SERVICE AND TROUBLESHOOTING
Soft start, Refrigerant Type, and Ex
-
pansion Valve Type MUST be properly
programmed or damage to compres
-
sors and other system components
may result.
Following is a list, in order of appearance:
DATA LOGGING MODE = : DO NOT MODIFY
DATA LOGGING TIMER = : DO NOT MODIFY
SOFT START
REFRIGERANT TYPE
EXPANSION VALVE TYPE
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
The last displays shown on the above list is for the
accumulated run and start timers for each system. All
values can also be changed using the
↑ (UP) and ↓ (DOWN)
arrow keys, but under normal circumstances would not
be advised. After the last start display, the microprocessor
will display the first programmable value under the
PROGRAM key.
Service Mode – Inputs
After entering Service Mode (program UP arrow, UP
arrow
↑↑
then DOWN arrow, DOWN arrow
↓↓)
, all
digital and analog inputs to the I/O Board can be viewed
by pressing the OPER DATA key. After pressing the
OPER DATA key, the UP arrow and DOWN arrow
keys are used to scroll through the analog and digital
inputs.
Following is the order of analog and digital inputs that
will appear when sequenced with the DOWN arrow
key:
ANALOG INPUTS
•
SYS 1 *SUCT PRESSURE
•
UNIT TYPE
•
SYS 1 **DISCH PRESSURE
•
SYS 1*** COOLER INLET REFRIG. TEMP.
•
SYS 2*** COOLER INLET REFRIG. TEMP.
•
SYS 1**** SUCTION TEMP.
•
SYS 2**** SUCTION TEMP.
•
AMBIENT AIR TEMP.
•
LEAVING LIQUID TEMP.
•
RETURN LIQUID TEMP.
•
SYS 2 *SUCTION PRESSURE
•
SYS 2 SPARE
•
SYS 2 **DISCH PRESSURE
•
SYS 1 MTR VOLTS
•
SYS 2 MTR VOLTS
DIGITAL INPUTS
•
PWM TEMP RESET INPUT
•
LOAD LIMIT INPUT
•
FLOW SW / REM START
•
SPARE
•
SINGLE SYSTEM SELECT
•
SYS 1 MP / HPCO INPUT
•
SYS 2 MP / HPCO INPUT
* The suction pressure transducer is optional on YCAL0014 through
YCAL0060. A low pressure switch is standard on these models in
place of the suction transducer.
** The discharge pressure transducer is optional on some models.
*** The cooler inlet refrigerant temp. sensor is on R-407C units
only.
****The suction temp. sensor is on EEV units only.
The analog inputs will display the input connection,
the temperature or pressure, and corresponding input
voltage such as:
This example indicates that the system 1 suction
pressure input is connected to plug 7 - pin 10 (J7-
10) on the I/O Board. It indicates that the voltage is
2.1VDC which corresponds to 81 psig (5.6 bars) suction
pressure.
The digital inputs will display the input connection and
ON/OFF status such as:
This indicates that the flow switch/remote start input is
connected to plug 13 - pin 5 (J13-5) on the I/O Board,
and is ON (ON = +30VDC unregulated input, OFF =
0VDC input on digital inputs).
S Y S 1 S U C T P R J 7 - 1 0
2 . 1 V D C = 8 1 P S I G
F L O W S W / R E M S T A R T
J 1 3 - 5 I S O
N
Summary of Contents for YCAL0014E Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Page 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Page 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Page 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Page 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Page 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Page 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Page 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Page 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Page 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Page 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Page 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Page 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Page 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Page 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Page 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Page 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Page 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Page 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Page 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...