JOHNSON CONTROLS
34
FORM 150.63-NM8 (1020)
INSTALLATION
PHYSICAL DATA (ENGLISH)
YCUL0045E_ - YCUL0275E_
Notes:
1. Pump Down Capacity is based on 100°F (37.8°C) liquid R22 and 80% of condenser volume.
2. Operating Refrigerant Charge is for Condensing Unit only, does not include refrigerant lines and evaporator coil.
Model Number YCUL
0045
0061
0081
0095
0121
0125
0145
General Unit Data
Nominal kW, R-22
44.7
61.5
77.0
93.9
112.9
127.7
140.7
Nominal kW, R-407C
42.9
59.4
74.9
91.4
109.7
123.4
136.8
Number of Refrigerant Circuits
1
1
1
1
1
2
2
Refrigerant Charge, Operating
R-22, ckt1 / ckt2, kg
11.7
13.3
18.7
23.4
24.2
16.4/16.4 19.5/16.4
R-407C, ckt1 / ckt2, kg
11.3
12.8
18.0
22.6
23.3
15.8/15.8 18.8/15.8
Pumpdown Capacity
R-22, ckt1 / ckt2, lbs
19.6
19.6
27.4
41.1
41.1
26.5/26.5 26.5/26.5
R-407C, ckt1 / ckt2, lbs
18.8944 18.8944 26.4136 39.6204 39.6204 25.5/25.5 25.5/25.5
Oil Charge, ckt1 / ckt2, liters
6
6
8
13
12
8/8
8/8
Shipping Weight
Aluminum Fin Coils, kg
930
934
1089
1109
1265
1790
1814
Copper Fin Coils, kg
998
1002
1157
1177
1333
1926
1950
Compressors, scroll type
Compressors per circuit
2
2
2
2
3
2
2
Compressors per unit
2
2
2
2
3
4
4
Nominal kWo per compressor
26
35
46
53
46
35/35
46/35
Condenser
Total Face Area meters
2
4
4
6
6
6
12
12
Number of Rows
2
2
2
3
3
2
2
Fins per m
512
512
512
512
512
512
512
Condenser Fans
Number of Fans total
2
2
2
2
2
4
4
Fan hp/kw
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
2 / 1.4
Fan RPM
950
950
950
950
950
950
950
Number of Blades
3
3
3
3
3
3
3
Total Chiller Airflow l/s
7672
7672
11091
11091
11091
22351
22351
TABLE 11 –
PHYSICAL DATA (METRIC)
Summary of Contents for YCUL0045E
Page 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Page 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Page 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...