SECTION 34 - DIAGNOSTICS AND TROUBLESHOOTING
FORM 160.54-M1
ISSUE DATE: 10/25/2019
JOHNSON CONTROLS
JCI COMPANY CONFIDENTIAL
34
This diagnostic screen is used to analyze the analog and
Digital inputs of the Motor Monitoring Board. The in-
puts are identified by terminal strip and terminal num-
ber. Also, serial communications error statistics are
displayed here. See the description of this board in
of this manual.
ANALOG INPUTS
The voltage level of each Analog Input (as measured
to ground) at the indicated input terminals is displayed
as X.XX VDC.
TB1-2
Motor Winding Phase A
Temperature (50K Ohm thermistor)
TB1-5
Motor Winding Phase B
Temperature (50K Ohm thermistor)
TB1-8
Motor Winding Phase C
Temperature (50K Ohm thermistor)
TB2-11
Not used
TB2-8
Not used
TB2-5
Not used
TB2-2
Not used
TB1-11
Not used
VIBRATION INPUTS
Gain -
Displays the value programmed for the Vibra-
tion Input Gain setpoint for the accelerometer inputs.
The gain can be changed from this screen using the
CHANGE GAIN key. See below.
Vibration -
The accelerometer vibration level input
(as measured to ground) at the indicated terminals is
displayed as XX.X. The vibration values are not in any
particular units of measure. They are relative values.
The larger the number, the greater the magnitude of
vibration.
TB3-2
Motor Bearing Shaft End
Vibration (accelerometer)
TB3-4
Motor Bearing Opposite
Shaft End Vibration (accelerometer)
TB3-6
Not used
TB3-8
Not used
MOTOR MONITORING BOARD DIAGNOSTIC SCREEN
(SOFTWARE VERSION C.OPT.01.22.307 AND LATER)
LD14330
FIGURE 109 -
MOTOR MONITORING BOARD DIAGNOSTIC SCREEN