SECTION 5 – TECHNICAL DATA
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
FIVE FAN UNITS
DIMENSIONS – YLAA0100SE
LD23533
1678 [66.1]
1222 [48.1]
588 [21.1]
3” VICTAULIC INLET
2256 [88.8]
2242 [88.3]
(1497mm (50Hz)
)
1595 [62.8] (60Hz)
FRAME HEIGH
T
2248 [88.5]
OVERALL HEIGHT DEPENDS ON BUILD LOCATION
REFER TO NOTES 5 ADN 6 ABOVE
035-24059-004 REV-E
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
(190mm x 120mm EUROPEAN BUILD)
CONTROL PANEL BOTTOM DETAIL
(28mm EUROPEAN BUILD)
21 [0.8
]
822 [32.4]
254 [10.0]
269 [10.6]
35 [1.4]
35 [1.4]
3” VICTAULIC
OUTLET
3” VICTAULIC
OUTLET
(OPTIONAL HEAT
RECOVERY UNIT)
51.4 [2.02]
686 [27.0]
1276 [50.2]
1753 [69.0]
194 [7.6]
1256 [49.5]
16mm [5/8”]
MOUNTING
HOLES TYP
OVERALL LENGTH
FRAME LENGTH
3022 [119.0]
3245 [127.8]
3696 [145.5]
WATER CONNECTIONS
OVERALL WIDTH
FRAME WIDTH
289 [11.4] 288.0 [11.34]
DIMENSION VARIES BASED
ON CHILLER MODEL SELECTED
OPTIONAL
DISCONNECT SWITCH
(STANDARD ON CE)
561 [22.1]
2795 [110.0]
1669 [65.7]
1132 [44.6]
573 [22.5]
2077 [81.8]
82 [3.2
]
1298mm EUROPEAN BUILD
1177 [46.4]
FIGURE 29 -
FIVE FAN UNITS DIMENSIONS – YLAA0100SE