292
FORM 160.54-M1
ISSUE DATE: 10/25/2019
SECTION 33 - SYSTEM CALIBRATION, SERVICE SETPOINTS, AND RESET PROCEDURES
JCI COMPANY CONFIDENTIAL
JOHNSON CONTROLS
Enter the appropriate chiller/compressor combination
as follows:
1. At the keypad, login at SERVICE access level us-
ing password 1 3 8 0.
2. Select SETPOINTS/SETUP/OPERATIONS Screen.
3. Press the CHILLER STYLE/COMPRESSOR key.
4.
Use ◄ or ► keys to select the appropriate chiller
style/compressor combination. Default is “Style
F/G,H5-8 Compr”.
5. Press ENTER (
) key.
FLOW SWITCH
(Flash memory card version C.MLM.01.08.xxx and later)
Style E (and earlier) chillers are supplied with Paddle
type flow sensors. Style F (and later) chillers are sup-
plied with factory mounted Thermal type flow sensors.
The Paddle type sensors are connected to the I/O Board
115 VAC Digital inputs TB4-12 (evaporator) and TB4-
11 (condenser). The Thermal type sensors are connect-
ed to either J7 or J14 on the microboard, depending on
the vintage of the chiller. On new production chillers
before June 2009, they are provided connected to the
microboard J7 (See
). On new
production chillers after June 2009, they are provided
connected to the microboard J14 (See
In order for the program to read the correct flow sensor
input, the Flow Switch setpoint on the OPERATIONS
Screen must be set appropriately in the procedure be-
low. The correct setting is determined by the software
version and the actual flow sensor connection point to
the OptiView Control Center as follows:
With software version C.OPT.01.20.307 (and earlier),
supplied before June 2009, the selections are ANA-
LOG or DIGITAL. Select ANALOG when the Ther-
mal type flow sensors are connected to the microboard
J7 (See
). Select DIGITAL
when the Paddle type sensors are connected to the I/O
Board TB4 (See
With software version C.OPT.01.21.307 (and later),
supplied after June 2009, the selections are J7, J14 or
TB4. Select J7 when the Thermal type flow sensors
are connected to the microboard J7 (See
). Select J14 when the Thermal type sensors
are connected to the microboard J14 (See
). Select TB4 when the Paddle type sensors
are connected to the I/O Board TB4 (See
) and the Heating Condenser Water Paddle
type flow sensor is connected to the LTC I/O Board J20
(if equipped with the Heat Recovery option; see
).
After the selection is made, the program will read the
flow sensor input at the selected connection point and
ignore the other connection points.
TABLE 31 -
SOFTWARE VERSION C.OPT.01.16.XXX (AND LATER)
CHILLER STYLE/
COMPRESSOR
PROXIMITY
SENSE
OIL
HEATER
OUTPUT*
LEVEL
CONTROL
PERIOD
DEFAULT
FLOW
SWITCH
OIL-VARIABLE
SPEED PUMP
PRESSURE
SETPOINT NOT
ACHIEVED
THRESHOLD*
STANDARD
COASTDOWN
TIME
“Style CDE/GHJ
Compr”
Probe
TB1-34
3.5 sec
Digital
(Paddle Type)
35 psid
Programmable
150-900 sec
“Style E/P Compr”
Limit Switch
TB1-64
10.0 sec
Digital
(Paddle Type)
25 psid
Programmable
150-900 sec
“Style F/G, H5-8
Compr”
Limit Switch
TB1-64
3.5 sec
Programmable
(Analog or
Digital)
35 psid
Programmable
150-900 sec
“Style F/J1-J5H3
Compr” “Style G/
K1-K4 Compr”
Probe
TB1-64
3.5 sec
Programmable
(Analog or
Digital)
35 psid
Programmable
150-900 sec
“Style F and G/
PQH9 Compr”
Limit Switch
TB1-64
10.0 sec
Programmable
(Analog or
Digital)
35 psid
Programmable
150-900 sec
“Style F/J7 Compr”
“Style G/K6-K7
Compr”
Probe
TB1-64
3.5 sec
Programmable
(Analog or
Digital)
35 psid
Programmable
240-900 sec