OPERATIONAL LIMITATIONS (ENGLISH)
Temperature and Flows
Excessive flow will cause damage to the
cooler. Do not exceed max. cooler flow.
Special care should be taken when mul-
tiple chillers are fed by a single pump.
NOTE
• For leaving brine temperature below 40°F (4.4°C),
contact your nearest Johnson Controls Office for
application requirements.
• For leaving water temperature higher than 55°F
(12.8°C), contact the nearest Johnson Controls
Office for application guidelines.
• The evaporator is protected against freezing to
-20°F (-28.8°C) with an electric heater as stan-
dard.
• For operation at temperatures below 25°F
(-3.9°C), the optional Low Ambient Kit will need
to be installed.
• For operation at temperatures above 115°F
(46.1°C), the optional High Ambient Kit will need
to be installed on the system.
SECTION 5 – TECHNICAL DATA
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
TABLE 6 -
VOLTAGE LIMITATIONS
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
575-3-60
517
633
Summary of Contents for YLUA0078
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...JOHNSON CONTROLS 42 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 100: ...JOHNSON CONTROLS 100 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 152: ...JOHNSON CONTROLS 152 FORM 150 73 NM1 ISSUE DATE 09 04 2020 THIS PAGE INTENTIONALLY LEFT BLANK...