SECTION 9 - MAINTENANCE
JOHNSON CONTROLS
177
Form 201.28-NM1.1
Issue date: 08/06/2021
9
Chilled liquid and suction temperature sensor input voltage
Table 30 -
Temperature input voltage sensor (Measured signal to shield at the sensor)
Temperature ºF
(°C)
Voltage
Temperature °F
(°C)
Voltage
Temperature °F
(°C)
Voltage
16.1 (-8.8)
1.52
35.9 (2.2)
2.19
55.6 (13.1)
2.85
16.7 (-8.5)
1.54
36.5 (2.5)
2.21
56.3 (13.5)
2.87
17.3 (-8.2)
1.56
37.0 (2.8)
2.23
56.9 (13.8)
2.89
17.9 (-7.8)
1.58
37.6 (3.1)
2.25
57.5 (14.2)
2.91
18.5 (-7.5)
1.60
38.2 (3.4)
2.27
58.1 (14.5)
2.93
19.1 (-7.2)
1.62
38.7 (3.7)
2.29
58.7 (14.8)
2.95
19.7 (-6.8)
1.64
39.3 (4.1)
2.30
59.4 (15.2)
2.97
20.3 (-6.5)
1.66
39.9 (4.4)
2.32
60.0 (15.6)
2.99
20.9 (-6.2)
1.68
40.4 (4.7)
2.34
60.6 (15.9)
3.01
21.5 (-5.8)
1.70
41.0 (5.0)
2.36
61.3 (16.3)
3.03
22.1 (-5.5)
1.72
41.6 (5.3)
2.38
61.9 (16.6)
3.05
22.7 (-5.2)
1.74
42.1 (5.6)
2.40
62.5 (16.9)
3.07
23.3 (-4.8)
1.76
42.7 (5.9)
2.42
63.2 (17.3)
3.09
23.9 (-4.5)
1.78
43.3 (6.3)
2.44
63.8 (17.7)
3.11
24.5 (-4.2)
1.80
43.9 (6.6)
2.46
64.5 (18.1)
3.13
25.0 (-3.9)
1.82
44.4 (6.9)
2.48
65.1 (18.4)
3.14
25.6 (-3.6)
1.84
45.0 (7.2)
2.50
65.8 (18.8)
3.16
26.2 (-3.2)
1.86
45.6 (7.5)
2.52
66.5 (19.2)
3.18
26.8 (-2.9)
1.88
46.2 (7.9)
2.54
67.1 (19.5)
3.20
27.3 (-2.6)
1.90
46.7 (8.2)
2.56
67.8 (19.9)
3.22
27.9 (-2.8)
1.91
47.3 (8.5)
2.58
68.5 (20.3)
3.24
28.5 (-1.9)
1.93
47.9 (8.8)
2.60
69.2 (20.7)
3.26
29.0 (-1.7)
1.95
48.5 (9.2)
2.62
69.9 (21.1)
3.28
29.6 (-1.3)
1.97
49.1 (9.5)
2.64
70.6 (21.4)
3.30
30.2 (-1)
1.99
49.7 (9.8)
2.66
71.3 (21.8)
3.32
30.8 (-0.7)
2.01
50.3 (10.2)
2.68
72.0 (22.2)
3.34
31.3 (-0.4)
2.03
50.8 (10.4)
2.70
72.7 (22.6)
3.36
31.9 (-0.1)
2.05
51.4 (10.8)
2.71
73.4 (23)
3.38
32.5 (0.3)
2.07
52.0 (11.1)
2.73
74.2 (23.4)
3.40
33.0 (0.6)
2.09
52.6 (11.4)
2.75
74.9 (23.8)
3.42
33.6 (0.9 )
2.11
53.2 (11.8)
2.77
34.2 (1.2)
2.13
53.8 (12.1)
2.79
34.8 (1.5)
2.15
54.5 (12.5)
2.81
35.3 (1.8)
2.17
55.0 (12.8)
2.83