343615-YTG-A-0807

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE

AIR CONDITIONERS

DY 036, 048 & 060

3, 4 & 5  NOMINAL TONS

14.00 SEER

®  

TECHNICAL GUIDE

DESCRIPTION

YORK Sunline Magnum

™ 

units are convertible single pack-

age air conditioners with a common cabinet and a common 
roof curb for the 3, 4 and 5 ton sizes. The units were 
designed for light commercial and commercial applications. 
They can easily be installed on a roof curb, slab, roof jack or 
frame.

All units include:

Powder Paint finish that meets ASTM-B-117 1000 hour 
salt spray standards

Permanently lubricated motors

Bottom or side air discharge configuration capability 
(field convertible)

Manufactured under the quality standards of ISO9001

Simplicity

® 

Control Board

Copper tube/aluminum fin coils

Easy access to all components

Rigging holes in base rails for lifting

Fork lift slots on three sides

Single point power connection

Complete factory package - tested, charged and wired

CSA agency listing on all units

WARRANTY

Factory Limited Parts Warranty

One-year parts warranty

A Five-year parts warranty on the compressor and
electric heat elements.

Ten-year parts warranty on the gas-fired heat
exchangers.

Summary of Contents for DY 036

Page 1: ...rame All units include Powder Paint finish that meets ASTM B 117 1000 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactured under the quality standards of ISO9001 Simplicity Control Board Copper tube aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three...

Page 2: ... LEVELS HORIZONTAL DUCTED INLET 10 Tbl Pg 9 DY048 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED DISCHARGE 10 10 DY048 INDOOR SOUND POWER LEVELS VERTICAL DUCTED INLET 11 11 DY048 INDOOR SOUND POWER LEVELS VERTICAL DUCTED DISCHARGE 11 12 DY060 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED INLET 12 13 DY060 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED DISCHARGE 12 14 DY060 INDOOR SOUND POWER LEVELS VERTIC...

Page 3: ...X Options 3 5 Y Options 4 5 Z Options 3 4 5 1 Disconnect 2 Non Pwr d Conv Outlet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options SS Drain Pan Configuration Options not required for all units These four digits will not be assigned until a quote is requested or an order placed CPC Controller DFS APS Johnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS AP...

Page 4: ...oard monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat units The unit control board will alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection To prevent nuisance trouble calls the control board uses a three strikes you re out philosophy The high and low pressure swi...

Page 5: ...atures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed 2 pleated filters are offered as a factory installed option CONVENIENCE OUTLET This 110 volt outlet can be powered by the unit with a stepdown transformer or the unit may be ordered with a non powered convenience outlet that can be wired in the field DISCONNECT SWITCH For gas heat units and cooling units with elec...

Page 6: ...full stainless steel heat exchanger assembly STAINLESS STEEL DRAIN PAN An optional rust proof stainless steel drain pan is available to provide years of trouble free operation in corrosive environ ments BOTTOM DRAIN CONNECTION An optional bottom drain connection is available for inside the curb connec tions for applications in cold environments to reduce freezing drain lines PHASE MONITORS Designe...

Page 7: ...to convert a single enthalpy economizer to dual enthalpy BURGLAR BARS Mount in the supply and return openings to prevent entry into the duct work FLUE EXHAUST EXTENSION KIT In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes CO2 SENSOR Sens...

Page 8: ...high x 8 ft long 0 30m x 0 46m x 2 44m Cooling Operation2 dB ID Blower Only dB Cooling Operation2 dB ID Blower Only dB TABLE 5 DY036 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 80 84 80 83 85 87 84 87 125 74 77 74 76 80 82 80 83 250 58 61 58 61 68 68 63 65 500 48 51 47 ...

Page 9: ...Blower Only dB 0 36 0 33 0 71 0 49 1069 870 1903 917 0 2 0 3 0 2 0 7 632 632 881 883 DY036 3 Ton Vertical Ducted Inlet TABLE 7 DY036 INDOOR SOUND POWER LEVELS VERTICAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 80 83 80 83 83 86 82 85 125 78 79 77 78 80 83 79 82 250 55 60 54 59 63 63 58 62 500 48 51 46 50...

Page 10: ... with reverberation room wall 5 Duct end sound reflection correction 11 6 3 1 0 0 0 0 dB at 63 125 250 500 1k 4k 8k Hz TABLE 9 DY048 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 77 97 75 95 84 91 82 91 125 72 86 69 85 81 83 78 80 250 60 62 57 59 71 71 66 67 500 53 56 49 ...

Page 11: ...high x 8 ft long 0 30m x 0 46m x 2 44m Cooling Operation2 dB ID Blower Only dB Cooling Operation2 dB ID Blower Only dB TABLE 11 DY048 INDOOR SOUND POWER LEVELS VERTICAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 78 95 77 93 85 92 82 91 125 73 84 72 82 84 87 78 82 250 56 58 53 56 68 68 60 61 500 51 54 48 5...

Page 12: ... with reverberation room wall 5 Duct end sound reflection correction 11 6 3 1 0 0 0 0 dB at 63 125 250 500 1k 4k 8k Hz TABLE 13 DY060 INDOOR SOUND POWER LEVELS HORIZONTAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 82 87 79 88 88 89 82 87 125 75 76 72 74 82 83 78 78 250 69 69 66 66 79 79 73 73 500 64 64 60...

Page 13: ...high x 8 ft long 0 30m x 0 46m x 2 44m Cooling Operation2 dB ID Blower Only dB Cooling Operation2 dB ID Blower Only dB TABLE 15 DY060 INDOOR SOUND POWER LEVELS VERTICAL DUCTED DISCHARGE UNIT DESCRIPTION MODEL CONFIGURATION Indoor Blower Speed RPM Blower Static Pressure IWG Airflow CFM Blower Motor BHP 63 83 88 82 88 91 91 85 88 125 78 78 75 76 85 85 79 79 250 66 67 62 62 77 78 70 72 500 59 60 54 5...

Page 14: ...28 2 9 28 28 27 24 21 18 15 1200 72 41 2 7 26 23 19 16 12 37 2 9 25 21 18 14 11 67 37 2 7 33 30 26 23 19 16 12 33 2 8 31 28 24 21 17 14 10 62 32 2 7 32 32 32 29 25 22 18 29 2 9 29 29 29 25 22 18 15 57 32 2 7 32 32 32 29 25 22 18 29 2 9 29 29 30 26 23 19 16 1350 72 41 2 7 28 24 20 16 12 37 3 0 27 23 19 15 11 67 37 2 7 35 31 27 23 19 15 11 33 2 9 32 29 25 21 17 13 9 62 32 2 7 32 32 32 28 24 20 16 29...

Page 15: ... 35 31 27 23 19 1600 72 54 3 4 35 30 26 21 16 49 3 7 33 28 24 19 14 67 49 3 4 45 40 35 31 26 21 17 43 3 7 41 37 33 28 24 19 14 62 44 3 3 44 44 44 39 35 30 25 39 3 6 39 39 39 34 30 25 20 57 43 3 3 43 43 43 39 34 29 25 39 3 6 39 39 39 34 29 25 20 1800 72 53 3 4 38 33 27 22 17 49 3 7 36 31 25 20 15 67 48 3 4 46 43 38 32 27 22 16 43 3 7 42 39 35 30 24 19 14 62 44 3 3 44 44 44 38 33 28 22 39 3 6 39 39 ...

Page 16: ...43 4 37 6 31 7 25 9 20 1 67 62 5 4 7 57 2 51 4 45 5 39 7 33 9 28 1 22 2 58 3 5 3 55 1 49 3 43 4 37 6 31 8 25 9 20 1 62 57 6 4 7 57 6 57 6 56 3 50 4 44 6 38 8 32 9 53 9 5 3 53 9 53 9 53 7 47 9 42 1 36 2 30 4 57 55 9 4 7 55 9 55 9 57 9 52 1 46 2 40 4 34 6 52 8 5 3 52 8 52 8 54 6 48 8 43 0 37 1 31 3 2250 72 68 5 4 8 49 3 42 6 36 0 29 3 22 7 64 2 5 4 47 1 40 5 33 9 27 2 20 6 67 62 8 4 8 60 1 55 0 48 4...

Page 17: ... coil 1 filters and the heat exchangers Refer to STATIC RESISTANCES Table for resistance values 2 Side Duct application 230 Volts TABLE 20 SUPPLY AIR BLOWER PERFORMANCE DY036 048 060 DIRECT DRIVE BOTTOM DUCT APPLICATION UNIT TONNAGE MOTOR SPEED AVAILABLE EXTERNAL STATIC PRESSURE IWG1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS...

Page 18: ... 3 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 0 30 ELECTRIC HEATERS1 7 15KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 0 19 0 22 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 23 0 26 COOLING ONLY2 0 08 0 10 0 12 0 14 0 16 0 18 0 20 0 23 0 26 0 29 0 32 TABLE 22 ELECTRIC HEATER CFM LIMITATIONS UNIT MODEL SIZE NOMINAL TONS VOLTAGE MINIMUM SUPPLY AIR CFM HEATER SIZE NOMINAL KW 5 7 10...

Page 19: ...11 7 15 2CE045107462 6 8 8 2 15 2 20 2CE045110462 10 1 12 1 20 2 20 2CE045115462 13 6 16 4 25 4 25 2CE045120462 19 5 23 5 34 3 35 575 3 60 3 2 26 0 1 3 8 0 0 0 None 8 2 15 2CE04511058 10 6 10 2 16 7 20 2CE04511558 15 9 15 3 23 1 25 2CE04512058 21 2 20 4 29 5 30 DY048 208 1 60 15 4 86 0 2 3 10 6 0 0 None 32 2 40 2CE04510506 4 0 19 2 37 3 45 2CE04510706 5 6 26 9 46 9 50 2CE04511006 8 0 38 5 61 3 70 ...

Page 20: ...2CE04511025 8 0 22 2 41 0 45 2CE04511525 11 9 33 0 54 5 60 2CE04512025 15 9 44 1 68 4 70 2CE04513025 22 2 61 6 90 3 100 230 3 60 17 3 123 0 2 3 10 6 0 0 None 34 5 35 2CE045105252 5 3 12 7 34 5 35 2CE045107252 7 5 18 0 35 8 40 2CE04511025 10 6 25 5 45 1 50 2CE04511525 15 9 38 2 61 1 70 2CE04512025 21 2 51 0 77 0 80 2CE04513025 29 6 71 2 102 3 110 460 3 60 9 6 70 0 1 3 10 6 0 0 None 18 6 20 2CE04510...

Page 21: ... 7 20 2CE045107462 6 8 8 2 21 5 25 2CE045110462 10 1 12 1 26 4 25 2CE045115462 13 6 16 4 31 7 30 2CE045120462 19 5 23 5 40 6 40 575 3 60 3 2 26 0 1 3 8 0 4 0 None 12 4 15 2CE04511058 10 6 10 2 21 7 25 2CE04511558 15 9 15 3 28 1 30 2CE04512058 21 2 20 4 34 5 35 DY048 208 1 60 15 4 86 0 2 3 10 6 10 0 None 42 2 50 2CE04510506 4 0 19 2 49 8 50 2CE04510706 5 6 26 9 59 4 60 2CE04511006 8 0 38 5 73 8 80 ...

Page 22: ...50 2CE04511025 8 0 22 2 53 5 60 2CE04511525 11 9 33 0 67 0 70 2CE04512025 15 9 44 1 80 9 90 2CE04513025 22 2 61 6 102 8 110 230 3 60 17 3 123 0 2 3 10 6 10 0 None 44 5 45 2CE045105252 5 3 12 7 44 5 45 2CE045107252 7 5 18 0 48 3 50 2CE04511025 10 6 25 5 57 6 60 2CE04511525 15 9 38 2 73 6 80 2CE04512025 21 2 51 0 89 5 90 2CE04513025 29 6 71 2 114 8 125 460 3 60 9 6 70 0 1 3 10 6 5 0 None 23 6 25 2CE...

Page 23: ... Fins Per Inch 18 18 18 Face Area Ft 2 17 1 17 1 17 1 COMPRESSOR Quantity 1 1 1 Type Recip Recip Scroll AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2 1 1 1 Total Face Area Ft 2 6 3 6 3 6 3 CHARGE Refrigerant 22 lbs oz 9 4 9 8 11 8 TABLE 26 ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kW CAP MULTI PLIER 208 208 1 00 240 230 0 92 480 460 0 92 600...

Page 24: ...IZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET BACK POSITION COOLING HEATING ELECTRONIC THERMOSTAT MULTI STAGE RH RC Y W G R Y1 W1 C G ADD JUMPER THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER 1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 INCLUDES SUBBASE TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING USE THERMOSTAT 2TH04700224 COOLING HEATING ELECTRONIC THERMOSTAT SI...

Page 25: ...343615 YTG A 0807 Unitary Products Group 25 FIGURE 3 UNIT DIMENSIONS 3 5 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 5 TON COOLING GAS HEAT FRONT VIEW ...

Page 26: ...343615 YTG A 0807 26 Unitary Products Group FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD DETAIL A FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL B ...

Page 27: ...TRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS DOT PLUGS TABLE 29 MINIMUM CLEARANCES LOCATION CLEARANCE Front 24 Cooling Electric Heat 32 Gas Heat Rear 12 Less Economizer 36 With Economizer or Fixed Air Motorized Damper Left Side Filter Access 24 ...

Page 28: ...343615 YTG A 0807 28 Unitary Products Group FIGURE 9 TYPICAL APPLICATIONS ...

Page 29: ...9 85 82 102 106 110 DY036N04 615 141 133 166 175 95 91 88 110 114 118 DY036D06 625 143 135 168 178 96 93 89 111 115 120 DY036N08 635 145 138 171 181 98 94 91 113 117 122 DY036D10 645 148 140 174 184 99 96 92 115 119 124 DY048 Cooling Electric 585 134 127 158 167 90 87 84 104 108 112 DY048 D N 06 635 145 138 171 181 98 94 91 113 117 122 DY048 D N 10 655 150 142 177 187 101 97 94 117 121 125 DY060 C...

Page 30: ...BASIC UNIT DY Cooling Only 575 585 590 DY Gas Electric N04 615 N06 635 N08 635 650 N10 655 660 D06 625 635 640 D10 645 655 660 OPTIONS Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 20 30 kW 28 ACCY Roof Curb 92 Barometric Relief Fixed Air Damper 10 FIGURE 11 ROOF CURB DIMENSIONS ...

Page 31: ...nt and factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test proce dures Units shall be CSA listed classified to ANSI Z21 47 UL 1995 CSA No 236 standards UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non chalking powder...

Page 32: ...s steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25 F Burners shall be of the inshot type constructed of aluminum coated steel and con tain air mixture adjustments All gas piping shall enter the unit cabinet at a single location through either the si...

Page 33: ...pre selected positions regardless of the outdoor air enthalpy Dampers return to the fully closed position when the indoor fan motor is de energized Dampers shall fully close on power loss OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF CURB 14 and 8 high full perimeter curb with wood nailer shipped knocked down BAROMETRIC RELIEF DAMPER Contains a rain hood air inlet screen exhaust damper and mount...

Page 34: ...343615 YTG A 0807 34 Unitary Products Group ...

Page 35: ...343615 YTG A 0807 Unitary Products Group 35 ...

Page 36: ...Subject to change without notice Printed in U S A 343615 YTG A 0807 Copyright 2007 by Unitary Products Group All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 ...