Compressor 1 or 2 screen
Figure 11: Compressor 1 screen
This screen displays a cutaway of the compressor #1 or #2, revealing the impeller. Animation of
the impeller indicates when the compressor is running. Parameters related to the compressor are
displayed here. Also, compressor manual control functions are performed here. The Pre-rotation
Vanes and Discharge Valve can be manually controlled. This screen also serves as a gateway to
subscreens to calibrate the Pre-rotation vanes and Proximity Probe.
Note:
Requires login access level of SERVICE.
Table 18: Display only fields
Field/LED name
Description
Oil pressure
Displays the pressure differential between the Pump Oil Pressure transducer for
the compressor and the common Sump oil pressure transducer. If either of these
transducers are out of range, the display field will show XX.X psid. The displayed value
includes the offset pressure derived from auto-zeroing during the system pre-lube
period. The offset pressure is the pressure differential between the compressor Pump
Oil Pressure Transducer and the Sump Oil Pressure transducer outputs during a 3-
second period beginning 10 seconds into the system pre-lube period. During this time,
the transducers are sensing the same pressure and their outputs should indicate the
same pressure. As a result, due to accuracy tolerances in transducers, differences
can exist. Therefore, to compensate for differences between transducers and assure
differential pressure sensing accuracy, the offset pressure is subtracted algebraically
from the differential pressure. The offset pressure calculation is not performed if
either transducer is out of range. The offset value is taken as 0 psi in this instance.
If one compressor is already running when bringing on the second compressor, the
offset calculation used will be that which was calculated during the first compressor
pre-lube.
Oil sump temperature
Displays the temperature of the oil sump.
Discharge temperature
Displays the discharge temperature.
High speed thrust bearing proximity
differential
Displays the distance between the high speed thrust collar and the tip of the Proximity
Probe for compressor #1. This measurement takes into account the reference position
established at the time of chiller manufacture.
HGBP command
Indicates the Hot Gas Bypass Command 0% (Closed to 100% (Open). Only displayed if
Hot Gas option is installed and enabled on the Operations screen.
Model YD Mod D with OptiView Control Center
42
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...