York ZW-06 Installation Manual Download Page 36

5565604-BIM-B-1018

36

Johnson Controls Ducted Systems

The VFD should also be grounded per the manufacturer's 
specifications.

Figure 27: Simplified VFD Wiring

A terminal block located in the control box is provided for field 
connection of the VFD speed reference signal (2-10 VDC) and 
to the normally-open, run-permit auxiliary contact. The use of 
shielded cable is recommended for the above control wiring 
connections.

Optional Hot Gas Bypass (HGBP)

To allow for low cooling load operation, a direct-acting, 
pressure-modulating bypass control valve installed on the 
system #1 discharge line is used to divert high temperature, 
high pressure refrigerant around the TXV in order to maintain a 
desired minimum evaporator pressure. 

The opening pressure of the bypass valve is adjustable 
between 95 and 115 psig with a factory-setting of 105 psig. 
HGBP is standard on all units with VAV and optional with CV 
units.

Economizer Sequences

Several functions can drive the economizer, including: minimum 
position, free cooling, economizer loading, and minimum 
outdoor air supply.

Economizer Minimum Position

The economizer minimum position is set during occupied mode 
when outside air is not suitable for free cooling. The position of 
the damper is set proportionally between the "Economizer 
Minimum Position and the Economizer Minimum Position Low 
Speed Fan" set points, in relationship to the VFD output 
percentage. On a constant volume single speed supply fan 
system both set-points should be set to the same value. 

Free Cooling

Four types of free cooling options are available: dry bulb 
changeover, single enthalpy, dual enthalpy changeover, and 
Auto.

Dry Bulb Changeover

For dry bulb economizer operation, the outside air is suitable for 
free cooling if the outside air temperature is 1°F below the 
Economizer OAT Enable Setpoint 

and

 1°F below the Return Air 

Temperature.

Free cooling is no longer available if the outside air temperature 
rises above 

either

 the Economizer OAT Enable setpoint 

or

 the 

return air temperature.

Single Enthalpy Changeover

For single enthalpy economizer operation, the outside air is 
suitable for free cooling if the outside air enthalpy is at least 1 
BTU/lb below the Economizer Outside Air Enthalpy Setpoint 

and

 the outside air temperature is no greater than the RAT plus 

9°F.

If the outside air temperature rises above the RAT plus 10°F, 
free cooling is no longer available. The outside air temperature 
must drop to no greater than RAT plus 9°F to enter free cooling 
again.

Free cooling is no longer available if the outside air enthalpy 
rises above the Economizer Outside Air Enthalpy Setpoint.

Dual Enthalpy Changeover

For dual enthalpy economizer operation, the outside air 
enthalpy must be lower than the return air enthalpy by 1 btu/lb 
AND the outside air temperature is no greater than the RAT 
plus 9°F.

Auto

The control determines the type of free cooling changeover 
based on which sensors are present and reliable. Conditions 
include:

• Return and outside air dry bulb = dry bulb changeover
• Return and outside air dry bulb and outside air humidity = 

single enthalpy

• Return and outside air dry bulb and return and outside air 

humidity = dual enthalpy

• If either the return or outside air dry bulb sensors are 

unreliable, free cooling is not available

Do not connect AC power to the T1, T2, T3 drive 
terminals to prevent damage to the VFD.

The fuses (FU3, FU4, FU5) supplied with the unit are 
sized according to the electrical load of the blower 
motor, but may not provide adequate protection to the 
customer-installed drive, depending upon its 
specifications.  Once a drive has been selected and 
installed, refer to the drive manufacturer's 
recommendations for proper fuse sizing.

ELEMENTARY DIAGRAM

VFD

TB8 (IN CONTROL BOX)

RUN PERMIT

(DIGITAL)

SPEED REF

(ANALOG)

(2-10 VDC)

GND

GRN

GND

GRN

GND

1 DMTR

118 / BK

119 / BR

120 / Y

3

M

(T1)

(T2)

(T3)

(   )

(L1)

(L3)

(L2)

722 / BK

725 / BR

728 / Y

720 / PR

723 / BR

726 / O

TB1

FU3

FU5

FU4

1

2

3

4

5

6

L3

L2

L1

T1

T2

T3

Summary of Contents for ZW-06

Page 1: ...lication 45 18 Airflow Performance Bottom Duct Application 47 19 RPM Selection 48 20 Indoor Blower Specifications 49 21 Power Exhaust Specifications 49 22 Motor Sheave Datum Diameters 51 23 Additional...

Page 2: ...precautions and codes including ANSI Z223 1 or CSA B149 1 latest edition Improper installation may create a condition where the operation of the product could cause personal injury or property damage...

Page 3: ...nly 3 For installation on combustible material and may be installed directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials 4 For use with...

Page 4: ...TD Filter 5 2 Pleated Filter CG 6 4 Pleated Filter CG A Std Cabinet E SSD SST Drain Pan R Reverse Drain Pan A No Economizer B Economizer w Barometric RLF D Economizer w Power EXH H Motorized Damper Ou...

Page 5: ...e ground 3 Remove the condenser coil external protective covering prior to operation 4 Remove the toolless doorknobs and instruction packet prior to installation Figure 2 Condenser Covering Figure 3 C...

Page 6: ...process cooling applications computer rooms switchgear etc please call the applications department for Ducted Systems 1 877 874 SERV for guidance Additional accessories may be needed for stable opera...

Page 7: ...re when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spr...

Page 8: ...fted The condenser coils should be protected from rigging cable damage with plywood or other suitable material D A C B LEFT FRONT D A C B E F LEFT FRONT X Y LEFT FRONT Table 2 Weights and Dimensions S...

Page 9: ...Heat1 1 Weight given is for the maximum heater size available 54KW 49 49 Gas Heat2 2 Weight given is for the maximum number of tube heat exchangers available 8 tube 110 110 Variable Frequency Drive3...

Page 10: ...Ducted Systems Figure 9 ZW 12 Physical Dimensions 15 23 29 03 14 85 29 03 14 85 15 23 28 86 29 66 44 09 24 58 TYP 4 PL FRONT See detail B for drain location See detail A for gas inlet C D E F B 4 3 1...

Page 11: ...1 2 30 3 16 24 3 16 17 3 16 6 3 16 42 CABINET 3 126 2 000 3 184 4 727 7 705 14 594 Gas Pipe Inlet Gas Exhaust Vent 50 3 4 CABINET 3 126 2 000 3 184 4 737 7 715 17 541 Gas Pipe Inlet Gas Exhaust Vent 5...

Page 12: ...Unit Bottom Duct Openings Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27...

Page 13: ...t Electrical Entry Figure 12 ZW 06 thru 10 Unit Side Duct Openings Disconnect Swith Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry...

Page 14: ...Left End Duct Opening Dot Plugs 2 7 8 5 5 32 D C 31 5 8 18 1 4 B A Table 6 Side Duct Dimensions Unit Model Number Dimension in A B C D ZW 06 28 1 4 18 1 16 28 1 4 18 1 4 ZW 07 28 1 4 18 1 16 28 1 4 18...

Page 15: ...imension in A B C ZW 06 30 358 22 580 22 330 ZW 07 30 358 22 580 22 330 ZW 08 30 358 22 580 22 330 ZW 10 30 358 22 580 22 330 ZW 12 30 358 22 580 22 330 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATE...

Page 16: ...o be reused by securing each panel to its respective down flow opening But keep in mind that the supply panel is installed with the painted surface UP facing the heat exchanger while the return panel...

Page 17: ...me size and type Dirty filters reduce the capacity of the unit and result in frosted coils or safety shutdown Refer to physical data tables for the number and size of filters needed for the unit The u...

Page 18: ...wired with a separate branch circuit fed directly from the meter panel and properly fused Refer to Figures 22 23 and 24 for typical field wiring and to the appropriate unit wiring diagram mounted insi...

Page 19: ...Johnson Controls Ducted Systems 19 Figure 23 Field Wiring Disconnect Cooling Unit With Gas Heat Without VFD Option L1 T1 L2 T2 T3 L3 THREE PHASE POWER SUPPLY FACTORY OR FIELD SUPPLIED DISCONNECT GROUN...

Page 20: ...le stage he g units Jumper is required if there is no Smoke Detector circuit Jumper is required for any co of R RC or RH 5 5 OCC is an output from the thermostat to indicate the Occupied on X is an in...

Page 21: ...5 2 5 5 None 41 9 47 4 50 60 E09 6 8 1 18 9 41 9 47 4 50 60 E18 13 5 2 37 5 53 4 60 3 60 70 E24 18 2 50 69 75 9 70 80 E36 25 5 2 70 8 95 101 9 100 110 230 13 6 83 1 21 3 03 5 2 5 5 None 41 9 47 4 50 6...

Page 22: ...75 5 90 90 E24 18 0 2 50 0 74 5 81 3 90 90 E36 25 5 2 70 8 100 5 107 4 110 110 E54 40 6 2 112 7 152 9 159 7 175 175 230 23 1 160 0 36 0 2 1 9 6 5 5 0 0 None 70 0 75 5 90 90 E18 18 0 2 43 3 70 0 75 5 9...

Page 23: ...3 51 8 50 60 E09 6 8 1 18 9 46 3 51 8 50 60 E18 13 5 2 37 5 58 9 65 8 60 70 E24 18 2 50 74 5 81 4 80 90 E36 25 5 2 70 8 100 5 107 4 110 110 230 13 6 83 1 21 3 03 9 6 5 5 None 46 3 51 8 50 60 E09 9 1...

Page 24: ...9 9 90 100 E24 18 0 2 50 0 80 0 86 8 90 100 E36 25 5 2 70 8 106 0 112 9 110 125 E54 40 6 2 112 7 158 4 165 2 175 175 230 23 1 160 0 36 0 2 1 14 0 5 5 0 0 None 74 4 79 9 90 100 E18 18 0 2 43 3 74 4 79...

Page 25: ...60 70 E09 6 8 1 18 9 51 9 57 4 60 70 E18 13 5 2 37 5 65 9 72 8 70 80 E24 18 2 50 81 5 88 4 90 90 E36 25 5 2 70 8 107 5 114 4 110 125 230 13 6 83 1 21 3 03 5 2 5 5 20 None 51 9 57 4 60 70 E09 9 1 21 7...

Page 26: ...85 5 100 100 E24 18 0 2 50 0 87 0 93 8 100 100 E36 25 5 2 70 8 113 0 119 9 125 125 E54 40 6 2 112 7 165 4 172 2 175 175 230 23 1 160 0 36 0 2 1 9 6 5 5 10 0 None 80 0 85 5 100 100 E18 18 0 2 43 3 80...

Page 27: ...60 70 E09 6 8 1 18 9 56 3 61 8 60 70 E18 13 5 2 37 5 71 4 78 3 80 80 E24 18 2 50 87 93 9 90 100 E36 25 5 2 70 8 113 119 9 125 125 230 13 6 83 1 21 3 03 9 6 5 5 20 None 56 3 61 8 60 70 E09 9 1 21 7 56...

Page 28: ...89 9 100 110 E24 18 0 2 50 0 92 5 99 3 100 110 E36 25 5 2 70 8 118 5 125 4 125 150 E54 40 6 2 112 7 170 9 177 7 175 200 230 23 1 160 0 36 0 2 1 14 0 5 5 10 0 None 84 4 89 9 100 110 E18 18 0 2 43 3 84...

Page 29: ...Btu 96 144 96 144 96 144 144 192 144 192 AFUE Steady state efficiency 80 80 80 80 80 80 80 80 80 80 No burners 4 6 4 6 4 6 6 8 6 8 No stages 23 23 23 23 23 23 23 23 23 23 Temperature Rise Range F 20...

Page 30: ...89 AK74 AK84 AK74 AK74 BK77 Belt A53 A54 A52 A54 A56 A54 A56 A54 A54 BX56 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 56 56 56 56 56 56 5...

Page 31: ...our of gas flow required specific gravity of the gas and the length of run National Fuel Gas Code Z223 1 in U S A or the current Gas Installation Codes CSA B149 1 in Canada should be followed in all c...

Page 32: ...eaned of dirt and scale by hammering on the outside of the pipe and blowing out loose particles Before initial start up be sure that all gas lines external to the unit have been purged of air 5 The ga...

Page 33: ...ctric heaters are available as factory installed options or field installed accessories Refer to electric heat instructions for installation These heaters mount in the heat compartment with the heatin...

Page 34: ...Down Flow application 2 Horizontal Flow application that requires the purchase of a barometric relief hood Rain Hood All of the hood components including the filters the gasketing and the hardware fo...

Page 35: ...peration and complete electrical isolation of the drive TEST routes power to the VFD but not to the motor to allow for drive programming and or diagnostics If a drive failure occurs the unit does not...

Page 36: ...g is no longer available if the outside air temperature rises above either the Economizer OAT Enable setpoint or the return air temperature Single Enthalpy Changeover For single enthalpy economizer op...

Page 37: ...supply air temperature to the Economizer Setpoint At no time will a compressor output be turned ON if the economizer output is less than 100 even if the differential between zone or return temperature...

Page 38: ...mistor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Page 39: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Page 40: ...egative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HOT...

Page 41: ...pressures or producing a high noise level the scroll is misphased Blower Rotation Check for proper supply air blower rotation If the blower is rotating backwards the line voltage at the unit point of...

Page 42: ...t high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correction factors are shown in Table 16 and Fi...

Page 43: ...iven is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80 Enter the blower table at 6000 sCFM and...

Page 44: ...s found 5 1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns o...

Page 45: ...4 2 04 2400 631 0 16 682 0 41 736 0 66 793 0 90 852 1 14 911 1 36 970 1 58 1028 1 78 1084 1 97 1136 2 13 2600 642 0 27 692 0 52 747 0 76 804 1 01 862 1 24 922 1 47 981 1 69 1039 1 89 1094 2 07 1146 2...

Page 46: ...G1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to de...

Page 47: ...1012 1 61 1065 1 81 1113 2 02 1153 2 24 2400 689 0 42 743 0 69 800 0 93 859 1 16 919 1 37 978 1 57 1035 1 77 1088 1 97 1135 2 18 1176 2 40 2600 712 0 60 766 0 87 823 1 11 882 1 34 942 1 55 1002 1 75...

Page 48: ...RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard 3 HP Drive Hi Static 5 HP Drive 3200 797 1 32 851 1 46 903 1 60 953 1 74 1001 1 86 1048 1 99 1093 2 11 1138 2 23...

Page 49: ...ws after 10 12 hrs run time is recommended Table 20 Indoor Blower Specifications Size Tons Model Motor Motor Sheave Blower Sheave Belt HP RPM Eff SF Frame Datum Dia in Bore in Model Datum Dia in Bore...

Page 50: ...en 5 Select the correct blower performance table for the unit from Tables 17 and 18 Tables are presented for side and down flow configuration 6 Determine the unit Measured CFM from the Blower Performa...

Page 51: ...allation for any installation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure and...

Page 52: ...has a delay of 10 seconds minimum off Optional VAV Start up and Control Table 23 Additional Static Resistance Size Tons Model CFM Cooling Only1 1 Add these values to the available static resistance in...

Page 53: ...s have been completed Upon the final compressor de energizing the blower is stopped following the elapse of the fan off delay for cooling To be available a compressor must not be locked out due to a h...

Page 54: ...e Suction Line at the Evaporator Coil detects a temperature below 26 Deg F default the UCB will de energize the associated compressor initiate the ASCD and if the other compressor is idle stop the con...

Page 55: ...emperature limit switch of electric heat units The control circuit includes the following safety controls Limit Switch LS This control is located inside the heater compartment and is set to open at th...

Page 56: ...n attempts If the unit fails after three ignition attempts the furnace is locked out for one hour The furnace is monitored during this one hour period for unsafe conditions Recycle Operation When a fl...

Page 57: ...ICB monitors the Pressure and Roll out switches of gas heat units The control circuit includes the following safety controls Pressure Switch PS Once the draft motor has reached full speed and closes t...

Page 58: ...ON position See Figure 33 4 Turn ON electric power to unit 5 If thermostat set temperature is above room temperature the main burners will ignite If a second stage of heat is called for the main burne...

Page 59: ...contact your gas company for this information as it varies widely from area to area EXAMPLE By actual measurement it takes 19 seconds for the hand on a 1 cubic foot dial to make a revolution with a 1...

Page 60: ...move the screws holding each end of the manifold to the manifold supports 3 Disconnect wiring to the gas valves and spark igniter s Remove the manifold gas valve assembly Orifices can now be inspected...

Page 61: ...microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in series Connec...

Page 62: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Page 63: ...reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for reh...

Page 64: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Page 65: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Page 66: ...ication circuit Earth ground reference of the cable to prevent interference on the FC bus BACnet MSTP communication circuit Item Selector in red housing at left on top edge of the communication board...

Page 67: ...air Cable2 2 We recommend 26 AWG solid 6 wire 3 twisted pairs cable as the best fit for fabricating modular cables with the modular jack housing assembly Be sure the cable you use fits the modular jac...

Page 68: ...WLDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HT...

Page 69: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Page 70: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Page 71: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Page 72: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Page 73: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Reviews: