5604542-UIM-B-0419

Johnson Controls Ducted Systems

21

 FIGURE 20:  

Wiring Diagram - Three Phase ECM 208/230&460V motor for models (36,42)B(32,42)s Gen2

FIELD WIRING, LINE VOLTAGE

OPTIONAL OR MODEL SPECIFIC

LOW VOLTAGE FACTORY WIRING

HIGH VOLTAGE FACTORY WIRING

               DANGER - SHOCK HAZARD
 
TURN OFF ELECTRICAL POWER BEFORE
SERVICING TO PREVENT POSSIBLE DAMAGE
TO THE EQUIPMENT AND POSSIBLE PERSONAL
INJURY.
 
                              CAUTION
 
TO PREVENT ELECTRICAL SHOCK OPEN
REMOTE DISCONNECT SO ELECTRICAL SUPPLY
TO HEAT PUMP IS SHUT OFF.
 
   COMPONENTS SHOWN IN DASH LINES 
   ARE OPTIONAL.
 
   DUAL CAPACITOR SHOWN.  SEPARATE
   CAPACITORS MAY BE USED ON ACTUAL UNIT.
 
   WIRING MUST CONFORM TO 
   NATIONAL AND LOCAL CODES.
 
   IF ANY OF THE ORIGINAL WIRE SUPPLIED
   WITH THIS UNIT MUST BE REPLACED, IT
   MUST BE REPLACED WITH 105  C
   THERMOPLASTIC OR ITS EQUIVALENT.
 
   WHERE POWER SUPPLY HAS ONE (1) 230
   VOLT CONDUCTOR AND ONE (1) NEUTRAL
   CONDUCTOR, CONNECT L2 OF CONTACTOR
   TO NEUTRAL.

1

2

3

4

5

LEGEND
 
AS  - AMBIENT SENSOR
CAP - CAPACITOR
CC  - CONTACTOR COIL
CCH - CRANKCASE HEATER
HPS - HIGH PRESS SWITCH
HS  - HEATER SWITCH
CS - COIL SENSOR
LPS - LOW PRESS SWITCH
RV  - REVERSING VALVE
SC  - START CAPACITOR
SR  - START RELAY

COLOR CODE
 
BLK - BLACK
BLK/PNK - BLACK w/PINK STRIPE
BLU - BLUE
BRN - BROWN
GRN - GREEN
GRN/YEL - GREEN w/YELLOW STRIPE
GRY - GRAY
ORG - ORANGE
PNK - PINK
PUR - PURPLE
RED - RED
WHT - WHITE
WHT/BRN - WHITE w/BROWN STRIPE
YEL - YELLOW

CCH

RV

SEE UNIT INSTALLATION 

INSTRUCTIONS FOR LOW 

VOLTAGE TERMINATIONS

BLK

BLK

BLU

BLU

WHT

WHT

/BRN

ORG

YEL

RED

BLU

CS

AS

BLK

ORG

HS

5603870-UWD-A-1118

BLK

ORG

HPS

LPS

BLK

BLK

YEL

YEL

BLU OR

BLK/PNK

C  R  O  Y  W  Wout

HPS LPS RV RVG C M COIL AMBIENT

COND FAN

RELAY

DEMAND DEFROST

BOARD

BLU OR

BLK/PNK

S

C

R

FAN MOTOR

6

3

5

PLUG

4

2

1

GRN/YEL

BLU

RED

BLK

BLK

VS

CONTROL

BLU

YEL OR WHT

OR ORG OR PUR

RED

BLU

SLV

SLV

BLK

L3

L1

T3

T1

USE COPPER

CONDUCTORS

ONLY

230/460 VAC 60 Hz

3 PHASE SUPPLY

CC

CONTACTOR

BLK

YEL OR WHT OR ORG OR PUR

BLK

RED

GRY

L2

T2

A2

A1

RED

BLK

BLK

BRN

T1

T3

T2

COMPRESSOR

RED

RED

BLU

Summary of Contents for TH4 Series

Page 1: ...2 B 32 42 s Gen2 21 LIST OF TABLES Maximum Minimum Operating Limit Conditions 2 R 410A Saturation Properties 8 YHE18 Heat Charging Charts 8 YHE24 Heat Charging Charts 8 YHE30 Heat Charging Charts 9 YH...

Page 2: ...on the UPGNET web site Provide adequate structural support for the unit ADD ON REPLACEMENT RETROFIT When this unit is being used as a replacement for an R 410A unit it is required that the outdoor uni...

Page 3: ...HU EUDFH XQGHU FHQWHU RI FRPSUHVVRU 127 QVXUH DGHTXDWH ZDOO VXSSRUW 87 21 6SHFLDO FDUH PXVW EH WDNHQ WR DYRLG UHFLUFXODWLRQ RI GLVFKDUJH DLU WKURXJK RXWGRRU FRLO FIGURE 2 Alternative Installation Clea...

Page 4: ...taken not to damage the couplings or kink the tubing Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary If soft copper must be used care must be...

Page 5: ...ide the grommet back into original position 6 Protect the vapor valve with a wet rag and braze the vapor line con nection to the outdoor unit The nitrogen flow should be exiting the system from the va...

Page 6: ...place on TXV and install liq uid line to the top of the thermal expansion valve Adjust assembly so liquid line aligns with hole in access panel Hand tighten the liq uid line and apply an additional 1...

Page 7: ...e for the indoor unit s static pressure vs CFM or to a curve chart CHARGING THE UNIT The factory charge in the outdoor unit includes enough charge for the unit 15 ft 4 6 m of refrigerant piping and th...

Page 8: ...80 60 70 80 60 70 80 60 70 80 60 70 80 450 Liquid Pressure PSIG 381 427 472 351 394 436 336 384 432 318 363 409 274 324 375 276 318 361 600 Liquid Pressure PSIG 345 389 434 319 355 404 308 354 400 294...

Page 9: ...58 303 348 1400 Liquid Pressure PSIG 309 351 393 292 336 381 285 332 379 272 315 357 255 299 342 246 290 335 Suction Pressure PSIG 136 109 96 80 60 52 YHE TH4 RHP14L35 CF CM CU42 AE42 AVC42 RFCX42CE C...

Page 10: ...oor Temperature F 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 1400 Liquid Pressure PSIG 336 384 433 312 359 406 293 344 395 279 321 364 230 290 349 248 282 316 1600 Liquid Pressure PSIG 320...

Page 11: ...cess panel FIELD CONNECTIONS POWER WIRING 1 Install the proper size weatherproof disconnect switch outdoors and within sight of the unit 2 Remove the screws at the top and sides of the corner cover Sl...

Page 12: ...ton be supplied at all times To see connection diagrams of all UPG equipment the Low Voltage System Wiring document is available online at www upgnet com in the Product Catalog Section INDOOR CUBIC F...

Page 13: ...ing table summarizes the behavior of the control when the two TEST pins are connected More detailed descriptions of the various functions are included in other sec tions of this document TABLE 11 TEST...

Page 14: ...rrangement of the refrigeration circuit within the coil The control may initiate a defrost cycle even when the coil is not completely cov ered with frost This is normal operation The control regulates...

Page 15: ...ur regardless of the liq uid line coil temperature reading The coil does not have to be cold for the unit to be forced into defrost Once the defrost cycle begins the con trol shall follow the normal d...

Page 16: ...te flash code The control will reset the soft lockout condition when any of the follow ing occur after removal of the fault condition 1 Power is cycled to the R or Y inputs of the control This will ca...

Page 17: ...OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON ACTUAL UNIT WIRING MUST CONFOR...

Page 18: ...RAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITCH RV REVERSING VALVE SC START CAPAC...

Page 19: ...LE PERSONAL INJURY TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCA...

Page 20: ...RICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO HEAT PUMP IS SHUT OFF COMPONENTS SHOWN IN DASH LINES ARE OPTIONAL WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES IF ANY OF THE ORIGINAL WIRE...

Page 21: ...TOR CONNECT L2 OF CONTACTOR TO NEUTRAL 1 2 3 4 5 LEGEND AS AMBIENT SENSOR CAP CAPACITOR CC CONTACTOR COIL CCH CRANKCASE HEATER HPS HIGH PRESS SWITCH HS HEATER SWITCH CS COIL SENSOR LPS LOW PRESS SWITC...

Page 22: ...5604542 UIM B 0419 22 Johnson Controls Ducted Systems NOTES...

Page 23: ...ta Venting if applicable Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Location s Connections Per Installation Instructions and Local Codes Gas pi...

Page 24: ...ON OFF or the appropriate Value for the fields that apply to the defrost control board installed Run Time Time and Temperature board only 30 60 or 90 minutes Bonnet Sensor Present HEAT Refrigerant Ch...

Reviews: