SECTION 4 - INSTALLATION
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
FIGURE 14 -
SINGLE POINT POWER WIRING
Minimum Circuit Ampacity (MCA),
Minimum/Maximum Fuse Size and
Minimum/Maximum Circuit Breaker size
varies on chillers based upon model and
options ordered. Consult YorkWorks or
the chiller data plate for electrical data
on a specific chiller.
Voltage Utilization Range
RATED
VOLTAGE
UTILIZATION RANGE
200/60/3
180-220
230/60/3
208-254
380/60/3
342-402
400/60/3
360-440
460/60/3
414-508
575/60/3
520-635
400/50/3
360-440
LD18588
POWER SUPPLY WIRING
Single Point Wiring