main menu again by
pressing the ( ) or ( ) button. From the main
window you can also enter windows displaying
the calculated sunrise/sunset time by pressing
the ( ) cursor. Return is automatic after 10 s.
Function Description
NIGHT BREAK SETTING
SUNRISE / SUNSET TIME CORRECTION SETTING
CURRENT TIME SETTING
CURRENT DATE SETTING
SUMMER / WINTER TIME SETTING
GEOGRAPHICAL POSITION AND TIME ZONE SETTING
EXTERNAL INPUT SETTING
EXTERNAL MEMORY SETTING**
CALCULATED SUNRISE TIME
CALCULATED SUNSET TIME
**
- days of the week
- relay mode
- automatic mode
- manual mode
- winter time
- summer time
- external input
- day
- year
- night break setting
- time correction setting
- current time setting and summer / winter time change
- current date setting
- geographical position setting
- external input setting
- external memory operation **
- write to external memory **
- read from external memory **
- external memory usage**
- reading / saving error**
/
- sunrise / sunset time
/
- latitude / longitude
- automatic,
- user
- switched on /switched off
OPERATION MODE CHANGE (AUTOMATIC, MANUAL)
, i Before changing the operation mode select channel (
) or (
) in the main menu
by means of the ( ) cursor.
MODE CHANGE INTO MANUAL - f the system is in the main window and the automatic mode
is active, press the ( ) button to change the system into the manual mode with a simultaneo-
us change of the relay mode;
i Subsequent pressing of the ( ) button causes the relay switches to the opposite mode, but
the operation mode does not change;
MODE CHANGE INTO AUTOMATIC - if the system is in the main menu and the manual mode
is active, press the ( ) button to change the system into the automatic mode with a simulta-
neous change of the relay mode;
and Subsequent pressing
of the ( ) button causes the
relay switches to the opposite
mode, but the operation mode
does not change;