JOHNSON CONTROLS
52
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TEChNICAl DATA
SINGlE POINT FIElD SUPPlIED POWER WIRING
(See FIG. 5)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard),
Non-Fused Disconnect Switch (optional) or Circuit Breaker (optional)).
ELECTRICAL DATA (ENGLISH)
YCAL0012 - 0032
TABLE 10 – YCAL012 - ELECTRICAL DATA (ENGLISH)
Model
Volt/
60 Hz
Min Circuit
Ampacity
(MCA)
Min
Non Fused
Disconnect
Dual Element Fuse
Circuit Breaker
Terminal-
Block Lug
Wire Range
Lug/
Phase
Min
Max
Min
Max
YCAL0012EC
200
52
60
60
70
60
70
#14-2/0
1
230
48
60
60
60
76
60
#14-2/0
1
380
29
30
35
35
35
35
#14-2/0
1
460
24
30
30
30
83
30
#14-2/0
1
575
19
30
25
25
25
25
#14-2/0
1
YCAL0018EC
200
85
100
100
110
100
110
#14-2/0
1
230
79
100
90
110
90
110
#14-2/0
1
380
46
60
60
60
60
60
#14-2/0
1
460
38
60
45
60
45
60
#14-2/0
1
575
31
60
35
40
35
40
#14-2/0
1
YCAL0021EC
200
94
100
110
125
110
125
#14-2/0
1
230
88
100
100
110
100
110
#14-2/0
1
380
51
60
60
70
60
70
#14-2/0
1
460
42
60
50
50
50
50
#14-2/0
1
575
34
60
40
45
40
45
#14-2/0
1
YCAL0025EC
200
127
150
150
175
150
175
#14-2/0
1
230
119
150
150
150
150
150
#14-2/0
1
380
69
100
80
90
80
90
#14-2/0
1
460
58
60
70
70
70
70
#14-2/0
1
575
46
60
50
60
50
60
#14-2/0
1
YCAL0027EC
200
133
150
150
175
150
175
#14-2/0
1
230
124
150
150
150
150
150
#14-2/0
1
380
72
100
80
100
80
100
#14-2/0
1
460
60
100
70
80
70
80
#14-2/0
1
575
48
60
60
60
60
60
#14-2/0
1
YCAL0032EC
200
137
150
175
175
175
175
#14-2/0
1
230
128
150
150
175
150
175
#14-2/0
1
380
74
100
90
100
90
100
#14-2/0
1
460
62
100
70
80
70
80
#14-2/0
1
575
49
60
60
60
60
60
#14-2/0
1
NOTE: Values shown in the table above are for models without optional pump package.
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...