5567611-BIM-B-1218
6
Johnson Controls Ducted Systems
Figure 3: Compressor section
4.
If a factory option convenience outlet is installed, you must
install the weatherproof outlet in the field. The cover is
located behind the filter access panel.
a. Remove the shipping label that covers the convenience
outlet.
b. Follow the instructions on the back of the weatherproof
cover box.
c. Attach the cover to the unit with the four (4) screws
provided.
Limitations
These units must be installed in accordance with the following:
In the U.S.A.:
1.
National Electrical Code, ANSI/NFPA No. 70 - Latest
Edition
2.
National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3.
Gas-Fired Central Furnace Standard, ANSI Z21.47a. -
Latest Edition
4.
Local building codes, and
5.
Local gas utility requirements
In Canada:
1.
Canadian Electrical Code, CSA C22.1
2.
Installation Codes, CSA - B149.1.
3.
Local plumbing and waste water codes, and
4.
Other applicable local codes.
Refer to the unit application data found in this document.
After installation is complete, you must adjust gas fired units to
obtain a temperature rise within the range specified on the unit
rating plate.
If components are added to a unit to meet local codes, they are
installed at the dealer’s and/or customer’s expense.
The size of the unit for the proposed installation must be based
on a heat loss/heat gain calculation made according to the
methods of the Air Conditioning Contractors of America
(ACCA).
This furnace is not to be used for temporary heating of buildings
or structures under construction.
208/230-3-60 units with a factory installed powered
convenience outlet option are wired for a 230v power
supply. Change the tap on the transformer for 208-3-60
operation. See the unit wiring diagram.
Toolless
Doorknobs
Installation
Instruction
Packet
The Smart Equipment™ control board used in this
product can effectively operate the cooling system down
to 0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When you apply this
product for process cooling applications (such as
computer rooms or switchgear), please call the
applications department for Ducted Systems @ 1-877-
874-SERV for guidance. Additional accessories may be
needed for stable operation at temperatures below 30°F.