Evaporator screen
Figure 7: Evaporator screen
This screen displays a cutaway view of the chiller evaporator. All setpoints relating to the
evaporator side of the chiller are maintained on this screen. Animation of the evaporation process
indicates whether the chiller is presently in a
RUN
condition. Animation of the liquid flow indicates
chilled liquid flow.
Table 7: Display only fields
Field/LED name
Description
Leaving chilled liquid temperature
Displays the temperature of the liquid as it leaves the evaporator.
Entering chilled liquid temperature Displays the temperature of the liquid as it enters the evaporator.
Evaporator small temp difference
Displays the difference between the Leaving Chilled Liquid temperature and the
Evaporator Refrigerant temperature. The Evaporator Refrigerant temperature is
measured by the Refrigerant Temperature sensor input if the sensor is present,
otherwise it is calculated from the Evaporator Saturation temperature.
Evaporator pressure
Displays the present refrigerant pressure in the evaporator.
Evaporator saturation temperature Displays the present saturation temperature in the evaporator.
Evaporator refrigerant temperature Displays the temperature of the refrigerant in the evaporator, if the sensor is present.
Chilled liquid flow switch (open /
closed)
Displays whether the liquid flow is present in the evaporator.
Chilled liquid pump
Displays the command presently sent by the control center to the Chilled Liquid Pump
(RUN or STOP).
Leaving chilled liquid temperature setpoints:
Setpoint
Displays the present setpoint to which the chiller is operating, whether controlled
locally or remotely.
Shutdown
Displays the Leaving Chilled Liquid Temperature at which the chiller will shut down to
avoid overcooling the building. By default this value is 4°F below the Leaving Chilled
Liquid Setpoint, but is adjustable.
Restart
Displays the Leaving Chilled Liquid Temperature at which the chiller will restart after
it has shutdown due to over-cooling temperature. By default, the chiller will restart at
the Leaving Chilled Liquid Temperature Setpoint, but is adjustable.
Model YD Mod D with OptiView Control Center
34
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...