Young 05631C Instruction Sheet Download Page 1

INSTRUCTION SHEET 05631C-90

REV: B051311

MODEL 05631C 

WIND  LINE DRIVER

SPECIFICATIONS

Wind Speed Input: 

YOUNG Wind Monitor series of sensors  

AC sine wave, Frequency proportional 

to wind speed.  3 pulses per revolution. 

Input sensitivity nom. 40 mV p-p

Wind Direction Input: 

Analog voltage from azimuth 

potentiometer.  Regulated excitation 

voltage is supplied from interface circuit 

to potentiometer.  

Wind Speed Output: 

4 to 20 mA = 0-100 M/S

Wind Direction Output:  4 to 20 mA = 0 to 360°

Overall accuracy: 

± 1% of full scale over temperature and 

supply voltage range

Dimensions: 

110 mm W x 75 mm H x 56 mm D   

(4.3 in W x 2.9 in H x 2.2 in D)

Mounting: 

U-bolt for vertical pipe 

 

 25-50mm (1-2 in) Diameter

Power Requirement: 

12-30 VDC 

Temperature Range:  

-50 to 50°C (-58 to 122°F)

INTRODUCTION

The Wind Line Driver converts raw signals from the wind sensors to 

proportional 4 to 20 mA current loop values. The Line Driver acts like 

a variable resistance that draws 4 - 20 mA when powered with 12 to 

30 VDC. Although it has only one PC board, the Line Driver contains 

two completely independent circuits - one for wind speed and the 

other for wind direction. See wiring diagram below.

IMPORTANT!

The Wind Line Driver provides a calibrated current signal 

for wind speed and wind direction. Externally connected 

devices should be reviewed for compatibility and correct 

signal scaling.

Repairs should be attempted only by qualified service personnel.

Declaration of Conformity

R. M. Young Company

2801 Aero Park Drive

Traverse City, MI 49686 USA

Model  05631C  Wind Line Driver

The undersigned hereby declares on behalf of R. M.

Young Company that the above-referenced product, to

which this declaration relates, is in conformity with the

provisions of:

Council Directive 2004/108/EC (December 15, 2004)

on Electromagnetic Compatibility

David Poinsett

R&D Manager

WARRANTY

This product is warranted to be free of defects in materials and 

construction for a period of 12 months from date of initial purchase. 

Liability is limited to repair or replacement of defective item. A copy 

of the warranty policy may be obtained from R. M. Young Company.

CE COMPLIANCE

This product has been tested and shown to comply with European 

CE requirements for the EMC Directive. Please note that shielded 

cable must be used.

CALIBRATION FORMULAS

 

WIND SPEED  vs 

mA OUTPUT

 

m/s 

(  6.250 x mA)-25

 

knots 

(12.149 x mA)-48.6

 

mph 

(13.980 x mA)-56

 

km/h 

(22.500 x mA)-90

 

WIND DIRECTION    vs 

mA OUTPUT

 

  DEGREES  = 

(22.5 x mA)-90

R. M. YOUNG COMPANY 

  

2801 Aero Park Drive ,  Traverse City,   Michigan   49686   U.S.A.

TEL  (231) 946-3980       FAX  (231) 946-4772     E-mail: [email protected]