background image

5604542-UIM-B-0419

8

Johnson Controls Ducted Systems

CHARGING WITH GAUGES

All units include a cooling charging chart for cooling. The heating
charging charts in Table 3 through Table 10 in this document use the
chart corresponding to the installed indoor coil. It can also be obtained
at 

www.upgnet.com

 under the Service Application Data section.

Before using gauges, confirm that your gauges are accurate by
comparing the gauges against a calibrated pressure gauge that
has been calibrated against a national standard. If a calibrated
pressure gauge is not available, place a R-410A virgin refrigerant
container in a conditioned space long enough to come to tempera-
ture equilibrium with the surroundings. Then measure the tem-
perature of the air and the pressure of the refrigerant and compare
it to the following table:

:

Before measuring the pressures, use the method above to check the air
flow and then consult the table and match the liquid pressure to that air
flow.

Reference the heat charging charts in Table 3 through Table 10

.

 CAUTION

Refrigerant charging should only be carried out by a qualified air con-
ditioning contractor.

 CAUTION

Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.

!

!

TABLE 2: 

R-410A Saturation Properties

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

Temp 

(°F)

Pressure 

(Psig)

40

119

75

218

110

365

45

130

80

236

115

391

50

143

85

255

120

418

55

156

90

274

125

447

60

170

95

295

130

477

65

185

100

317

70

201

105

341

TABLE 3: 

YHE18 Heat Charging Charts

YHE/TH4/RHP14L18

CF/CM/CU18, AP18B, AE18B, AVC18B, RFCX18B(P,E)

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

450

Liquid Pressure (PSIG)

381

427 472 351 394 436

336

384

432

318

363 409 274

324

375

276

318

361

600

Liquid Pressure (PSIG)

345

389 434 319 355 404

308

354

400

294

338 382 263

308

354

259

300

342

750

Liquid Pressure (PSIG)

309

352 395 286 329 372

281

325

369

270

313 356 251

292

333

243

283

322

-

Suction Pressure (PSIG)

136

111

97

80

59

52

YHE/TH4/RHP14L18

CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24BE

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

450

Liquid Pressure (PSIG)

387

434 480 357 400 444

342

390

439

323

370 416 278

330

381

280

324

367

600

Liquid Pressure (PSIG)

351

396 441 324 361 411

314

360

407

299

344 389 267

313

360

264

306

347

750

Liquid Pressure (PSIG)

315

358 402 291 335 378

286

330

375

275

318 362 256

297

339

247

288

328

-

Suction Pressure (PSIG)

145

119

104

85

63

55

TABLE 4: 

YHE24 Heat Charging Charts 

YHE/TH4/RHP14L24

CF/CM/CU24, AP24B, AE24B, AVC24B, RFCX24B(P,E)

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

600

Liquid Pressure (PSIG)

399

449 498 368 418 467

353

401

449

332

380 427 298

344

389

286

331

375

800

Liquid Pressure (PSIG)

359

407 454 335 366 431

322

358

415

306

352 397 280

323

365

269

312

354

1000

Liquid Pressure (PSIG)

319

365 410 301 348 394

292

337

382

280

324 367 262

302

342

253

293

333

-

Suction Pressure (PSIG)

136

109

96

80

60

52

YHE/TH4/RHP14L24

CF/CM/CU30, AP30, AE30, AVC30, RFCX30B(P,E)

CFM

Ambient Temperature (°F)

60

47

40

30

17

10

Indoor Temperature (°F)

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

60

70

80

600

Liquid Pressure (PSIG)

378

425 472 349 396 443

335

380

426

315

360 405 283

326

369

271

313

356

800

Liquid Pressure (PSIG)

340

385 430 318 347 409

305

339

393

290

333 376 265

306

346

255

295

336

1000

Liquid Pressure (PSIG)

302

346 389 285 329 374

277

320

362

265

307 348 248

286

324

240

278

316

-

Suction Pressure (PSIG)

136

111

97

80

59

52

Summary of Contents for TH4 Series

Page 1: ...2 B 32 42 s Gen2 21 LIST OF TABLES Maximum Minimum Operating Limit Conditions 2 R 410A Saturation Properties 8 YHE18 Heat Charging Charts 8 YHE24 Heat Charging Charts 8 YHE30 Heat Charging Charts 9 YH...

Page 2: ...on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor uni...

Page 3: ...HU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clea...

Page 4: ...taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copper must be used care must be...

Page 5: ...ide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the va...

Page 6: ...place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1...

Page 7: ...e for the indoor unit s static pressure vs CFM or to a curve chart CHARGING THE UNIT The factory charge in the outdoor unit includes enough charge for the unit 15 ft 4 6 m of refrigerant piping and th...

Page 8: ...80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 381 427 472 351 394 436 336 384 432 318 363 409 274 324 375 276 318 361 600 Liquid Pressure PSIG 345 389 434 319 355 404 308 354 400 294...

Page 9: ...58 303 348 1400 Liquid Pressure PSIG 309 351 393 292 336 381 285 332 379 272 315 357 255 299 342 246 290 335 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 CF CM CU42 AE42 AVC42 RFCX42CE C...

Page 10: ...oor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1400 Liquid Pressure PSIG 336 384 433 312 359 406 293 344 395 279 321 364 230 290 349 248 282 316 1600 Liquid Pressure PSIG 320...

Page 11: ...cess panel FIELD CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Sl...

Page 12: ...ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC F...

Page 13: ...ing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST...

Page 14: ...rrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates...

Page 15: ...ur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal d...

Page 16: ...te flash code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will ca...

Page 17: ...OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFOR...

Page 18: ...RAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITCH RV REVERSING VALVE SC START CAPAC...

Page 19: ...LE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCA...

Page 20: ...RICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE...

Page 21: ...TOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITC...

Page 22: ...5604542 UIM B 0419 22 Johnson Controls Ducted Systems NOTES...

Page 23: ...ta Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas pi...

Page 24: ...ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Ch...

Reviews: