Yudian AI Series Operating Instructions Manual Download Page 1

 

 

 

 

AI-SERIES MULTI-CHANNEL PID TEMPERATURE CONTROLLER 

AI-7028 / AI-7048 

 

Operation Instruction   

Ver. 7.8 

 

 

1.  SUMMARY 

Multi-channel  temperature  controller  provides  thermocouple  inputs  and  solid-state  SSR  outputs. 

Each  channel  can  be  set  as  different  type  of  inputs  and  works  independently.  This  controller  can 

either  used  independently  or  used  with  computer  or  PLC  (Programmable  Logic  Controller).  The 

supply  power  can  be  ordered  as  24VDC/AC  or  100~240VAC.  It  complies  with  ISO9001  quality 

assurance. It is highly reliable with EMC standard compatible. The power and all I/O terminals has 

passed 4KV/5KHz EFT test. It is able to be stably working under strong interference. By adopting 
YUDIAN’s new technology, the anti-interference power of multi-channel inputs is as strong as that of 
single channel measurement.   

 

Providing up to 4 channels of programmable inputs, supporting multiple thermocouple inputs, K, 
S, E,  J, B,  N, T, WRe5-WRe25  and  etc,  with automatic  cold  junction  compensation and  linear 

voltage  (mV)  inputs  with  user  defined  scale.  Individual  digital  filtering  for  each  channel  are 

possible to be adjusted or disabled. 

 

High  performance  hardware  design,  which  greatly  decreased  temperature  drift  and  the 
interference among the 4 channels.    Therefore, this multi-channel  controller obtains the same 

measurement accuracy and anti-interference ability as that of single channel controller. 

 

Rail mounted panel with code D5/E5/D7/E7 are available. Those panels without display can be 
programmed by connecting the external handset display E8. 

 

Apart  from  rail  mounted  panel  D5,  every  channel  has  independent  high/low  limit  alarm  or 
deviation  alarm  outputs.  Those  alarms  can  be  assigned  to  different  alarm  output  slot  (AL1  or 

AL2) by programming. Alarms from different channels can be assigned to the same alarm slot or 

different alarm slots. 

 

There are 12 programmable Field Parameters. Users can tailor-made the parameter table. 

 

Advanced  communication  functions,  compatible  with  the  communication  protocol  of  other  AI 
series  instruments  such  as  AI-708  high  precision  artificial  intelligent  regulator/temperature 

controller. One unit of AI-7048 in communication works as if there are 4 individual units of AI-708 

controllers working. 

 

Among  this  multi-channel  controller  series,  AI-70482  provides  4  channels  of  individual  inputs 
with weak electronic signal isolation among channels. It is suitable for application of grounded 

thermocouples of which the negative pole of thermocouple is connected to the probe shell.   

Summary of Contents for AI Series

Page 1: ...hich greatly decreased temperature drift and the interference among the 4 channels Therefore this multi channel controller obtains the same measurement accuracy and anti interference ability as that o...

Page 2: ...600 1800 C Temperature shift 0 01 FS C typical value is 60ppm C Electromagnetic compatibility EMC 4KV 5KHz according to IEC61000 4 4 4KV according to IEC61000 4 5 Isolation withstanding voltage Betwee...

Page 3: ...Negative poles of 4 thermocouple inputs in common Terminal 5 8 Positive poles of 4 SSR voltage outputs Terminal 3 4 Negative poles of 4 SSR voltage outputs in common The specification of SSR outputs...

Page 4: ...erminal 13 14 17 18 Positive poles of 4 thermocouple inputs Terminal 15 16 19 20 Negative poles of 4 thermocouple inputs E7 multi channel temperature controller Wiring diagram Terminal 3 4 Power 100 2...

Page 5: ...be set by pressing or Press key to decrease the value Press key to increase the value Press key to move to the digit expected to modify Keep pressing or the speed of decreasing or inscreasing value ge...

Page 6: ...t off time It means The on off period is as long as 1 6 second means no communication and no alarm it can be treated as normal The light flashing with period 0 6 second means no communication and some...

Page 7: ...n dPt 0 the display resolution is 1 when dPt 1 the resolution is 0 1 Note dPt only affects the display and has no effect on internal data 0 3 SCLx Scale low limit SCL and SCH define the corresponding...

Page 8: ...maximum will disable the alarm function B 0 Normal application B 1 Change all of the low alarm to be low deviation alarm when deviation value PV SV L ALx it will trigger the alarm When PV SV L ALx HYS...

Page 9: ...operators the parameter EP can be set as EP1 SP1 EP2 SP2 EP3 SP3 EP4 SP4 EP5 none Loc 0 Then only parameter SP1 4 can be displayed and modified but via communication on the host computer all parameter...