Charging Pile Instructions-V2.0
12
7.2 Installation Method and Installation Hole Size
(1) The charging pile is required to be installed on the cement column that shall be buried in
the ground mostly to ensure safe and stable running, referring to Figure 7.2.1
(2) The charging pile input line entries from the bottom, and enough space shall be reserved
inside cement column.
(3) Four expansion screws shall be used to fix charging pile on the cement column, and the
screw size shall be determined by installation size and based on on-site requirements. Please
refer to figure 7.2.2, chart 7.2.2 and chart 7.2.3 for specific size.
(4) During the installation, enough distance between the charging pile and wall shall be
ensured. The installation distance between the back door of the charging pile and wall shall
be no less than 700 mm, and the distance between the side face of the charging pile and wall
shall be no less than 500 mm.
(5) The canopy shall be built together with the charging pile.
(6) The above installation method is just a sample for reference. Relevant installation
methods shall be chose according to the actual onsite situation Please refer to the
construction instruction for details.
(7) For input lines, specified cables are recommended. See Chart 7.2.1 for details:
Chart 7.2.1 Cables Specification
Output
power
AC Input Voltage
Max.
Input
Current
Cable Size Recommended
30kW
400V±15% AC
55A
YJV22-0.6/1kV-3*16mm
²
+2*10mm
²
40kW
400V±15% AC
73A
YJV22-0.6/1kV-3*25mm
²
+2*16mm
²
45kW
400V±15% AC
83A
60kW
400V±15% AC
110A
YJV22-0.6/1kV-3*35mm
²
+2*16mm
²
75kW
400V±15% AC
138A
YJV22-0.6/1kV-3*50mm
²
+2*25mm
²