SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
89
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
2
OVERVIEW
This screen displays information pertaining to a Vari-
able Speed Drive (VSD).
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN. Only displayed if this
option is installed.
Motor Heater (LED)
Indicates whether the optional Motor Heater is ON or
OFF.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value.
Current Limit Setpoint
Displays the current limit value in use. This value
could come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC
or 2 to 10VDC input in Analog Remote mode, PWM
signal in Digital Remote mode, E-Link or SC-EQ com-
munications interface in ISN mode, or a locally pro-
grammed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Output Voltage
Displays the output voltage measured to the motor.
Output Frequency
Displays the present output frequency to the motor.
Input Power
Displays the total kilowatts measured by the VSD or
Harmonic Filter, if installed.
KW Hours
Displays the cumulative amount of kilowatts used over
time as the VSD motor controller operates.
Output Current – Phase A, B, C
Displays the phase current measured to the motor.
Pre-Rotation Vane Position
Displays the Pre-Rotation Vane position as a value be-
tween 0 and 100%.
VARIABLE SPEED DRIVE SCREEN
LD20155
FIGURE 37 -
VARIABLE SPEED DRIVE SCREEN