background image

JOHNSON CONTROLS

13

Form 160.00-N6 

Issue date: 08/27/2021

2

General

These details specify procedures that must be followed 

by the customers' contractor when installing the indus-

trial drive and motor systems. In order to better un-

derstand the reasons for many of the practices that are 

recommended, it is helpful to segregate these practices 

into two separate categories as follows:

•  To protect against the risk of electrical shock or 

burn.

• 

To protect the equipment from fire or other dam

-

age due to ground faults or lightning strikes.

These practices must be followed by the contractor in 

compliance with NEC and other code requirements.

Equipment grounding

•  All metal building structures such as columns, 

floor  beams,  and  similar  structures,  must  be 

grounded by an interconnecting heavy ground ca-

ble  5  in accordance with recommended building 

practices and local codes.

•  All electrical joints and connections to the build-

ing structures must be brazed or exothermic weld-

ed to ensure that the required good electrical and 

mechanical properties do 

not

 deteriorate with the 

passage of time.

•  All panels must be grounded at least one point us-

ing a heavy safety cable  7  . Panels greater than 

15 ft long must be grounded at both ends. The 

ground cable needs to be at least 1/0 AWG for me-

chanical reasons and need not be greater than 500 

MCM. This cable is usually non-insulated.

•  The safety ground cable  7  must be brazed or exo-

thermic welded  7A  to a building steel structure 

that is closest to the panel, preferably within 25 ft.

•  The equipment end  7B  must be bolted or brazed 

to a ground termination point on the panel.

•  The equipment grounding terminal is a copper 

ground bus or stub bus bonded to the panel enclo-

sure using brazing or bolting in such manner that 

the conducting path has a resistance of 0.1 ohm 

or less.

•  The grounding conductors must be capable of 

handling anticipated ground fault currents.

•  There must be a jumper cable 11 across the 

ground bus floor sill between any shipping splits 

and sized the same as the safety ground unless 

otherwise specified.

•  The protective grounding described previously 

for power conversion and control cabinets is also 

required for motors, transformers, and reactors. 

Each of these must have its own grounding con-

ductor going directly to the building ground grid.

Grounding procedure needed to ensure 

electrical noise immunity

•  Installation on a concrete housekeeping pad:

The majority of installations have the MVVSD 

positioned on a concrete housekeeping pad. This 

pad must be level within 1/4 in. end-to-end to pre-

vent flexing of the cabinet sections. It is also criti-

cal that the heavy transformer inside rests equally 

on all four corners of the cabinet structure below 

it. A dedicated grounding conductor is required 

between the upstream feeder and the input power 

lugs in the drive. A dedicated grounding conduc-

tor likewise is required from the output lugs in 

the drive to the chiller motor. There is an internal 

grounding bus within the drive which joins these 

input and output grounding conductors along with 

all cabinet sections of the drive. 

• 

Installation on steel leveling beams or metal floor

-

ing or decking:

• 

Leveling  beams,  steel  mesh,  galvanized 

floor, decking, and similar structures, must 

be installed before placing the equipment. 

These must be connected to the building 

ground system using a brazing or exothermic 

welding process.

•  Grounding leveling beams are not an abso-

lute necessity for satisfactory operation on 

new construction where such beams can be 

provided with little difficulty. For existing 

construction, it usually is more difficult, in 

which case the leveling beams may be dis-

pensed with, provided other grounded struc-

tures such as columns and floor beams are 

within 10 ft of the equipment.

Section 2 - Equipment grounding

Summary of Contents for MVVSD0500RK-80

Page 1: ...stallation Supersedes 160 00 N6 919 Form 160 00 N6 821 Medium Voltage 500 hp to 2500 hp 2300 V 3300 V 4160 V and 6600 V 60 Hz 3300 V and 6600 V 50 Hz Variable Speed Drives for YK YD and YK EP Chiller...

Page 2: ...this document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in que...

Page 3: ...ge to Dissipate To A Safe Level Before Working On Equipment Only Qualified Personnel Should Be Permitted To Operate Or Service This Equipment Disconnect And Lock Out Primary And Control Circuit Power...

Page 4: ...lers It is the responsibility of rigging lifting and operating service personnel to verify the applicability of these documents to the equipment If there is any question regarding the applicability of...

Page 5: ...approval cUL UL and CE Environmental 32 F to 104 F 0 C to 40 C max 95 humidity non condensing 5000 ft 1524 m altitude Vibration 0 5 G or less at 10 Hz to 60 Hz Enclosure NEMA 1 IP20 IEC 529 MVVSD req...

Page 6: ...21 Handling and storage 21 Location 22 Drive lifting and assembly 22 Mounting requirements 23 Mounting 23 Electrical connection 24 Control wiring 24 Power wiring 24 Grounding 25 Oil pump wiring 26 Up...

Page 7: ...GURE 10 Ground bus splice connection 25 FIGURE 11 Oil pump connections 26 TABLE 1 Unit model reference 8 TABLE 2 Oil pump drive power supply 11 TABLE 3 Minimum voltage during start up 12 TABLE 4 Contr...

Page 8: ...0 lb 2 722 kg MVVSD2250RK 80 2300 60 2300 60 2250 494 12 500 lb 5 670 kg 6 000 lb 2 722 kg 222 x 50 x 104 564 x 127 x 264 MVVSD2500RK 80 2300 60 2300 60 2500 561 12 500 lb 5 670 kg MVVSD0500RK 92 3300...

Page 9: ...000 lb 5 443 kgs MVVSD2250RK 94 3300 60 3300 60 2250 345 12 700 lb 5 761 kgs 5 500 lb 2 495 kg 174 x 50 x 104 442 x 127 x 264 MVVSD2500RK 94 3300 60 3300 60 2500 391 13 500 lb 6 123 kgs MVVSD0500RK 8...

Page 10: ...60 2250 274 11 200 lb 5 080 kg 4 500 lb 2 041 kg 164 x 50 x 104 417 x 127 x 264 MVVSD2500RK 95 6600 50 4160 60 2500 310 12 000 lb 5 443 kg MVVSD0500RK 85 6600 60 4160 60 500 62 6 400 lb 2 903 kg 74 x...

Page 11: ...voltage and thecontrol relay with 115 V coil 9 Wire 14AWG copper for one way distance of less than 175 ft Wire 12AWG copper for one way dis tance of more than 175 ft but less than 300 ft 10 The follow...

Page 12: ...3 correspond to phase se quence A B and C 19 Control circuit wiring for 3M condenser wa ter pump motor starter is shown for cooling only application For units with Flash Miniature Card Software Versio...

Page 13: ...of 0 1 ohm or less The grounding conductors must be capable of handling anticipated ground fault currents There must be a jumper cable 11 across the ground bus floor sill between any shipping splits...

Page 14: ...Make sure that elec tronic component damage is avoided during the welding process Keep the welded return path as close as possible to the work position The return path must always be within 3 ft of t...

Page 15: ...JOHNSON CONTROLS 15 Section 2 Equipment grounding Form 160 00 N6 Issue date 08 27 2021 2 Figure 1 Grounding details LD14345 Equipment grounding cont d...

Page 16: ...0 N6 Issue date 08 27 2021 Section 2 Equipment grounding Unit dimensional details 74 in x 44 in x 104 in Figure 2 Unit dimensions 74 in x 44 in x 104 in LD14422 I Input M Motor C Controls C Oil Pump 4...

Page 17: ...ipment grounding Form 160 00 N6 Issue date 08 27 2021 2 Unit dimensional details 122 in x 44 in x 104 in Figure 3 Unit dimensions 122 in x 44 in x 104 in LD14423 I Input M Motor C Controls C Oil Pump...

Page 18: ...6 Issue date 08 27 2021 Section 2 Equipment grounding Unit dimensional details 164 in x 50 in x 104 in Figure 4 Unit dimensions 164 in x 50 in x 104 in LD14424 I Input M Motor C Controls C Oil Pump 46...

Page 19: ...pment grounding Form 160 00 N6 Issue date 08 27 2021 2 Unit dimensional details 174 in x 50 in x 104 in Figure 5 Unit dimensions 174 in x 50 in x 104 in LD14425 I I I Input M Motor C Controls C Oil Pu...

Page 20: ...THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS 20 Form 160 00 N6 Issue date 08 27 2021...

Page 21: ...or s has ample clearance and all of the controls are accessible Failure to remove power factor correction or surge capacitors from the load side of the drive can result in serious damage to the equipm...

Page 22: ...esult in serious electrical failure which is not covered by warranty If the appli cation is greater than 5000 ft 1524 m above sea level the drive must be reviewed as a special quote For ad ditional de...

Page 23: ...onnel must install this equipment Install the unit in a secure upright position in a well ventilated area A noncombustible insulating floor or mat must be provided in the area immediately surrounding...

Page 24: ...d a shielded communications cable The six conduc tors are for the following GND Ground L 120 VAC control power line side 2 120 VAC control power neutral side 24 120 VAC start signal from panel to MVVS...

Page 25: ...lectrode to the MV VSD ground bus or ground terminal 2 If not already provided by the factory a main bonding jumper must be installed from the incoming grounded connector bus neutral to the ground bus...

Page 26: ...tions 24 16 53 L 2 R24 67 68 69 GND See Table 4 Table 5 and Table 6 for wire numbers and termination points for YK YD and YKEP units respectively Table 4 Control and oil pump wire numbers and terminat...

Page 27: ...he MVVSD Check connections Although the equipment and devices have been completely tested at the fac tory a final field check must be made that all elec trical wiring and bus bar connections are corre...

Page 28: ...that the MVVSD and associated field wir ing are free from short circuits and grounds The preferred method is to perform a dielectric test at 2 25 times the nominal system voltage plus 2 000 V This mu...

Page 29: ...osed With all removable barriers in place and all doors closed and latched the devices must be turned on with a firm positive motion Protective devices and switches that are not quick acting must not...

Page 30: ...JOHNSON CONTROLS 30 Form 160 00 N6 Issue date 08 27 2021 NOTES...

Page 31: ...5556 5 6 C range Table 7 SI metric conversion Measurement Multiply English unit By factor To obtain metric unit Capacity Tons Refrigerant Effect ton 3 516 Kilowatts kW Power Horsepower 0 7457 Kilowat...

Page 32: ...Pennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2021 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 N6 821 Issue Date Augus...

Reviews: