Smart Positioner YT-2700L,R Installation manual
3) Attach YT-2700L (with bracket) to the actuator yoke – DO NOT TIGHTEN COMPLETELY.
4) Connect YT-2700L feedback lever to the actuator clamp. The gap on the YT-2700L
feedback lever is 6.5mm. The connection bar thickness should be less than 6.3mm.
<Figure 3>
5) Connect air filter regulator to the actuator temporarily. Set supply pressure of the regulator in
order to position the actuator clamp at 50% of valve stroke. <Figure 4>
6) Insert connection bar into the YT-2700L feedback lever. The connection bar should be
inserted at the 50% point on the feedback lever, which would help to reduce hysteresis.
7) If connection bar does not point at 50% point, then adjust bracket or feedback link bar
position. Failure to position at 50% would lower the linearity of the poistioner. <figure5>
Young Tech Co. #662-8 PumgMu Dong, Kimpo City, (415-809) Korea (031) 986-4935 www.ytc.co.kr