102777-YIM-E-0206
Unitary Products Group
131
GAS FURNACE SAFETY FEATURES
COMBUSTION AIR PROVING
Combustion air proving is provided by a pressure switch. As
the motor approaches full speed, this switch closes before
any other circuit or gas component can be energized.
ROLLOUT
Rollout protection is provided by a switch mounted on the
heat shield of each furnace module. The switch senses any
flame or excessive heat in the burner compartment. When
the switch opens, the furnace module is immediately locked
out until there is a break in power to the specific furnace mod-
ule and the manual itch is reset. Note that only the module
with the open rollout switch will be locked out, the remaining
modules will continue to operate although all should be
inspected.
A trip of the rollout switch likely indicates a flue restriction, an
opening in the flue passageway, defective pressure switch or
a loose combustion blower wheel. Corrective action should
be taken accordingly.
MAINTENANCE
NORMAL MAINTENANCE
Periodic maintenance normally consists of changing or clean-
ing filters and (under some conditions) cleaning the main
burners.
FILTERS
Inspect once a month. Replace disposable or clean perma-
nent type as necessary. The dimensional size of the replace-
ment filter must be the same as the replaced filter (Refer to
Table 11).
MOTORS
Outdoor fan motors are permanently lubricated and require
no maintenance. Lubrication, if desired, is to be performed by
a qualified service agency.
Ventor motors are factory lubricated for an estimated 10-year
life.
Indoor Fan Motors - The indoor blower motor features ball-
bearings that do not require periodic lubrication. Periodic
lubrication of the motor bearings can extend the life but is
optional.
To go to bypass mode, the bypass VFD as installed in this
unit must be switched by hand on the front of the bypass
enclosure in the fan cabinet of the rooftop unit. It does not
automatically go to bypass mode if the drive fails.
The switches on the front of the bypass box control its run
mode. For normal running:
•
The ON/OFF rotary power switch must be in the ON
position.
•
The BYPASS/OFF/DRIVE switch S1 should be in the
DRIVE position.
•
The HAND/STOP/AUTO switch S2 should be in the
AUTO position, so that the unit control will properly run
the fan and control the speed.
•
The TEST/NORMAL switch S3 should be in the NOR-
MAL position.
If the drive fails:
•
Switch the BYPASS/OFF/DRIVE switch to BYPASS. If
there is a call for the fan, it will go to full speed.
•
If there are VAV boxes, connect them to the circuit at
TB1/6 and they will be driven open in bypass mode.
Prior to any of the following maintenance proce-
dures, shut off all power to the unit. Failure to do
so could cause personal injury.
Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
Damage can occur if the bearings are over lubri-
cated. Use grease sparingly.
Perform all maintenance operations on the blower
motor with power disconnected from the unit. Do
not attempt to lubricate bearings with the unit in
operation.
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...