FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE

AIR CONDITIONERS

DM 036, 048, 060 & 072

3, 4, 5 & 6  NOMINAL TONS

10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)

®  

TECHNICAL GUIDE

DESCRIPTION

YORK Sunline 2000™ units are convertible single package 
air conditioners with a common cabinet and a common roof 
curb for the 3, 4, 5 and 6 ton sizes. The units were designed 
for light commercial and commercial applications. They can 
easily be installed on a roof curb, slab, roof jack or frame.

All units include:

Powder Paint finish that meets ASTM-B-117 750 hour 
salt spray standards

Permanently lubricated motors

Bottom or side air discharge configuration capability 
(field convertible)

Manufactured under the quality standards of ISO9001

Simplicity

TM 

Control Board

Copper tube/aluminum fin coils

Easy access to all components

Rigging holes in base rails for lifting

Fork lift slots on three sides

Single point power connection

Complete factory package - tested, charged and wired

CSA agency listing on all units

WARRANTY

Factory Limited Parts Warranty

One-year parts warranty

A Five-year parts warranty on the compressor and
electric heat elements.

Ten-year parts warranty on the gas-fired heat
exchangers.

Summary of Contents for DM 036

Page 1: ...b roof jack or frame All units include Powder Paint finish that meets ASTM B 117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability field convertible Manufactured under the quality standards of ISO9001 SimplicityTM Control Board Copper tube aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork li...

Page 2: ...T DRIVE SIDE DUCT APPLICATION 17 10 SUPPLY AIR BLOWER PERFORMANCE 5 TON BELT DRIVE SIDE DUCT APPLICATION 18 11 SUPPLY AIR BLOWER PERFORMANCE 6 TON BELT DRIVE SIDE DUCT APPLICATION 19 12 SUPPLY AIR BLOWER PERFORMANCE 3 6 TON DIRECT DRIVE 20 13 BELT DRIVE MOTOR AND DRIVE DATA 20 14 STATIC RESISTANCES 21 15 ELECTRIC HEATER CFM LIMITATIONS 21 16 ELECT DATA DM036 048 DIRECT DRIVE WITHOUT POWR D CONVENI...

Page 3: ...P Options 2 4 Q Options 2 3 4 R Options 3 4 S Option 5 T Options 1 5 U Options 1 3 5 V Options 1 4 5 W Options 1 3 4 5 X Options 3 5 Y Options 4 5 Z Options 3 4 5 Options 1 Disconnect 2 Non Pwr d Conv Oultet 3 Smoke Detector S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Additional Options See Next Page Product Generation 1 First Generation Voltage 1 208 230 1 60 2 208 230 3 60 4 460 3 60 5 575 3 60...

Page 4: ...Cond Coils CP CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor CQ CPC Controller DFS APS Technicoat Evap Cond Coils Coil Guard CR CPC Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard DA CPC Controller with Dirty Filter Switch Air Proving Switch Hinged Filter Door Toolless Access Panels DB CPC Controller DFS APS Phase Monitor Hinged Filter Door Toolless Access P...

Page 5: ...Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Hinged Filter Door Toolless Access Panels GG Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Coil Guard Hinged Filter Door Toolless Access Panels GH Honeywell Excel 10 Controller DFS APS Technicoat Cond Coil Phase Monitor Coil Guard Hinged Filter Door Toolless Access Panels GJ Honeywell Excel 10 Controller DFS APS ...

Page 6: ...t Evap Cond Coils NP Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor NQ Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Coil Guard NR Novar ETC 3 Controller DFS APS Technicoat Evap Cond Coils Phase Monitor Coil Guard PA Novar ETC 3 Controller with Dirty Filter Switch Air Proving Switch Hinged Filter Door Toolless Access Panels PB Novar ETC 3 Controller DFS APS Pha...

Page 7: ...ser Coil Phase Monitor Dirty Filter Switch Hinged Filter Door Toolless Access Panels UG Technicoat Condenser Coil Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UH Technicoat Condenser Coil Phase Monitor Coil Guard Dirty Filter Switch Hinged Filter Door Toolless Access Panels UJ Technicoat Evaporator Coil Hinged Filter Door Toolless Access Panels UK Technicoat Evaporator ...

Page 8: ...of cooling and heat Safety Monitoring The control board monitors the high and low pressure switches the freezestats the gas valve if applicable and the temperature limit switch on gas heat units The unit control board will alarm on ignition failures compressor lockouts and repeated limit switch trips Nuisance Trip Protection To prevent nuisance trouble calls the control board uses a three strikes ...

Page 9: ...ss that utilizes Technicoat 10 1TM processes Coating is applied by total immersion of the complete coil for maximum protection ELECTRIC HEATERS wired for single point power sup ply These nickel chromium heater elements are pro vided with limit and automatic reset capability to prevent operation at excessive temperatures FILTER OPTIONS Standard units are shipped with 1 throw away filters installed ...

Page 10: ... fin ished roof These full perimeter curbs meet the require ments of the National Roofing Contractors Association NRCA and are shipped knocked down for field assem bly Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports HIGH ALTITUDE NATURAL GAS Burner orifices and pilot orifices are provided for proper furnace operation a...

Page 11: ... of knowing the details of each system This constitutes and expectation to any specification or guaran tee requiring a dBA value or sound data in any other form than sound power level ratings 2 At a distance of 10 feet from the blower TABLE 2 CAPACITY RATINGS ARI 210 240 1 1 80 67 F Indoor and 95 F outdoor MODEL MBH EER2 2 EER Energy Efficiency Ratio at full load the cooling capacity in Btu s per ...

Page 12: ...0 34 33 29 25 21 17 13 62 33 3 7 33 33 33 29 25 21 17 31 4 0 31 31 31 27 23 19 15 57 34 3 6 34 34 34 30 26 22 18 32 4 0 32 32 32 28 24 20 16 72 39 3 7 27 24 20 17 14 37 4 1 26 23 20 16 13 67 36 3 6 34 30 27 24 20 17 14 34 4 0 33 30 26 23 20 16 13 62 32 3 6 32 32 32 29 25 22 19 30 4 0 30 30 30 27 24 20 17 57 33 3 6 33 33 33 29 26 23 19 31 3 9 31 31 31 27 24 21 17 72 37 3 6 25 22 19 16 13 36 4 1 24 ...

Page 13: ... 45 42 37 32 27 22 17 62 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 26 21 57 43 4 9 43 43 43 38 33 28 23 40 5 4 40 40 40 35 30 25 20 72 53 5 0 36 32 28 23 19 51 5 5 35 31 26 22 17 67 46 4 9 44 40 35 31 26 22 17 44 5 4 44 39 35 30 26 21 17 62 42 4 9 42 42 42 37 33 28 24 39 5 3 39 39 39 35 30 26 21 57 41 4 8 41 41 41 37 32 28 23 39 5 3 39 39 39 34 30 25 21 72 51 5 0 33 29 26 22 18 48 5 5 32 2...

Page 14: ... 50 47 42 36 30 24 18 62 48 5 8 48 48 48 42 37 31 25 44 6 4 44 44 44 38 32 26 20 57 46 5 8 46 46 46 40 35 29 23 42 6 4 42 42 42 36 31 25 19 72 60 6 0 42 37 32 26 21 57 6 6 41 36 30 25 20 67 54 5 8 52 47 41 36 31 25 20 50 6 5 50 45 40 34 29 24 18 62 48 5 7 48 48 48 43 37 32 27 44 6 4 44 44 44 38 33 28 22 57 46 5 8 46 46 46 41 35 30 25 42 6 3 42 42 42 37 32 26 21 72 57 6 0 38 34 29 24 19 53 6 5 37 3...

Page 15: ... 66 61 54 47 40 32 25 62 64 7 0 64 64 64 56 49 42 35 58 7 8 58 58 58 51 43 36 29 57 64 7 0 64 64 64 56 49 42 34 58 7 7 58 58 58 50 43 36 29 72 75 7 1 56 49 43 36 29 76 8 0 55 48 41 34 27 67 70 7 1 68 61 54 48 41 34 27 66 7 9 66 59 52 45 38 32 25 62 64 7 0 64 64 63 56 49 42 35 59 7 8 59 59 59 52 45 38 31 57 64 7 0 64 64 63 56 49 42 35 59 7 7 59 59 58 51 44 37 30 72 73 7 1 52 45 39 33 27 73 7 9 50 4...

Page 16: ...0 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 1700 1600 1500 1400 1055 875 1300 1036 780 1066 850 1200 1011 735 1047 765 1075 800 1100 987 690 1028 720 1060 750 1084 775 1000 963 655 1005 680 1040 695 1068 715 1089 735 900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 0361 2 AVAILABLE EXTERNAL STATIC PRESSURE IWG3 0 90 1 00 1 10 1 20 1 30 1 40 1 50 UNIT SIZE MBH AIR...

Page 17: ...S RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 1900 1085 1210 1800 1064 1145 1102 1180 1700 1040 1075 1081 1115 1121 1140 1600 1020 1005 1060 1050 1100 1085 1500 1003 945 1044 995 1086 1035 1400 982 880 1024 920 1067 965 1107 1000 1300 970 835 1010 870 1053 920 1099 960 1200 953 780 992 815 1034 855 1080 905 0 60 0 70 0 80 AVAILABLE EXTERNAL STATIC PRESSURE IWG3 0 20 ...

Page 18: ...0 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 1385 1155 1425 1190 1475 2000 1100 1285 1133 1340 1169 1385 1205 1445 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 1600...

Page 19: ...TTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 3200 3000 2800 1245 2190 2600 1193 1920 1222 1990 1250 2060 2400 1142 1675 1173 1730 1205 1800 1234 1885 2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600 1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360 0 60 0 70 0 80 AVAILABLE EX...

Page 20: ...4 800 1644 770 1531 710 0721 HI 2101 1260 2000 1205 1914 1155 1830 1110 0361 0481 0 70 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0 90 0 80 1 00 0361 0481 0601 AVAILABLE EXTERNAL STATIC PRESSURE IWG2 0601 0 60 0 20 0 30 0 40 0 50 UNIT SIZE MBH MOTOR SPEED UNIT SIZE MBH MOTOR SPEED 1 Side Duct application 230 460 575 Volts 2 Includes allowances for a wet evaporator coil 1 filters and the heat exchange...

Page 21: ...outdoor air than for 100 return air If the resistance of the return air duct system is less than 0 25 IWG the unit will deliver less CFM during full economizer operation 3 Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables 5 7 10 15 20 30 208 230 1 60 1100 1100 1200 1200 1300 208 230 3 60 1100 1100 1200 1200 1300 460 3 60 1100 1200 1200 13...

Page 22: ...0706 7 5 31 3 45 3 60 2CE04511006 10 6 44 2 61 5 70 2CE04511506 15 9 66 3 89 1 90 2CE04512006 21 2 88 3 116 7 125 NONE 0 0 0 0 25 7 40 2CE045105252 4 0 11 1 25 7 40 2CE04510725 2 5 6 15 5 25 7 40 2CE04511025 8 0 22 2 34 0 40 2CE04511525 11 9 33 0 47 5 50 2CE04512025 15 9 44 1 61 4 70 NONE 0 0 0 0 25 7 40 2CE045105252 5 3 12 7 25 7 40 2CE04510725 2 7 5 18 0 28 8 40 2CE04511025 10 6 25 5 38 1 40 2CE...

Page 23: ... 40 NONE 0 0 0 0 31 7 50 2CE045105252 4 0 11 1 31 7 50 2CE045107252 5 6 15 5 31 7 50 2CE04511025 8 0 22 2 36 3 50 2CE04511525 11 9 33 0 49 8 50 2CE04512025 15 9 44 1 63 7 70 2CE04513025 22 2 61 6 85 5 90 NONE 0 0 0 0 31 7 50 2CE045105252 5 3 12 7 31 7 50 2CE04510725 2 7 5 18 0 31 7 50 2CE04511025 10 6 25 5 40 4 50 2CE04511525 15 9 38 2 56 3 60 2CE04512025 21 2 51 0 72 2 80 2CE04513025 29 6 71 2 97...

Page 24: ...510706 7 5 31 3 48 6 60 2CE04511006 10 6 44 2 64 7 70 2CE04511506 15 9 66 3 92 3 100 2CE04512006 21 2 88 3 119 9 125 NONE 0 0 0 0 24 1 35 2CE04510525 2 4 0 11 1 24 1 35 2CE045107252 5 6 15 5 25 9 35 2CE04511025 8 0 22 2 34 3 35 2CE04511525 11 9 33 0 47 8 50 2CE04512025 15 9 44 1 61 7 70 NONE 0 0 0 0 24 1 35 2CE04510525 2 5 3 12 7 24 1 35 2CE04510725 2 7 5 18 0 29 1 35 2CE04511025 10 6 25 5 38 4 40...

Page 25: ...6 40 NONE 0 0 0 0 29 9 45 2CE045105252 4 0 11 1 29 9 45 2CE045107252 5 6 15 5 29 9 45 2CE04511025 8 0 22 2 34 0 45 2CE04511525 11 9 33 0 47 5 50 2CE04512025 15 9 44 1 61 4 70 2CE04513025 22 2 61 6 83 3 90 NONE 0 0 0 0 29 9 45 2CE045105252 5 3 12 7 29 9 45 2CE04510725 2 7 5 18 0 29 9 45 2CE04511025 10 6 25 5 38 1 45 2CE04511525 15 9 38 2 54 1 60 2CE04512025 21 2 51 0 70 0 70 2CE04513025 29 6 71 2 9...

Page 26: ...7 5 31 3 57 8 70 2CE04511006 10 6 44 2 74 0 80 2CE04511506 15 9 66 3 101 6 110 2CE04512006 21 2 88 3 129 2 150 NONE 0 0 0 0 33 9 45 2CE045105252 4 0 11 1 33 9 45 2CE045107252 5 6 15 5 38 2 45 2CE04511025 8 0 22 2 46 5 50 2CE04511525 11 9 33 0 60 0 70 2CE04512025 15 9 44 1 73 9 80 NONE 0 0 0 0 33 9 45 2CE045105252 5 3 12 7 34 7 45 2CE04510725 2 7 5 18 0 41 3 45 2CE04511025 10 6 25 5 50 6 60 2CE0451...

Page 27: ... NONE 0 0 0 0 41 7 60 2CE045105252 4 0 11 1 41 7 60 2CE045107252 5 6 15 5 41 7 60 2CE04511025 8 0 22 2 48 8 60 2CE04511525 11 9 33 0 62 3 70 2CE04512025 15 9 44 1 76 2 80 2CE04513025 22 2 61 6 98 0 100 NONE 0 0 0 0 41 7 60 2CE045105252 5 3 12 7 41 7 60 2CE04510725 2 7 5 18 0 43 6 60 2CE04511025 10 6 25 5 52 9 60 2CE04511525 15 9 38 2 68 8 70 2CE04512025 21 2 51 0 84 7 90 2CE04513025 29 6 71 2 110 ...

Page 28: ...06 7 5 31 3 61 1 70 2CE04511006 10 6 44 2 77 2 80 2CE04511506 15 9 66 3 104 8 110 2CE04512006 21 2 88 3 132 4 150 NONE 0 0 0 0 34 1 45 2CE04510525 2 4 0 11 1 34 1 45 2CE045107252 5 6 15 5 38 4 45 2CE04511025 8 0 22 2 46 8 50 2CE04511525 11 9 33 0 60 3 70 2CE04512025 15 9 44 1 74 2 80 NONE 0 0 0 0 34 1 45 2CE04510525 2 5 3 12 7 34 9 45 2CE04510725 2 7 5 18 0 41 6 45 2CE04511025 10 6 25 5 50 9 60 2C...

Page 29: ...5 NONE 0 0 0 0 39 9 50 2CE045105252 4 0 11 1 39 9 50 2CE045107252 5 6 15 5 39 9 50 2CE04511025 8 0 22 2 46 5 50 2CE04511525 11 9 33 0 60 0 70 2CE04512025 15 9 44 1 73 9 80 2CE04513025 22 2 61 6 95 8 100 NONE 0 0 0 0 39 9 50 2CE045105252 5 3 12 7 39 9 50 2CE04510725 2 7 5 18 0 41 3 50 2CE04511025 10 6 25 5 50 6 60 2CE04511525 15 9 38 2 66 6 70 2CE04512025 21 2 51 0 82 5 90 2CE04513025 29 6 71 2 107...

Page 30: ...400 3400 3400 CONDENSER COILS Rows Deep 1 1 1 2 Fins Per Inch 16 16 22 16 Face Area Sq Ft 17 1 17 1 17 1 16 7 COMPRESSOR Qty Per Unit Scroll Type 1 1 1 1 AIR FILTERS Quantity Per Unit 15 X 20 X 1 or 2 2 2 2 2 Quantity Per Unit 14 X 25 X 1 or 2 1 1 1 1 Total Face Area sq ft 6 3 6 3 6 3 6 3 CHARGE Refrigerant 22 lbs oz 5 8 6 8 6 8 10 0 TABLE 25 ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAG...

Page 31: ...ECOND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT USE THERMOSTAT 2TH0471024 THERMOSTAT1 TERMINALS UNIT TERMINAL STRIP TB1 24 VOLT TRANSFORMER ADD JUMPER ADD JUMPER 1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 INCLUDES SUBBASE 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER 3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC...

Page 32: ...036 21502 002 A 0303 32 Unitary Products Group FIGURE 3 UNIT DIMENSIONS 3 6 TON COOLING ONLY ELECTRIC HEAT FRONT VIEW FIGURE 4 UNIT DIMENSIONS 3 6 TON COOLING GAS HEAT FRONT VIEW ...

Page 33: ...036 21502 002 A 0303 Unitary Products Group 33 FIGURE 5 UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 UNIT WITH FIXED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD DETAIL A DETAIL B ...

Page 34: ...ING ENTRY See Detail B MOUNTING BRACKET FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS TABLE 28 MINIMUM CLEARANCES LOCATION CLEARANCE Front 24 Cooling Electric Heat 32 Gas Heat Back 12 Less Economizer 36 With Economizer or Fixed Air Motorized Damper Left Side Filter Access 24 Less...

Page 35: ...036 21502 002 A 0303 Unitary Products Group 35 FIGURE 9 TYPICAL APPLICATIONS ...

Page 36: ...TION UNIT TOTAL A B C D E F DM036 Cooling Electric 565 84 83 82 104 105 107 DM036N04 625 93 92 91 115 117 118 DM036N08 635 94 93 92 117 119 120 DM048 Cooling Electric 615 91 90 89 113 115 116 DM048N06 675 100 99 98 124 126 128 DM048N10 685 102 100 99 126 128 129 DM060 Cooling Electric 640 95 94 93 118 119 121 DM060N08 700 104 103 101 129 131 132 DM060N10 710 105 104 103 131 133 134 DM072 Cooling E...

Page 37: ... TON BASIC UNIT DM Cooling Only 565 615 640 720 DM Gas Electric N04 625 N06 675 N08 635 700 775 N10 685 710 785 OPTIONS Economizer 50 Motorized Damper 26 Electric Heater 5 7 kW 18 10 15 kW 23 20 30 kW 28 ACCY Roof Curb 92 Barometric Relief Fixed Air Damper 10 Belt Drive Blower 5 FIGURE 11 ROOF CURB DIMENSIONS ...

Page 38: ... factory tested prior to shipment All unit wiring shall be both numbered and color coded All units the cooling performance shall be rated in accordance with DOE and ARI test procedures Units shall be CSA listed classified to ANSI Z21 47 UL 1995 CSA No 236 standards UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non chalking powdered pain...

Page 39: ...n and redun dant main gas valve Venter wheel shall be constructed of stainless steel for corrosion resistance The heat exchanger shall be of the tubular type constructed of T1 40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25 F Burners shall be of the inshot type constructed of aluminum coated steel and con tain air mixture adjustments All gas p...

Page 40: ...f the conditioned space during normal operation Whenever the indoor fan motor is energized the dampers open up to one of two pre selected positions regardless of the outdoor air enthalpy Dampers return to the fully closed position when the indoor fan motor is de energized Dampers shall fully close on power loss OTHER PRE ENGINEERED ACCESSORIES AVAILABLE ROOF CURB 14 and 8 high full perimeter curb ...