APPEARANCE

FEATURES

TECHNICAL DATA

DESCRIPTION

●  Ensuring  continuity  of  supply  to  a  single-

phase load,

●  three-phase  supply  L1-L2-L3  (L1-priority 

phase),

●  adjustment  of  the  response  threshold  for 

maximum voltage,

●  adjustment  of  the  response  threshold  for 

minimum voltage,

●  adjustment of the priority phase  reset time,

●  adjustment of the auto reset time,

●  output  load  capacity  -  max.  16A  for  C1 

loads,

●  parameter  signaling  for  individual  supply 

phases - 3 x LEDs,

●  fault indication,

●  mounting in the switchgear (DIN-Rail).

APM-10  Automatic  phase  switch  is    a  de-

vice designed to maintain continuity of power 

supply to a single-phase load at the time of 

voltage fluctuation in the network. The device 

automatically selects the closest priority phase 

within the user-defined setting range and con-

nects it to the single-phase load. The maxi-

mum load capacity of the output should not 

exceed 16A for loads in class AC1. APM-10 is 

designed for installations in switchgears (DIN-

Rail). The housing has the width of 2 modules.

Power supply terminals:  L1, L2, L3, N

Rated supply voltage:  3 x 230 V AC + N

Rated frequency:  45 ÷ 55 Hz

Response range at U

min

:  160 ÷ 210 V 

Response range at U

max: 

230 ÷ 280 V

Priority phase output reclosing time range T

r

*:  5 ÷ 200 s

Reclosing time adjustment range T

on

: 1 ÷ 600 s

 Fixed switching delay (disconnection) at U

min:

12 s

 Backup phase switching time:  no longer than  0.2 s

Voltage hysteresis:  5 ÷ 6 V

Accuracy of determining response threshold at voltage change:  ±3 V

Maximum commutated current (cos φ=1) of output contacts:  16 A

Maximum commutated current (cos φ=0.4) of output contacts:  5 A

Power consumption (under load): not greater than 1,2 W

Number of connection terminals:  8

Cross section of connection wires:  0,5 ÷ 1,5 mm

2

Operating temperature:  -20 ÷ +45 °C 

Working position:  free

Housing mounting:  DIN-Rail

Housing protection degree:   IP20

Overvoltage category:  II

Pollution degree:  2

Dimensions:  90,2x36x64,5

Weight:  0,15 kg

The device should be con-

nected to a one-phase network 

in accordance with legally bind-

ing standards. The connection 

method is described in this 

manual. Any activities related 

to  installation,  connection,  and  adjustment 

should be performed by qualified electricians 

who have read this user’s manual and famil-

iarised themselves with device functions. Re-

moving the enclosure voids the warranty and 

poses a risk of electric shock. Before instal-

lation, make sure that there is no voltage on 

connection cables. To install the device, use 

a cross-head screwdriver with a diameter of 

3.5 mm. The proper operation of the device 

is affected by how the device is transported, 

stored, and used.  It is not advisable to install 

the device in the following cases: lack of any 

components, damage to or deformation of 

the device. If the device operates improperly, 

please contact the manufacturer.

NOTE

Do not dispose of this device together 

with other waste! To avoid harmful effects 

on the environment and human health, 

the worn-out device should be stored 

in designated areas. Electrical waste 

from households may be handed over 

to the waste collector established for 

this purpose free of change and in any 

amount, as well as to the store when 

purchasing new equipment.

Signalling the parameters

of voltage supply phases

Signalling the faults

Regulation of the response

threshold for maximum voltage U

max

Regulation of the response

threshold for minimum voltage U

min

Regulation of time for automatic

 restart Т

on

Regulation of time of re-activation 

of the priority phase on output T

r

Output terminals

(for load connection)

Power supply terminals