SECTION 8 – TROUBLESHOOTING
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
167
Causes of insufficient vacuum level of the purge line and countermeasure against
insufficient vacuum levels.
Table 56 -
Insufficient Vacuum Levels
ITEM
CAUSE
COUNTERMEASURE
1
Purge pump trouble.
Contact your local Johnson Controls
Service Office.
2
Deterioration of vacuum pump oil.
Replace the vacuum pump oil.
3
Wrong operation of purging line switching
when the vacuum pump capacity was
checked.
Refrigerant Refining Method on
.
• Confirm that the valve is open or
closed.
4
Deterioration of the vacuum pump belt.
Contact your local Johnson Controls
Service Office.
5
Leakage in purge pipe line.
6
Blocked or dysfunctional purge solenoid
valves.
7
Check valve does not open.
8
Valve V21 mistakenly open.
Refrigerant Refining Method on
.
• Confirm that the valve is open or
closed.