SECTION 7 – MAINTENANCE
When inspecting and maintaining the absorption chill-
er-heater, note the following:
• Never splash water over the electrical parts in-
stalled in the control panel and absorption chiller-
heater.
• Do not change the set values of the control de-
vices and safety switches without permission.
• Do not turn the internal cycle control valve of the
absorption chiller-heater without permission.
• When you replace the oil in the vacuum pump, be
sure to turn OFF the main circuit breaker (MCB1)
in the control panel.
EXHAUST DUCT INSPECTION
Inspect the waste exhaust gas duct periodically to
check for an exhaust gas leak. Failure to do this can
starve the unit of the oxygen it needs to operate safely.
If you smell gas, do NOT operate the ma-
chine or change any of the settings until
the smell goes away. Fire may result.
If you smell gas, do NOT operate the machine or
change any of the settings until the smell goes away.
Fire may result.
VALVE INSPECTION
The chiller-heater is equipped with a refrigerant man-
ual blow valve (V2) that blows refrigerant from the re-
frigerant tank to the absorber.
The valve must not be tampered with or have its set-
tings changed. Daily maintenance and inspection is the
only reason to touch the valve.
During service and maintenance work, be
sure to turn OFF the main circuit breaker
(MCB1). If you do not, injury or electric
shock could occur.
Contact your local Johnson Controls
Service Office for inspection and main
-
tenance of the machine. Improper in-
spection and maintenance can cause a
machine problem or injure workers.
SOLENOID VALVES
The absorption chiller-heater is equipped with the fol-
lowing solenoid valves.
TABLE 18 -
SOLENOID VALVES
SOLENOID VALVE
NAME
SYMBOL
FUNCTION
Purge solenoid valve (1)
SV1
Close vacuum pump
piping
Purge solenoid valve (2)
SV2
Refrigerant blow
solenoid valve
SV3
Close automatic
refrigerant blow
piping
PUMP SHUT OFF VALVES
The chiller-heater is equipped with pump shut off
valves. They are used for inspection of the pumps.
If the absorption chiller-heater is operated with incor-
rect valve settings, the pump may be damaged. Do
NOT adjust these valves.
AIR PURGE VALVES AND DRAIN VALVES
The chiller-heater is equipped with air purge valves
and drain valves for chilled / hot water and cooling
water. They are used to drain the chilled / hot water and
the cooling water. They are also used purge air when
water is supplied.