5567611-BIM-B-1218
78
Johnson Controls Ducted Systems
Table 36: ZV-07 charging table - system 1
Table 37: ZV-07 charging table - system 2
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
133
55
252
82
31
80
49
85
135
54
293
92
29
80
51
95
137
54
339
99
28
80
52
300 CFM/ton
80/67
75
143
60
254
81
26
80
54
85
146
60
296
91
25
80
55
95
149
60
342
99
23
80
57
300 CFM/ton
80/72
75
156
67
259
80
21
80
59
85
160
67
300
90
20
80
60
95
162
67
346
99
19
80
61
300 CFM/ton
75/62
75
132
54
252
82
26
75
49
85
135
54
292
91
25
75
50
95
138
54
338
101
23
75
52
400 CFM/ton
80/62
75
136
56
256
78
26
80
54
85
140
56
296
88
26
80
54
95
144
57
342
99
25
80
55
400 CFM/ton
80/67
75
151
65
257
81
22
80
58
85
154
64
298
90
21
80
59
95
156
63
345
98
21
80
59
400 CFM/ton
80/72
75
162
71
263
78
17
80
63
85
166
70
304
88
17
80
64
95
169
70
350
97
16
80
64
400 CFM/ton
75/62
75
139
58
255
80
22
75
53
85
142
57
296
90
21
75
54
95
144
57
342
98
21
75
54
Air flow
Indoor Db/Wb
Outdoor DB
Suction
pressure
Suction
temp.
Discharge
pressure
Liquid temp. Delta T Db
Entering evap
Db
Leaving evap
Db
300 CFM/ton
80/62
75
128
54
256
80
31
80
49
85
131
53
300
88
29
80
51
95
135
52
348
97
28
80
52
300 CFM/ton
80/67
75
140
61
260
78
26
80
54
85
144
60
303
88
25
80
55
95
147
59
351
97
23
80
57
300 CFM/ton
80/72
75
150
68
265
77
21
80
59
85
154
67
307
87
20
80
60
95
159
66
355
97
19
80
61
300 CFM/ton
75/62
75
128
54
258
77
26
75
49
85
132
53
300
87
25
75
50
95
135
53
348
96
23
75
52
400 CFM/ton
80/62
75
132
57
261
76
26
80
54
85
137
57
303
86
26
80
54
95
141
56
351
96
25
80
55
400 CFM/ton
80/67
75
146
65
263
77
22
80
58
85
150
64
306
87
21
80
59
95
153
62
354
97
21
80
59
400 CFM/ton
80/72
75
155
71
271
75
17
80
63
85
160
70
312
86
17
80
64
95
164
69
358
96
16
80
64
400 CFM/ton
75/62
75
134
58
260
77
22
75
53
85
138
57
303
87
21
75
54
95
141
56
350
96
21
75
54