Mod B solid state starter screen
Figure 48: Mod B solid state starter screen
This screen displays all information pertaining to the Mod “B” Solid State Starter.
Table 71: Display only fields
Field/LED name
Description
Motor Run (LED)
Indicates whether the digital output from the controls is commanding the motor to
run.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit in use. This value could come from a 4 mA to 20 mA, 0 VDC
to 10 VDC, PWM signal, or SC-EQ communication interface, or a locally programmed
value.
Pulldown Demand Time Left
Displays the time remaining in the programmed pulldown period.
Input Power
Displays the kilowatts measured by the Solid State Starter.
KW Hours
Displays the cumulative amount of kilowatts used over time.
Starter Model
Displays the Solid State Starter model that is applied to the chiller. Starter Models are
7L, 14L, 26L or 33L.
Voltage – Phase A, B, C
Displays the 3-phase input line voltage measured by the Solid State Starter.
Current – Phase A, B, C
Displays the 3-phase motor current values measured by the Solid State Starter.
Temperature – Phase A, B, C
Displays the temperatures of the Silicon Controlled Rectifier assemblies.
Note:
For fields requiring access level of SERVICE. Service Technicians must refer to the
OptiView Control Center - Service Instructions (Form 160.76-M1)
for operation instructions and
explanation of all programmable setpoints and displayed values
Model YK Style H Centrifugal Liquid Chillers with OptiView Control Center
82