5188236-BIM-A-0316
70
Johnson Controls Unitary Products
Figure 30: Unit Control Board
W1
W2
Y1
G
Y2
OCC
C
SD-24
THERMOSTAT
WIRED HERE
{
R
X
Table 32: Simplicity SE UCB Details
Description
Function & Comments
Terminal Directional orientation: viewed with silkscreen labels upright
Limit, 24 VAC power and shutdown connections from unit wiring harness at left on upper edge of UCB
LIMIT
Monitored 24 VAC input through heat section limit
switch(es)
If voltage is absent, indicating the heat section is over-
temperature, the UCB will bring on the indoor blower
C
24 VAC, 75 VA transformer Common referenced
to cabinet ground
Connects through circuit traces to thermostat connection strip C
and indoor blower VFD pin C
24V
24 VAC, 75 VA transformer hot
Powers the UCB microprocessor, connects through circuit trace
to the SD 24 terminal
SD 24
24 VAC hot out for factory accessory smoke
detector, condensate overflow and/or user
shutdown relay switching in series
Connects through circuit trace to thermostat connection strip
SD-24. A wiring harness jumper plug connecting SD 24 to SD R
is in place if factory accessories for unit shutdown are not used -
this jumper plug must be removed if the switching of field-added
external accessories for unit shutdown are wired between
thermostat connection strip SD-24 and R
SD R
24 VAC hot return from factory accessory smoke
detector, condensate overflow and user shutdown
relay switching in series
Connects through circuit trace to the R terminal on the upper left
of the board