1133391-YIM-A-1014
8
Johnson Controls Unitary Products
Figure 5: Unit 4 Point Load Weight
Figure 6: Unit 6 Point Load Weight
Figure 7: Center of Gravity
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
D
A
C
B
LEFT
FRONT
D
A
C
B
E
F
LEFT
FRONT
X
Y
LEFT
FRONT
Table 2: Weights and Dimensions
Size
(Tons)
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
Shipping Operating
X
Y
A
B
C
D
A
B
C
D
E
F
037
(3)
ZR
887
867
40.3
25.5
205
170
223
269
141
124
110
144
163
185
049
(4)
ZR
900
880
40.9
25.1
202
172
232
273
139
124
112
151
168
187
061
(5)
ZR
887
867
41
25
198
169
230
269
136
122
110
150
166
184
Table 3: ZR037-061 Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping
Operating
Economizer
90
85
Power Exhaust
40
35
Electric Heat
1
49
49
Gas Heat
2
110
110
1. Weight given is for the maximum heater size available (24KW).
2. Weight given is for the maximum number of tube heat exchangers
available (8 tube).