TECHNICAL GUIDE

ADD - ON COILS

FOR USE WITH SPLIT-SYSTEM

COOLING & HEAT PUMPS

MODELS: GHD, GFD, GFA, GNA, 

GUA & GHA

600 - 2000 CFM     2 - 5 TON COILS

Due to continuous product improvement, specifications 
are subject to change without notice.

Visit us on the web at www.york.com for the most 
up-to-date technical information.

Additional rating information can be found at

www.ariprimenet.org.

HORIZONTAL

G1HD

FULL CASED

MULTI-POSITION

G2FD

UPFLOW UNCASED

G1NA

UPFLOW CASED

G1FA

HORIZONTAL CASED

G1HA

UPFLOW

G1UA

036-21145-003 Rev. A (0403)

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

 

  

 

  

 

Heating

Air Conditioning

R

DESCRIPTION

These cooling and heat pump coils are designed to be
installed with UPG furnaces and to be matched with UPG
cooling and heat pump outdoor units. All coils are available
as sweat-connect models for your convenience and ease of
matching.

Upflow Coils - 

Available in high-capacity models to match

any system and upflow furnace. Models available with factory
installed TXV or orifice metering system.

Multi-Position Coils - 

Available in high-capacity models to

match any system and any multi-position furnace and air
handler. Models available with factory installed TXV or orifice
metering system.

Horizontal Duct Coils - 

Available to match any cooling or

heat pump system and horizontal furnace. Field transition
may be required.

Dedicated Horizontal Cased Coils - 

Available to match

most cooling or heat pump systems and any horizontal gas
furnace or modular air handler. For horizontal application
only. Models available with factory installed TXV or orifice
metering system.

FEATURES

Insulated Cabinet - 

All evaporator coil cabinets are thermally

insulated to prevent sweating.

Internally Clean - 

All evaporator coils are factory leak-

tested, dehydrated, sealed and shipped with a holding
charge.

Durable Finish - 

Coil casings are made of pre-painted steel.

The pre-treated flat galvanized steel provides a better paint to
steel bond, which resists corrosion and rust creep.

Optimum Heat Transfer - 

Using the latest in heat transfer

technology, staggered rows of rifled copper tubes are
mechanically expanded into aluminum fins to provide opti-
mum air to surface contact for ample moisture removal as
well as high performance ratings.

Optional Factory Installed Thermal Expansion Valve -

Provides flexibility to match high efficiency applications at a
lower installed cost.

Yorkmate Refrigerant Control - 

Provides optimum system

performance and the flexibility to match coils with any effi-
ciency level cooling or heat pump system.

ACCESSORIES

Refer to Price Manual for specific model numbers. 

TXV Kits

 - Thermal expansion valve kits are available for

indoor coils to obtain specific system performance.

Horizontal Drain Pan Kits

 - A field installed horizontal drain

pan kit (1HP0623BK or 1HP0628BK) is available for horizon-
tal applications on the multi-position coil. The full cased multi-
position coil is also available with a factory installed horizon-
tal drain pan option.

Summary of Contents for GFA

Page 1: ...le to match most cooling or heat pump systems and any horizontal gas furnace or modular air handler For horizontal application only Models available with factory installed TXV or orifice metering system FEATURES Insulated Cabinet All evaporator coil cabinets are thermally insulated to prevent sweating Internally Clean All evaporator coils are factory leak tested dehydrated sealed and shipped with ...

Page 2: ...8S21 1620 72 99 4 85 5 71 2 56 2 67 79 6 66 8 54 4 41 6 62 62 1 49 4 40 2 33 7 57 53 3 46 7 40 2 33 7 G1FA060S21 T G1FA060S24 T G1UA060S21 G1UA060S24 1850 72 118 7 100 0 81 1 61 5 67 95 0 78 4 61 9 45 4 62 74 0 58 0 45 7 36 7 57 63 6 54 8 45 7 36 7 See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacity T indicates models with factory installed thermal exp...

Page 3: ... 8 67 80 4 67 5 55 0 42 1 62 62 7 49 9 40 7 34 0 57 53 9 47 2 40 7 34 0 G2FD060 S H 24 T 1825 72 119 9 101 0 80 0 62 2 67 96 0 79 2 62 6 45 8 62 74 8 58 6 46 2 37 0 57 64 3 55 4 46 2 37 0 G2FD061 S H 24 T 2000 72 124 8 105 2 85 3 64 7 67 99 9 82 5 65 2 47 7 62 77 9 61 1 48 1 38 6 57 66 9 57 7 48 1 38 6 See Condensing Unit or Heat Pump Technical Guide for Total Cooling Capacity and Sensible Capacit...

Page 4: ...9 9 27 2 24 2 21 0 57 28 1 25 6 22 7 19 8 G1NA036S17J 1200 72 49 3 44 9 39 9 34 7 67 45 4 41 3 36 7 32 0 62 37 2 33 8 30 1 26 2 57 35 0 28 3 28 3 24 6 G1NA036S17L 1200 72 59 9 54 5 48 5 42 6 67 55 1 51 1 44 6 38 9 62 45 2 41 1 36 6 31 9 57 42 5 38 7 34 4 30 0 G1NA036S21C 1200 72 49 3 44 9 39 9 34 7 67 45 4 41 3 36 7 32 0 62 37 2 33 8 30 1 26 2 57 35 0 31 8 28 3 24 6 G1NA042S24W 1400 72 86 7 73 0 5...

Page 5: ...2 1000 0 19 G1HA036H14 T 800 0 21 900 0 25 1150 0 30 1200 0 31 G1HA036H17 T 1000 0 20 1100 0 24 1200 0 27 1300 0 30 G1HA048H21 T 1400 0 25 1500 0 28 1550 0 30 1600 0 33 G1HA060H24 T 1700 0 25 1800 0 28 1850 0 30 1900 0 31 2000 0 34 MODEL AIRFLOW WET COIL CASED A TYPE MULTI POSITION G2FD024 S H 14 T 600 0 10 800 0 19 1000 0 29 G2FD024 S H 17 T 600 0 08 800 0 15 1000 0 23 G2FD035 S H 14 T 800 0 22 1...

Page 6: ...ice 75 G1FA060S21T 90 5 83 3 12 2 24 x 17 5 TXV 75 G1FA060S24 90 5 83 3 12 2 24 x 17 5 Orifice 78 G1FA060S24T 90 5 83 3 12 2 24 x 17 5 TXV 78 G1UA024S14 Cooling Heat Pump Sweat 59 2 92 2 14 2 12 x 17 5 1 x 0 866 3 8 Enhanced Orifice 30 G1UA024S17 59 2 92 2 14 2 12 x 17 5 31 G1UA030S14 65 3 40 2 14 2 12 x 17 5 38 G1UA036S14 73 4 38 2 14 2 18 x 17 5 41 G1UA036S17 73 3 89 2 14 2 16 x 17 5 40 G1UA036S...

Page 7: ...8 5 83 2 14 2 24 x 17 5 TXV 65 G2FD042 S H 21 78 4 86 3 11 2 16 x 17 5 Orifice 62 G2FD042H21T 78 4 86 3 11 2 16 x 17 5 TXV 62 G2FD048 S H 21 84 5 35 3 12 2 22 x 17 5 Orifice 69 G2FD048H21T 84 5 35 3 12 2 22 x 17 5 TXV 69 G2FD048 S H 24 84 5 35 3 12 2 24 x 17 5 Orifice 71 G2FD048H24T 84 5 35 3 12 2 24 x 17 5 TXV 71 G2FD060 S H 24 90 5 83 3 12 2 24 x 17 5 Orifice 79 G2FD060H24T 90 5 83 3 12 2 24 x 1...

Page 8: ...D VAPOR G1FA024S14 T 14 1 2 16 13 3 8 13 1 2 3 8 5 8 G1FA024S17 T 17 1 2 16 16 3 8 16 1 2 3 8 5 8 G1FA030S14 T 14 1 2 18 13 3 8 13 1 2 3 8 3 4 G1FA036S14 T 14 1 2 22 1 4 13 3 8 13 1 2 3 8 3 4 G1FA036S17 T 17 1 2 19 1 2 16 3 8 16 1 2 3 8 3 4 G1FA036S21 T 21 19 1 2 19 7 8 20 3 8 3 4 G1FA048S17 T 17 1 2 28 1 4 16 3 8 16 1 2 3 8 7 8 G1FA048S21 T T 21 24 19 7 8 20 3 8 7 8 G1FA060S21 T 21 28 1 4 19 7 8 ...

Page 9: ...3 3 8 13 1 2 3 8 5 8 G1UA024S17 17 1 2 14 16 3 8 16 1 2 3 8 5 8 G1UA030S14 14 1 2 16 5 8 13 3 8 13 1 2 3 8 3 4 G1UA036S14 14 1 2 19 7 8 13 3 8 13 1 2 3 8 3 4 G1UA036S17 17 1 2 18 3 8 16 3 8 16 1 2 3 8 3 4 G1UA036S21 21 17 7 8 19 7 8 20 3 8 3 4 G1UA048S17 17 1 2 25 5 8 16 3 8 16 1 2 3 8 7 8 G1UA048S21 21 22 5 8 19 7 8 20 3 8 7 8 G1UA060S21 21 26 3 8 19 7 8 20 3 8 7 8 G1UA060S24 24 1 2 26 1 8 23 3 8...

Page 10: ...EFRIGERANT CONNECTIONS A B C D E F G LINE SIZES LIQUID VAPOR G1HD024 28 3 4 24 23 3 4 21 5 8 3 8 5 8 G1HD036 28 3 4 24 23 3 4 21 5 8 3 8 3 4 G1HD048 28 3 4 28 23 3 4 25 5 8 3 8 7 8 G1HD060 34 3 4 28 29 3 4 25 5 8 3 8 7 8 G1HA HORIZONTAL B 19 1 2 25 1 2 A 21 1 2 A C 20 1 4 21 1 2 INLET OPENING INLET OPENING MODEL DIMENSIONS INCHES REFRIGERANT CONNECTIONS A B C LINE SIZES LIQUID VAPOR G1HA024S14 T 1...

Page 11: ...G 3 4 FLANGE MODELS DIMENSIONS INCHES REFRIGERANT CONNECTIONS A B C D E F G QUICK CONNECT LINE SIZE LIQUID VAPOR LIQUID VAPOR G2FD024 S H 14 T 14 1 2 22 23 19 7 8 13 3 8 20 3 16 13 1 2 3 8 5 8 G2FD024 S H 17 T 17 1 2 23 16 3 8 16 1 2 5 8 G2FD035 S H 14 T 14 1 2 23 13 3 8 13 1 2 5 8 G2FD030 S H 17 T 17 1 2 23 16 3 8 16 1 2 5 8 G2FD036 S H 17 T 17 1 2 28 16 3 8 16 1 2 3 4 G2FD036 S H 21 T 21 23 19 7...

Page 12: ...G1NA COIL MODELS DIMENSIONS INCHES REFRIGERANT CONNECTIONS A B C D E F G QUICK CONNECT LINE SIZE LIQUID VAPOR LIQUID VAPOR G1NA024S17G 16 1 4 19 7 8 14 5 8 3 8 3 4 G1NA030S17H 16 1 4 15 3 4 3 4 G1NA030S17K 16 1 4 17 7 8 3 4 G1NA036S17J 16 1 4 19 5 8 3 4 G1NA036S17L 16 1 4 19 7 8 7 8 G1NA036S21C 19 3 8 19 1 8 3 4 G1NA042S24W 21 3 8 20 3 8 23 7 8 7 8 G1NA048S21D 19 3 8 19 7 8 19 3 8 7 8 G1NA060S24T ...