3)  Attach YT-2700L (with bracket) to the actuator yoke – DO NOT TIGHTEN COMPLETELY.   

 

4)  Connect YT-2700L feedback lever to the actuator clamp.  The gap on the YT-2700L 

feedback lever is 6.5mm.  The connection bar thickness should be less than 6.3mm.  

<Figure 3>  

 
 
 
 
 
 
 
 
 
 
 
 

5)  Connect air filter regulator to the actuator temporarily.  Set supply pressure of the regulator in 

order to position the actuator clamp at 50% of valve stroke.  <Figure 4> 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6)  Insert connection bar into the YT-2700L feedback lever.  The connection bar should be 

inserted at the 50% point on the feedback lever, which would help to reduce hysteresis. 

 

7)  If connection bar does not point at 50% point, then adjust bracket or feedback link bar 

position.  Failure to position at 50% would lower the linearity of the poistioner.  <figure5>   

 
 
 
 
 
 
 
 
 
 

Young Tech Co.  #662-8 PumgMu Dong, Kimpo City, (415-809) Korea  (031) 986-4935   www.ytc.co.kr

 