5167821-YTG-K-1118
Johnson Controls Ducted Systems
23
115°F
125°F
750
77
36.9
3.0
18.6
16.5
14.5
-
-
-
34.4
3.3
18.2
16.3
14.3
-
-
-
72
32.4
3.0
22.8
19.7
16.6
13.4
-
-
29.5
3.3
21.6
18.6
15.6
12.6
-
-
67
28.6
3.0
27.1
22.8
18.6
15.3
12.0
-
25.4
3.4
25.0
21.0
16.9
13.9
10.9
-
62
28.1
3.0
27.8
24.2
20.6
17.2
13.8
10.3
26.0
3.3
25.7
22.0
18.3
15.2
12.2
9.2
900
77
36.4
3.0
21.6
17.8
14.0
-
-
-
33.3
3.3
21.2
17.3
13.5
-
-
-
72
33.4
3.0
25.2
21.2
17.1
13.0
-
-
30.4
3.4
23.9
19.9
16.0
12.0
-
-
67
30.4
3.0
28.8
24.5
20.2
16.1
11.9
-
27.4
3.4
26.6
22.5
18.5
14.6
10.7
-
62
29.5
3.0
29.3
26.3
23.3
19.1
14.9
10.7
27.2
3.3
26.9
24.0
21.0
17.1
13.3
9.4
57
28.6
3.0
28.6
28.1
26.4
22.2
17.9
13.7
27.1
3.3
27.1
25.4
23.5
19.7
15.9
12.1
1050
77
36.0
3.0
24.7
19.1
13.4
-
-
-
32.2
3.3
24.1
18.4
12.6
-
-
-
72
34.4
3.0
27.7
22.6
17.6
12.6
-
-
31.2
3.4
26.2
21.2
16.3
11.4
-
-
67
32.3
3.0
30.6
26.2
21.8
16.8
11.9
-
29.3
3.4
28.2
24.1
20.0
15.2
10.4
-
62
31.0
3.0
30.7
28.4
26.1
21.1
16.1
11.2
28.5
3.3
28.2
26.0
23.7
19.0
14.3
9.7
57
29.6
3.0
29.6
29.6
29.6
25.3
20.4
15.5
27.7
3.3
27.7
27.7
27.4
22.8
18.3
13.7
1200
77
35.6
3.0
27.8
20.3
12.8
-
-
-
31.1
3.3
27.0
19.4
11.8
-
-
-
72
35.4
3.0
30.1
24.1
18.2
12.2
-
-
32.0
3.4
28.4
22.6
16.7
10.8
-
-
67
34.1
3.1
32.3
27.9
23.5
17.6
11.8
-
31.2
3.4
29.8
25.7
21.6
15.9
10.2
-
62
32.4
3.0
32.1
30.5
28.8
23.1
17.3
11.6
29.8
3.3
29.5
28.0
26.5
20.9
15.4
9.9
57
30.6
3.0
30.6
30.6
30.6
28.5
22.8
17.2
28.3
3.3
28.3
28.3
28.3
26.0
20.6
15.3
1350
72
36.4
3.0
32.5
25.6
18.7
11.8
-
-
32.8
3.4
30.7
23.9
17.1
10.3
-
-
67
36.0
3.1
34.1
29.6
25.1
18.4
11.7
-
33.1
3.4
31.4
27.3
23.1
16.5
10.0
-
62
33.8
3.0
33.6
32.6
31.5
25.0
18.5
12.0
31.0
3.4
30.8
30.0
29.2
22.8
16.5
10.1
57
31.6
3.0
31.6
31.6
31.6
31.6
25.3
19.0
28.9
3.3
28.9
28.9
28.9
28.9
23.0
16.8
1500
72
37.4
3.1
34.9
27.1
19.2
11.4
-
-
33.6
3.4
-
25.2
17.4
9.7
-
-
67
37.8
3.1
35.8
31.3
26.7
19.2
11.6
-
35.1
3.4
-
28.8
24.7
17.2
9.7
-
62
35.2
3.0
35.0
34.6
34.3
27.0
19.7
12.4
32.3
3.4
-
32.0
31.9
24.7
17.5
10.3
57
32.6
3.0
32.6
32.6
32.6
32.6
27.8
20.7
29.6
3.3
-
29.6
29.6
29.6
25.3
18.4
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT037 high speed compressor (3.0 ton) (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F)
Return dry bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65