background image

5715184-BIM-A-0519

Johnson Controls Ducted Systems

19

Dimensions are those required in Standard ASTM D-3311.

Example:

An 80,000 BTUH furnace requires 32 ft of pipe and five 90º elbows.
Using 2 in. pipe and standard elbows, the total equivalent length is:

This exceeds the 65 ft maximum equivalent length of 2 in. pipe allowed
for that model and is thus not acceptable.

By using sweep elbows, the total equivalent length is:

This is less than the 65 ft maximum equivalent length of 2 in. pipe
allowed for that model and is thus acceptable. 

Alternatively, using 3 in. pipe and standard elbows, the total equivalent
length is:

This is less than the 90 ft maximum equivalent length of 3 in. pipe
allowed for that model and is thus acceptable.

COMBUSTION AIR AND VENT PIPING ASSEMBLY

The final assembly procedure for the combustion air and vent piping is
as follows:

1.

Cut piping to the proper length beginning at the furnace.

2.

Deburr the piping inside and outside.

3.

Chamfer (bevel) the outer edges of the piping.

4.

Dry-fit the vent piping assembly from the furnace to the outside ter-
mination checking for proper fit support and slope.

5.

Dry-fit the combustion air piping assembly checking for proper fit,
support and slope on the following systems:

a.

Sealed combustion air systems from the furnace to the out-
side termination

b.

Ventilated combustion air systems from the furnace to the
attic or crawl space termination

6.

Disassemble the combustion air and vent piping. Apply cement
primer and the cement per the manufacturer’s instructions. Primer
and cement must conform to ASTM D2564 for PVC, or ASTM
D2235 for ABS piping.

7.

All joints must provide a permanent airtight and watertight seal.

8.

Install the combustion air and vent piping such that it has a 1/4 in.
per foot (21 mm/m) grade so that condensate flows back toward the
furnace. Piping must be supported with pipe hangers to prevent
sagging.

9.

Seal around the openings where the combustion air and/or vent
piping pass through the roof or sidewalls.

COMBUSTION AIR/VENTING

 FIGURE 21:  

Elbow Dimensions

TABLE 8: 

Elbow Dimensions

Elbow

A Dimension (Illustrated in Figure 21)

2 in. Standard

2-5/16 in.

3 in. Standard

3-1/16 in.

2 in. Sweep

3-1/4 in.

3 in. Sweep

4-1/16 in.

TABLE 9: 

Equivalent Length of Fittings

Fitting

Equivalent Length

2 in. 90° sweep elbow

5 ft of 2 in. pipe

2 in. 45° sweep elbow

2-1/2 ft of 2 in. pipe

2 in. 90° standard elbow

7 ft of 2 in. pipe

2 in. 45° standard elbow

3-1/2 ft of 2 in. pipe

3 in. 90° sweep elbow

5 ft of 3 in. pipe

3 in. 45° sweep elbow

2-1/2 ft of 3 in. pipe

3 in. 90° standard elbow

7 ft of 3 in. pipe

3 in. 45° standard elbow

3-1/2 ft of 3 in. pipe

4 in. 90° elbow (sweep or standard)

5 ft of 4 in. pipe

4 in. 45° elbow (sweep or standard)

2-1/2 ft of 4 in. pipe

2 in. corrugated connector

10 ft of 2 in. pipe

3 in. corrugated connector

10 ft of 3 in. pipe

4 in. corrugated connector

10 ft of 4 in. pipe

32 ft of 2 in. pipe =

     32 equivalent ft

5 - 90º standard 2 in. elbows = (5 x 7) =

     35 equivalent ft

Total = 

67 equivalent ft of 2 in. pipe

32 ft of 2 in. pipe =

     32 equivalent ft

5 - 90º sweep 2 in. elbows = (5 x 5) =

     25 equivalent ft

Total = 

57 equivalent ft of 2 in. pipe

32 ft of 3 in. pipe =

     32 equivalent ft

5 - 90º standard 3 in. elbows = (5 x 7) =

     35 equivalent ft

Total = 

67 equivalent ft of 3 in. pipe

$

$

$

$

67$1'$5'(/%2:

/21*6:((3(/%2:

$

TABLE 10: 

Combustion Air Intake and Vent Connection Size at Furnace 

(All Models)

FURNACE VENT CONNECTION SIZES

Furnace Input

All

Intake Pipe Size

2 in. (5.1 cm)

Vent Pipe Size

2 in. (5.1 cm)

IMPORTANT:

 Furnace vent pipe connections are sized for 2 in.

(5.1 cm). pipe. Any pipe size change must be made outside the fur-
nace casing in a vertical pipe section to allow proper drainage of
condensate. An offset using two 45º (degree) elbows is required for
plenum clearance when the vent is increased to 3 in. (7.6 cm).

IMPORTANT:

 Accessory concentric vent/intake termination kits

1CT0302 and 1CT0303, and for Canadian applications 1CT0302-
636 and 1CT0303-636 are available and approved for use with
these furnaces. Horizontal sidewall vent terminations kits 1HT0901
and 1HT0902 are also approved for use with these furnaces.

 CAUTION

Solvent cements are flammable and must be used in well-ventilated
areas only. Keep them away from heat, sparks and open flames.
Do not breathe vapors and avoid contact with skin and eyes.

IMPORTANT:

 The vent must be installed with the minimum

required clearances, and must comply with local codes and require-
ments.

!

Summary of Contents for M9E080B12

Page 1: ...Termination 21 Downward Venting 22 Direct Vent Air Intake Connection and Vent Connection 22 Outside and Ambient Combustion Air 23 Attic and Crawl Space Combustion Air Termination 24 Gas Valve 27 Readi...

Page 2: ...The size of the unit must be based on an acceptable heat loss cal culation for the structure ACCA Manual J or other approved meth ods may be used 12 When moving or handling this furnace prior to inst...

Page 3: ...hes etc Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials When outdoor air is used for combustion the combustion air intake duct system...

Page 4: ...r protected to avoid physical damage by vehicles 24 in clearance in front and 18 in on side recommended for service access All furnaces approved for alcove installation FOR FURNACES INSTALLED IN THE C...

Page 5: ...urnace does not operate properly The ducts attached to the furnace plenum must be of sufficient size so the furnace operates at the specified external static pressure and within the air temperature ri...

Page 6: ...wnflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace The duct connec tors are designed to be connected to the rectangular duct under t...

Page 7: ...Filters Downflow furnaces typically are installed with the filters located above the furnace extending into the return air plenum or duct Any branch duct rectangular or round duct attached to the plen...

Page 8: ...ng 7 6 9 17 5 7 6 9 17 5RWDWH YHQW EORZHU HLWKHU ZD IMPORTANT On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be...

Page 9: ...ZQIORZ RPEXVWLRQ LU QOHW DV 3LSH QWU OHFWULFDO QWU RQGHQVDWH UDLQ 2SWLRQDO 5HWXUQ LU XWRXW LWKHU VLGH RU ODGGHG GRRU DGG DSSR LPDWHO DQ DGGLWLRQDO 6833 1 RPEXVWLRQ LU QOHW 5 7851 1 9HQW RQQHFWLRQ 2XWO...

Page 10: ...pples and conventional 90 degree elbow s to enter through the cabinet access holes FIGURE 11 Gas Valve DANGER An overpressure protection device such as a pressure regulator must be installed in the ga...

Page 11: ...be shut off prior to disconnecting the electrical power before proceeding with the conversion WARNING SHOCK HAZARD Turn off electrical supply to furnace WARNING Never use an open flame to check for l...

Page 12: ...thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the w...

Page 13: ...nsate pan is self priming and contains an inter nal trap to prevent flue gas leaking Do not install an external con densate trap IMPORTANT The furnace indoor coil and humidifier drains may be combined...

Page 14: ...taken to prevent the drain line from freezing Failure to provide proper protection from freezing can result in improper operation or damage to the equipment and possible property damage When exposed t...

Page 15: ...I VR WKDW QR VDJJLQJ ORRSV ZLOO FROOHFW DQG KROG FRQGHQVDWH ZKLFK ZLOO FDXVH WKH IXUQDFH WR QRW RSHUDWH 6KRUWHQ SUHVVXUH VZLWFK KRVH 5H URXWH DQG VKRUWHQ SUHVVXUH VZLWFK KRVH 6KRUWHQ UDLQ JXWWHU KRVH...

Page 16: ...KLV SRVLWLRQ 127 0D UHTXLUH WKH ORQJHU KRVH WKDW LV SURYLGHG ZLWK ZLGHU FDELQHWV 0RYH FRQGHQVDWH GUDLQ KRVH WR WKLV SRVLWLRQ 0D H LW HLWKHU VLGH RI WKH FDELQHW 0RYH UDLQ JXWWHU KRVH WR WKLV SRVLWLRQ K...

Page 17: ...ciety for Test ing and Materials ASTM standards D1785 Schedule 40 PVC D2665 PVC DWV F891 PVC DWV Cellular Core D2261 ABS DWV or F628 Schedule 40 ABS Pipe cement and primer must conform to ASTM Standar...

Page 18: ...A 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input BTUH Pipe Size in Max Equivalent Length ft Model Input BTUH Pipe Size in Max Equivalent Leng...

Page 19: ...A Dimension Illustrated in Figure 21 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 in 3 in Sweep 4 1 16 in TABLE 9 Equivalent Length of Fittings Fitting Equivalent Length 2 in 90 sw...

Page 20: ...as supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with local installation c...

Page 21: ...ustion air sec tions in these instructions Follow the instructions for outdoor combus tion air or ventilated combustion air and the instructions for installing the vent system with the vent terminatin...

Page 22: ...imming pool or a location where swimming pool chemicals might be stored Be sure the terminal assembly follows the outdoor clearances listed in Section 1 Outdoor Air Contaminants An unconfined space is...

Page 23: ...n 12 in 30 5 mm of the bottom of the confined space shall communicate directly or by means of ducts with the outdoors crawl spaces or attic spaces 2 One permanent opening commencing within 12 in 30 5...

Page 24: ...eing placed into operation could result in carbon monxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while...

Page 25: ...pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note reading The 2 cubic ft dial provides a more accurate measure...

Page 26: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Page 27: ...ench 3 Turn the electrical and gas supplies back on and with the burners in operation check for gas leakage around the gas valve pressure port using an approved non corrosive gas leak detection fluid...

Page 28: ...ower speed for each model is shown in Table 17 Use of a heating speed other than the default heating blower speed may result in reduced energy efficiency and higher electric utility bills In certain c...

Page 29: ...B High 1418 1390 1364 1333 1304 1281 1246 1205 Medium High 1305 1281 1244 1217 1182 1149 1109 1066 Medium 1139 1112 1071 1035 992 951 908 874 Medium Low 1017 986 948 901 859 819 765 727 Low 885 821 76...

Page 30: ...on air is provided the pressure switch closes and the ignition control provides a 17 second ignitor warm up period The gas valve then opens the gas starts to flow ignition occurs and the flame sensor...

Page 31: ...Flashes and will enter a one hour soft lockout 5 RED FLASHES This fault is indicated if the normally closed rollout switch opens The rollout control is manually reset Check for proper combustion air...

Page 32: ...e memory has been cleared and resumes the normal slow green flash after a five second pause SECTION XI REPLACEMENT PARTS LIST DESCRIPTION MOTOR MOTOR DIRECT DRIVE BLOWER BLOWER COMBUSTION ELECTRICAL C...

Page 33: ...RVICE 5754336 UWD A 0519 Fault Code Retrieval To retrieve fault codes push and release ERROR button on control board The LED will flash the last five error codes beginning with the most recent If ther...

Page 34: ...5715184 BIM A 0519 34 Johnson Controls Ducted Systems NOTES...

Page 35: ...Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control board volts AC Thermos...

Page 36: ...atic in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle...

Reviews: