JOHNSON CONTROLS
25
FORM 150.62-NM8 (1020)
1
See Electrical Notes and Legend located on page 28.
FIG. 4 – MULTIPLE POINT POWER SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED
DISCONNECT SWITCHES OR CIRCUIT BREAKERS (0090 - 0134)
MULTIPLE POINT POWER SUPPLY CONNECTION –
TERMINAL BLOCK, NON-FUSED DISCONNECT SWITCHES OR
CIRCUIT BREAKERS (0090 - 0134)
The unit evaporator heater uses
120VAC. Disconnecting 120VAC
power from the unit, at or below
freezing temperatures, can result in
damage to the evaporator and unit as
a result of the chilled liquid freezing.
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or
death, the technician should verify
that NO LETHAL VOLTAGES are
present inside the panel AFTER dis
-
connecting power, PRIOR to working
on equipment.
LD07721
Power Panel
Control Panel
Terminal Block1,
NF Disconnect
SW1
or Circuit Breaker1
Terminal Block2,
NF Disconnect
SW2
or Circuit Breaker2
1L1 1L2 1L3
2L1 2L2 2L3
GR
D
GR
D
MICROPANEL
2
L
CTB2
13 14
CTB1
Field Provided Unit Power Supply
Field Provided 120-1-60
Micropanel Power Supply if
Control Transformer not Supplied
Flow Switch
See electrical note 9
Power Panel
Control Panel
Power Panel
Control Panel
Terminal Block1,
NF Disconnect
SW1
or Circuit Breaker1
Terminal Block2,
NF Disconnect
SW2
or Circuit Breaker2
1L1 1L2 1L3
1L1 1L2 1L3
2L1 2L2 2L3
2L1 2L2 2L3
GR
D
GR
D
GR
D
GR
D
GR
D
GR
D
MICROPANEL
2
L
CTB2
2
L
CTB2
13 14
13 14
CTB1
Field Provided Unit Power Supply
Field Provided 120-1-60
Micropanel Power Supply if
Control Transformer not Supplied
Flow Switch
See electrical note 9
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...