JOHNSON CONTROLS
FORM 150.26-EG1 (116)
6
CONDENSER
The condenser is a cleanable thru-tube type with steel shell, copper tubes, removable
water heads, and includes integral subcooling. The design working pressure of the shell
(refrigerant) side will be 560 PSIG (38.6 bar) and 150 PSIG (10.3 bar) for the tube (liquid)
side. The shell will be constructed and tested in accordance with section Vll, division 1
of the ASME pressure-vessel code. The water side is exempt per paragraph U-1, (C), (6)
of section VlII, division 1 of the ASME pressure-vessel code. The condenser is equipped
with relief valves and will hold the full refrigerant charge for pumpdown. Water connec-
tions are grooved to accept ANSI/AWWA C-606 couplings. Vent and drain connections
are included.
REFRIGERANT CIRCUIT
Two independent refrigerant circuits will be furnished on each unit. All piping will be cop-
per with brazed joints. The liquid line will include: a shutoff valve with charging port; sight-
glass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorp-
tion removable-core filter drier. The entire suction line and the liquid line between the
expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation.
AHRI CERTIFICATION PROGRAM
YORK YCWL chillers have been tested and certified by Air-Conditioning, Heating and Re-
frigeration Institute (AHRI) in accordance with the latest edition of AHRI Standard 550/590
(I-P). Under this Certification Program, chillers are regularly tested in strict compliance
with this Standard. This provides an independent, third-party verification of chiller perfor-
mance. Refer to the AHRI site at
for complete Program Scope, Inclu-
sions, and Exclusions as some options listed herein fall outside the scope of the AHRI
certification program. For verification of certification, go to the AHRI Directory at
Rated in accordance with the latest
issuance of AHRI Standard 550/590
and 551/591.
Equipment Overview (Cont'd)
Summary of Contents for YCWL Series
Page 4: ...JOHNSON CONTROLS FORM 150 26 EG1 116 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 43: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 43 Unit Dimensions Four Compressor Cont d ...
Page 45: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 45 Unit Dimensions Five Six Compressor Cont d ...
Page 47: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 47 Unit Dimensions SI Four Compressor Cont d ...
Page 49: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 49 Unit Dimensions SI Five Six Compressor Cont d ...