background image

5604542-UIM-B-0419

4

Johnson Controls Ducted Systems

GROUND INSTALLATION

The unit may be installed at ground level on a solid base that will not
shift or settle, causing strain on the refrigerant lines and possible leaks.
The unit must be installed in as level a position as possible while main-
taining the clearances shown in Figures 1 & 2.

Normal operating sound levels may be objectionable if the unit is placed
directly under windows of certain rooms (bedrooms, study, etc.).

Condensate will drain from beneath the coil of the outdoor unit during
the defrost cycle. Normally this condensate may be allowed to drain
directly on the ground.

Elevate the unit sufficiently to prevent any blockage of the air entrances
by snow in areas where there will be snow accumulation. Check the
local weather bureau for the expected snow accumulation in your area.

Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.

ROOF INSTALLATION

When installing units on a roof, the structure must be capable of sup-
porting the total weight of the unit, including a pad, lintels, rails, etc.,
which should be used to minimize the transmission of sound or vibra-
tion into the conditioned space.

WALL MOUNT INSTALLATION

Care must be taken to mount the outdoor unit on a solid base that is
sloped to shed water, secure from settlement, and is isolated from the
structural foundation or walls to prevent sound and vibration transmis-
sion into the living space. 

On occasion, site conditions may require direct wall mounted brackets
to be used to locate and support the outdoor unit. In these applications,
care must be taken to address unit base pan support, structural integ-
rity, safe access and serviceability, as well as the possible sound and
vibration transmission into the structure. These applications are best
served by a properly engineered solution. 

UNIT PLACEMENT

1.

Provide a base in the pre-determined location.

2.

Remove the shipping carton and inspect for possible damage.

3.

Ensure that compressor tie-down bolts remain tightened.

4.

Position the unit on the base provided.

LIQUID LINE FILTER-DRIER

The heat pumps have a solid core bi-flow filter/drier located on the liquid
line.

PIPING CONNECTIONS

The outdoor unit must be connected to the indoor coil using field sup-
plied refrigerant grade (ACR) copper tubing that is internally clean and
dry. Units should be installed only with the tubing sizes for approved
system combinations as specified in tabular data sheet. The charge
given is applicable for total tubing lengths up to 15 feet (4.6 m). See
Piping Application Guide  (P/N  247077) for  installing tubing  of  longer
lengths and elevation differences.

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system, or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 3/8” foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight, high temperatures, or excessive humid-
ity must also be insulated.

5.

Tape and suspend the refrigerant lines as shown. DO NOT allow
tube metal-to-metal contact. See Figure 3.

6.

Use PVC piping as a conduit for all underground installations as
shown in Figure 4. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown.

 WARNING

The outdoor unit should not be installed in an area where mud or ice
could cause personal injury. Remember that condensate will drip from
the unit coil during heat and defrost cycles and that this condensate
will freeze when the temperature of the outdoor air is below 32°F.

NOTICE

Heat pumps will defrost periodically resulting in water drainage. The
unit should not be located where water drainage may freeze and cre-
ate a hazardous condition - such as sidewalks and steps.

 CAUTION

Failure to use the same as the original factory drier or using a substi-
tute drier or a granular type may result in damage to the equipment.

NOTICE

Replacements for the liquid line drier must  be  exactly  the  same  as
marked on the original factory drier. See Source 1 for O.E.M. replace-
ment driers.

!

!

R-410A Filter-Drier Source 1 Part No.

Apply with Models

S1-32649682000

All

NOTICE

Using a larger than specified line size could result in oil return prob-
lems. Using too small a line will result in loss of capacity and other
problems caused by insufficient refrigerant flow. Slope  horizontal
vapor lines at least 1" (2.5 cm) every 20 feet (6.1 m) toward the out-
door  unit  to  facilitate  proper  oil  return. If more than the 75 foot line
length is necessary, facilitate proper refrigerant velocity with adjusted
line diameter in accordance with the Piping Application Guide (P/N
247077). 

 CAUTION

This system uses R-410A refrigerant which operates at higher pres-
sures than R-22. No other refrigerant may be used in this system.
Gauge sets, hoses, refrigerant containers, and recovery system must
be designed to handle R-410A. If you are unsure, consult the equip-
ment manufacturer.

 WARNING

Never install a suction-line filter drier in the liquid line of an R-410A
system. Failure to follow this warning can cause a fire, injury or death.

 FIGURE 3:  

Installation of Vapor Line

!

!

$

+$1*(5

/,48,'
/,1(

,1&255(&7

&255(&7

,168/$7('9$325/,1(

7$3(

Summary of Contents for TH4 Series

Page 1: ...2 B 32 42 s Gen2 21 LIST OF TABLES Maximum Minimum Operating Limit Conditions 2 R 410A Saturation Properties 8 YHE18 Heat Charging Charts 8 YHE24 Heat Charging Charts 8 YHE30 Heat Charging Charts 9 YH...

Page 2: ...on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor uni...

Page 3: ...HU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clea...

Page 4: ...taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copper must be used care must be...

Page 5: ...ide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the va...

Page 6: ...place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1...

Page 7: ...e for the indoor unit s static pressure vs CFM or to a curve chart CHARGING THE UNIT The factory charge in the outdoor unit includes enough charge for the unit 15 ft 4 6 m of refrigerant piping and th...

Page 8: ...80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 381 427 472 351 394 436 336 384 432 318 363 409 274 324 375 276 318 361 600 Liquid Pressure PSIG 345 389 434 319 355 404 308 354 400 294...

Page 9: ...58 303 348 1400 Liquid Pressure PSIG 309 351 393 292 336 381 285 332 379 272 315 357 255 299 342 246 290 335 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 CF CM CU42 AE42 AVC42 RFCX42CE C...

Page 10: ...oor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1400 Liquid Pressure PSIG 336 384 433 312 359 406 293 344 395 279 321 364 230 290 349 248 282 316 1600 Liquid Pressure PSIG 320...

Page 11: ...cess panel FIELD CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Sl...

Page 12: ...ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC F...

Page 13: ...ing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST...

Page 14: ...rrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates...

Page 15: ...ur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal d...

Page 16: ...te flash code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will ca...

Page 17: ...OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFOR...

Page 18: ...RAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITCH RV REVERSING VALVE SC START CAPAC...

Page 19: ...LE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCA...

Page 20: ...RICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE...

Page 21: ...TOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITC...

Page 22: ...5604542 UIM B 0419 22 Johnson Controls Ducted Systems NOTES...

Page 23: ...ta Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas pi...

Page 24: ...ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Ch...

Reviews: