FORM 150.63-NM8 (1020)
UNIT CONTROLS
CONDENSER FAN CONTROL - YCUL0045 – YCUL0275
TABLE 24 –
YCUL0045 - YCUL0275 LOW AMBIENT CONDENSER FAN CONTROL –
DISCHARGE PRESSURE CONTROL
When Low Ambient Control of the
fans is selected, fan control will be by
discharge pressure only.
FAN STAGE
ON
OFF
CONTACTOR
I/O BOARD
OUTPUT
FAN #
SYS 1
SYS 2
SYS 1
SYS 2
SYS 1
SYS 2
1
1 FAN REV
DP > Fan Ctrl On Press
DP < Fan Ctrl On Press
– Diff. Press.
7M
10M
TB7-8
TB10-8
1 REV
2 REV
2
1 FAN FWD
DP > Fan Ctrl On Press
+ 20 PSIG (1.38 Bars)
DP < Fan Ctrl On Press.) –
[Diff Press. + 20 PSIG (1.38 Bars)]
8M
11M
TB7-9
TB10-9
3 FWD
4 FWD
3
2 FANS
FWD
DP > Fan Ctrl On Press
+ 40 PSIG (2.76 Bars)
DP < Fan Ctrl On Press.) –
[Diff Press. + 40 PSIG (2.76 Bars)]
8M & 9M
11M &
12M
TB7-9
&
TB7-10
TB10-9
& TB10-10
1 & 3
FWD
2 & 4
FWD
Summary of Contents for YCUL0045E
Page 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Page 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Page 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 141: ......
Page 142: ...NOTES...
Page 143: ...NOTES...