SERVICE AND TROUBLESHOOTING
CHECKING INPUTS AND OUTPUTS
DIGITAL INPUTS
Refer to the unit wiring diagram.
All digital inputs are
connected to J13 of the I/O Board. The term “digital”
refers to two states – either on or off. As an example,
when the air proving switch is closed, 30 volts
DC
will
be applied to J13, pin 5 (J13-5) of the I/O Board. If
the air proving switch is open, 0 volts DC will then be
present at J13-5.
Pin 1 of J13 is an
unregulated
30VDC that is the
DC
voltage
source
used to supply the DC voltage to the
various contacts, unit switch, flow switch, etc. This
DC source is factory wired to CTB1, terminal 13. Any
switch or contact used as a digital input would be con-
nected to this terminal, with the other end connecting to
its respective digital input on the I/O Board. Any time a
switch or contact is closed, 30VDC would be applied to
that particular digital input. Any time a switch or con-
tact is open, 0VDC would be applied to that particular
digital input.
Typically, as high as 34VDC could be measured for the
DC voltage on the digital inputs. This voltage is in refer-
ence to ground. The unit case should be sufficient as a
reference point when measuring digital input voltages.
ANALOG INPUTS – Temperature
Refer to the unit wiring diagram
. Temperature inputs are
connected to the I/O Board on plug J6. These
analog
inputs represent varying DC signals corresponding to
varying temperatures. All voltages are in reference to
the unit case (ground). Following are the connections
for the temperature sensing inputs:
Outside Air Sensor
J6-6 = +5VDC
regulated supply to sensor.
J6-9 =
VDC
input signal to the I/O Board.
See Table
29 for voltage readings that correspond to
specific outdoor temperatures.
J6-3 = drain (shield connection = 0
VDC
)
TABLE 29
–
OUTDOOR AIR SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP °F
VOLTAGE
RESISTANCE
TEMP C°
0
0.7
85398
-18
5
0.8
72950
-15
10
0.9
62495
-12
15
1.0
53685
-9
20
1.1
46240
-7
25
1.2
39929
-4
30
1.4
34565
-1
35
1.5
29998
2
40
1.7
26099
4
45
1.8
22673
7
50
2.0
19900
10
55
2.2
17453
13
60
2.3
15309
16
65
2.5
13472
18
70
2.6
11881
21
75
2.8
10501
24
80
2.9
9298
27
85
3.1
8250
29
90
3.2
7332
32
95
3.4
6530
35
100
3.5
5827
38
105
3.6
5209
41
110
3.7
4665
43
115
3.8
4184
46
120
3.9
3759
49
125
4.0
3382
52
130
4.1
3048
54
Summary of Contents for YCUL0045E
Page 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Page 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Page 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Page 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Page 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Page 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Page 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Page 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Page 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Page 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 141: ......
Page 142: ...NOTES...
Page 143: ...NOTES...