ACCESSORY CONNECTIONS

The furnace control will allow power-switching control of various 
accessories.

ELECTRONIC AIR CLEANER CONNECTION

Two 1/4” (6.4 mm) spade terminals (EAC and NEUTRAL) for electronic
air cleaner connections are located on the control board. The terminals
provide 115 VAC (1.0 amp maximum) during circulating blower 
operation.

HUMIDIFIER CONNECTION

Two 1/4” (6.4 mm) spade terminals (HUM and NEUTRAL) for humidifier
connections are located on the control board. The terminals provide 
115 VAC (1.0 amp maximum) during heating system operation.

A mounting hole is provided on the control panel next to the furnace

control board for mounting a humidifier transformer if required.

SINGLE STAGE THERMOSTAT

If a single stage thermostat is used, the high/low input staging will be
controlled by the furnace control board, using the staging jumper. If the
staging jumper is set to the 10, 15, or 20 position, the furnace will switch
from low fire to high fire after 10, 15, or 20 minutes and will stay in high
fire until the thermostat is satisfied. If  the  staging  jumper  is  left  in  the
OFF  position  and  a  single  stage  thermostat  is  used,  the  furnace  will
only operate at low fire.

SECTION VI: TWINNING

In applications where more heating capacity or more airflow capacity is
needed than what one furnace can deliver, twinning can be used to
make two furnaces operate in tandem (as long as the two furnaces
have the same model number). When two identical furnaces are
installed using the same duct system, it is very important that the two
furnace circulating air blowers operate in unison. If one blower starts
before the second blower, the duct system will become pressurized and
the blower on the second furnace will turn backwards causing the sec-
ond furnace to overheat, resulting in damage to the furnace. Twinning is
used to make two furnaces operate in tandem, using one duct system,
one room thermostat and causing both furnaces to turn on and off
simultaneously.

TWINNING DUCT SYSTEM

Twinned furnaces must only be applied on a common duct system. A
single air supply plenum must be used for both furnaces and coil(s).
Separate plenums and supply ducts systems cannot be utilized. A sin-
gle return air plenum, common to both furnaces must be used. It is sug-
gested that a return platform be utilized, with bottom air entrance into
each furnace. If a side entrance returns system is used, the common
return duct must be divided equally so as to supply each furnace with
an equal amount of return air.

Both furnaces must be identical models in both heating capacity and
CFM capacity. Both furnaces must be operated on the same motor
speed tap. See typical application, Figure 20.

If furnace staging is desired with two furnaces on a common duct,
where the gas burner on the first furnace operates on W1 and the gas
burner on the second furnace operates on W2, then the use of an air-
mixing device in the plenum to mix the air from both furnaces is strongly
recommended. The mixing device must be installed before any ducts
that supply air to occupied spaces. Twinning causes both indoor fans to
operate simultaneously. If a mixing device is not used, any ducts that
are connected down stream from the furnace that operates on W2, will
be supplying cold air in the Heating mode to the occupied spaces
unless W2 is energized.

GAS PIPING

Furnace gas supplies must be provided as specified with these instruc-
tions. Since the furnaces are side by side, with no space between, gas
supplies must enter on the right and left respectively. All gas piping
must be in accordance with the national fuel gas code, ANSI Z223.1,
latest edition, and/or all local code or utility requirements.

TWINNING

In applications where more heating capacity or more airflow capacity is
needed than what one furnace can deliver, twinning can be used to
make two furnaces operate in tandem, using one duct system and one
room thermostat. When one duct system is used for two furnaces, it is
necessary that the two blowers operate in unison. The twinning function
of the board in this furnace ensures that both blowers turn on and off
simultaneously, and operate on the same blower speed.

The control in the furnace has the twinning feature. With this feature, a
wire is connected between the TWIN terminal on one furnace board to
the TWIN terminal on the second furnace board. The board then com-
municates the blower status from one furnace to the other along this
wire. This communication makes the second furnace blower come on at
the same time, and on the same speed, as the first furnace blower. To
ensure stable communication, the common terminal of each control
must be connected.

 WARNING

Before installing the relay and wiring, disconnect electrical power to
both furnaces. Failure to cut power could result in electrical shock or
equipment damage.

 CAUTION

The relay must not be installed in any location where it could be
exposed to water. If the relay has been exposed to water in any way,
it must not be used.

 CAUTION

Twinned furnaces are to be on the same power source or line leg
(phase). Notify the job electrician early so they can properly balance
the electrical load. Failure to do this may result in control voltage
polarity issues. Refer to Rapid Red Flash Fault Code.

!

!

!

 FIGURE 20:  

Typical Twinned Furnace Application

IMPORTANT

When two furnaces are twinned, typical system total airflow will be
approximately 85% of additive individual furnaces, i.e., two 2000 CFM
units will yield a total 3400 CFM.

 CAUTION

If a return duct is connected to only one furnace (with a connection
between the two furnaces) an imbalance in the airflow will occur and
the furnace furthest from the return plenum will overheat.

Vent Pipe

Electrical
Supply

Gas Supply
(Both sides)

1 Coil for
Each Furnace

COMMON

SUPPL

Y

PLENUM

Supply
Air

!

Summary of Contents for TM9T Series

Page 1: ...n 27 Double Vertical Combustion Air Intake and Vent Termination 27 Downward Venting 27 Direct Vent Air Intake Connection and Vent Connection 27 Combustion Airflow Path Through The Furnace Casing 28 Ambient Combustion Air 29 Attic and Crawl Space Combustion Air Termination 30 Gas Valve 33 Reading Gas Pressure 34 Furnace Control Board 34 Wiring Diagram 39 LIST OF TABLES Unit Clearances to Combustibl...

Page 2: ... to installation always leave the doors on the furnace to provide support and to prevent damage or warping of the cabinet When lifting the furnace by the cabinet support the ends of the furnace rather than lifting by the cabinet flanges at the return air openings bottom or sides or sup ply air opening 13 When lifting the furnace it is acceptable to use the primary heat exchanger tubes as a lifting...

Page 3: ...he National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NSCNGPIC For a copy contact Standard Sales CSA International 178 Rexdale Boulevard Etobicoke Toronto Ontario Canada M9W 1RS STEP 3 Combustion and Ventilation Air US Section 5 3 of the NFGC air for Combus...

Page 4: ...side wall horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for resi dential purposes including those owned or operated by the Com monwealth and where the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following require m...

Page 5: ...cess cover shall be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges remove the screw holding an individual flange rotate the flange so it is in the upward position and reinstall the screw then repeat this for all 4 flanges If the flanges are not used they m...

Page 6: ...hand applications no conversion is required to an MC coil when used with a downflow horizontal furnace A mounting plate supplied with every coil should always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS These upflow coils are designed for installation on top of upflow fur naces only If the coil is used with a furnace of a different size use a 4...

Page 7: ...on a flat solid surface this bottom panel will provide an adequate seal to prevent air leakage through the unused bottom opening However if the furnace is to be installed on a surface that is uneven or if it is to be installed on blocks or otherwise raised off the floor it will be necessary to seal the edges of the bottom panel to the casing using tape or other appropriate gasket material to preve...

Page 8: ...t at the supply end of the furnace one support located approximately in the center of the furnace near the blower shelf and the third support should be at the return end of the fur nace Maintain a 6 15 2 cm minimum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the furna...

Page 9: ...WHO DQ DGGLWLRQDO 6833 1 RPEXVWLRQ LU QOHW 5 7851 1 9HQW RQQHFWLRQ 2XWOHW 9HQW RQQHFWLRQ 2XWOHW 9HQW RQQHFWLRQ 2XWOHW Table 3 Cabinet and Duct Dimensions BTUH kW Input Nominal CFM m3 min Cabinet Size Cabinet Dimensions Illustrated in Figure 13 Approximate Operating Weights A in A cm B in B cm C in C cm Lbs kg 60 17 6 1200 34 0 B 17 1 2 44 4 16 3 8 41 6 13 1 4 33 7 122 80 23 4 1200 34 0 B 17 1 2 44...

Page 10: ...ther side of the furnace using any of the gas pipe entry knockouts on both sides of the furnace Refer to Figures 13 and 16 DANGER An overpressure protection device such as a pressure regulator must be installed in the gas piping system upstream of the furnace and must act to limit the downstream pressure to the gas valve so it does not exceed 0 5 psig 14 w c 3 48 kPa Pressures exceeding 0 5 psig 1...

Page 11: ...t Altitude feet Gas Heating Value MJ cu m Altitude m 0 7999 8000 8999 9000 9999 0 2437 2438 2742 2743 3048 in w c in w c in w c kPa kPa kPa 800 1 7 1 7 1 7 29 8 0 42 0 42 0 42 850 1 7 1 7 1 7 31 7 0 42 0 42 0 42 900 1 7 1 7 1 7 33 5 0 42 0 42 0 42 950 1 7 1 7 1 5 35 4 0 42 0 42 0 38 1000 1 6 1 5 1 4 37 3 0 41 0 37 0 34 1050 1 5 1 4 1 3 39 1 0 37 0 34 0 31 1100 1 3 1 2 1 1 41 0 0 34 0 31 0 28 2500 ...

Page 12: ...d the main electrical source disconnected connect the thermostat wiring from the wiring connections on the thermostat to the terminal board on the ignition module as shown in Figures 18 or 19 Electronic thermostats may require the common wire to be connected Apply strain relief to thermostat wires passing through cabinet If air condition ing equipment is installed use thermostat wiring to connect ...

Page 13: ...t Hot Cool XFMR TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor TWO STAGE G Fan TWO STAGE FURNACE Y Y2 Second or Full Stage Compressor ID MODELS External Humidistat Optional Open on Humidity Rise Thermostat Installer Setup Connection of the C terminal 24 volt common is optional w...

Page 14: ...DN22H00124 PT 8 9 F L 8 9 T G L 8 9 T TM9 FURNACE W W1 First Stage Heat W2 Second Stage Heat RC AUX Auxiliary Heat E W1 First Stage Aux Heat 24VAC Humidifier Relay Optional L Malfunction Light L Malfunction Light O B Reversing Valve O Reversing Valve Energized in Cool E Emergency Heat Thermostat Installer Setup 0170 System Type must be set to 12 3 Heat 2 Heat Pump Selection of GAS ELEC switch on t...

Page 15: ...r on the first furnace operates on W1 and the gas burner on the second furnace operates on W2 then the use of an air mixing device in the plenum to mix the air from both furnaces is strongly recommended The mixing device must be installed before any ducts that supply air to occupied spaces Twinning causes both indoor fans to operate simultaneously If a mixing device is not used any ducts that are ...

Page 16: ...main drain is plumbed through the casing left side opening when viewed from the front of the furnace The condensate hoses must slope downwards at all points When drain hose routing changes are required shown in Figures 23 26 be sure to cap all un used openings If rerouting hoses excess length should be cut off so that no sagging loops will collect and hold condensate which will cause the furnace t...

Page 17: ...rain hose is to be installed by connecting it to the inlet pipe coupling and to the collec tor box as shown in Figures 23 25 and 26 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the vent drain must not be plugged If the intake drain is used the bird screen cannot be installed This is only appro...

Page 18: ...f so that no sagging loops will collect and hold condensate which will cause the furnace to not operate Shorten pressure switch hose Re route and shorten pressure switch hose Shorten rain gutter hose Move rain gutter hose to this position For 100 120K input furnaces the condensate drain is plumbed toward the left casing outlet from the factory For 040 060 080K input furnaces the condensate drain i...

Page 19: ...itch hose to this position NOTE May require the longer hose that is provided with wider cabinets Move condensate drain hose to this position may exit either side of the cabinet Move rain gutter hose to this position When drain hose routing changes are required be sure to cap all un used openings If rerouting hoses excess length should be cut off so that no sagging loops will collect and hold conde...

Page 20: ...hose to this position NOTE May require the longer hose that is provided with wider cabinets Change condensate drain connection to the 90 fitting provided Move condensate drain hose to this position Move rain gutter hose to this position NOTE May require hose extension that is provided with wider cabinets Move condensate drain hose to this position Change condensate drain connection to the 90 fitti...

Page 21: ...LQJ SURYLGHG 0RYH FRQGHQVDWH GUDLQ KRVH WR WKLV SRVLWLRQ 0RYH UDLQ JXWWHU KRVH WR WKLV SRVLWLRQ KDQJH FRQGHQVDWH GUDLQ FRQQHFWLRQ WR WKH ILWWLQJ SURYLGHG 0RYH FRQGHQVDWH GUDLQ KRVH WR WKLV SRVLWLRQ 5 2 0RYH SUHVVXUH VZLWFK KRVH WR WKLV SRVLWLRQ KHQ GUDLQ KRVH URXWLQJ FKDQJHV DUH UHTXLUHG EH VXUH WR FDS DOO XQ XVHG RSHQLQJV I UHURXWLQJ KRVHV H FHVV OHQJWK VKRXOG EH FXW RII VR WKDW QR VDJJLQJ ORRSV ...

Page 22: ...he combustion air pipe 6 All models are supplied with 2 5 1 cm vent connections When the pipe must be increased to 3 7 6 cm diameter the transition from 2 to 3 must be done as close to the furnace as possible The 2 to 3 increase should be installed in the vertical position as to not create an area that will pool water 7 In Canada vents shall be certified to ULC S636 Standard for Type BH Gas Ventin...

Page 23: ...4 145 100 000 4 125 120 000 3 80 120 000 3 60 120 000 4 145 120 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input BTUH Pipe Size in Max equivalent Length ft Model Input BTUH Pipe Size in Max equivalent Length ft 60 000 2 50 60 000 2 30 60 000 3 75 60 000 3 55 60 000 4 140 60 000 4 120 80 000 2 50 80 000 2 20 80 000 3 75 80 000 3 55 80 000 4 140 80 000 4 120 100 000 2 15 100 000 2 NA 10...

Page 24: ...ns TABLE 10 Elbow Dimensions Elbow A Dimension Illustrated in Figure 27 2 Standard 2 5 16 3 Standard 3 1 16 2 Sweep 3 1 4 3 Sweep 4 1 16 TABLE 11 Equivalent Length of Fittings Fitting Equivalent Length 2 90 sweep elbow 5 feet of 2 pipe 2 45 sweep elbow 2 1 2 feet of 2 pipe 2 90 standard elbow 7 feet of 2 pipe 2 45 standard elbow 3 1 2 feet of 2 pipe 3 90 sweep elbow 5 feet of 3 pipe 3 45 sweep elb...

Page 25: ...rements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier 12 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier G Clearance to inside corner 3 feet 91 4 cm 3...

Page 26: ...nace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 30 and 31 can be installed so the combustion air pipe terminates as described in outdoor combustion air or ventilated combustion air sec tions in these instructions Follow the instructions for outdoor combus tion air or ventilated...

Page 27: ...ns Refer to Ambient Combustion Air Supply for proper installa tion Refer to Figures 36 and 37 3 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated attic or crawl space The combustion air and the vent pipes are not termi nated in the same atmospheric zone Refer to Figure 38...

Page 28: ...erated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position FIGURE 36 Combustion Airflow Path Through The Furnace Casing WARNING This type of installation requires that the supply air to th...

Page 29: ...322 cm2 per 0 879 kW of the total input rating of all equipment located in the enclosure b Not less than the sum of all vent connectors in the confined space 3 The duct shall be least the same cross sectional area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the fr...

Page 30: ...ghting instructions Place the appliance being inspected in operation Adjust thermostat so the appliance shall operate contin uously 5 Test each appliance such as a water heater equipped with a draft hood for spillage down draft or no draft at the draft hood relief open ing after 5 minutes of main burner operation Appliances that do not have draft hoods need to be checked at the vent pipe as close ...

Page 31: ...er orifices are sized to provide proper input rate using natural gas with a heating value of 1030 BTU Ft3 38 4 MJ m3 If the heating value of your gas is significantly different it may be necessary to replace the orifices Verify natural gas input rate by clocking meter 1 Turn off all other gas appliances and pilots 2 Run furnace for a minimum of 3 minutes in high fire heating opera tion 3 Measure t...

Page 32: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232 581 92 39 78 196 32 113 225 563 94 38 76 192 33 109 218 545 96 38 75 188 34 106 212 529 98 37 74 184 35 103 206 514 100 36 72 180 36 100 200 500 102 35 71 178 37 97 195 486 104 35 69 173 38 95 189 4...

Page 33: ...re from W1 to W2 to R on the furnace control board for the furnace to operate HIGH fire Once correct manifold pres sure is set HI remove jumper from W2 for the furnace to operate on low fire Set the manifold pressure LO to correct manifold pres sure 4 After the manifold pressure has been adjusted re calculate the fur nace input to make sure you have not exceeded the specified input on the rating p...

Page 34: ... vent sys tems manufacturer test port fitting must be used DONOT drill a test port hole in polypropylene piping Use the following procedure 1 Drill a 11 32 hole in the side wall of the PVC vent pipe If the hole is in a horizontal section of the vent pipe ensure that it is located away from the bottom where condensation may be flowing back toward the furnace 2 Operate the furnace a minimum of 10 mi...

Page 35: ...4 1267 1232 1183 1143 1080 1003 871 798 120D20MP11 High 2341 2245 2153 2072 1977 1876 1769 1642 1506 1306 Medium High 2002 1952 1878 1823 1739 1657 1563 1458 1322 1185 Medium Low 1615 1579 1533 1473 1430 1368 1282 1186 1091 953 Low 1352 1295 1259 1245 1190 1141 1076 998 938 820 Left Side Airflow Data SCFM Models Speed Ext Static Pressure in H2O 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 060B12MP11 Hi...

Page 36: ...oper amount of combustion air is being provided the pressure switch will close the ignition control pro vides a 17 second ignitor warm up period the gas valve then opens the gas starts to flow ignition occurs and the flame sensor begins its sensing function The blower motor will energize 30 seconds after the gas valve opens if a flame is detected Normal furnace operation will continue until the th...

Page 37: ... description of 5 Red Flashes and 11 Red Flashes below If the main limit switch opens five times within a single call for heat the control will indicate 4 Red Flashes and will enter a one hour soft lock out 5 RED FLASHES This fault is indicated if the limit circuit is open for more than fifteen minutes usually indicating that a manual reset rollout switch has opened Check for proper combustion air...

Page 38: ...D will flash three green flashes when the memory has been cleared then will resume the normal slow green flash after a five second pause SECTION XII REPLACEMENT PARTS LIST DESCRIPTION MOTOR BLOWER COMBUSTION MOTOR DIRECT DRIVE BLOWER ELECTRICAL CONTROL FURNACE CONTROL TEMPERATURE IGNITER SENSOR FLAME SWITCH DOOR SWITCH LIMIT SWITCHES PRESSURE TRANSFORMER VALVE GAS AIR MOVING HOUSING BLOWER WHEEL B...

Page 39: ...ORE CAUTION PRECAUTION OUVREZ LES DISJONCTEURS AVANT DE PROCEDER AVEC LE SERVICE 1042426 UWD A 0413 Fault Code Retrieval To retrieve fault codes push and release ERROR button on control board The LED will flash the last five error codes beginning with the most recent If there are no fault codes in memory the LED will give two green flashes To clear the fault code memory push and hold the ERROR but...

Page 40: ...1083286 UIM F 1116 40 Johnson Controls Unitary Products NOTES ...

Page 41: ...s connected Technician Performing Start Up Installing Contractor Name Start Up Date Continued on next Page OFF 10 MIN 15 MIN 20 MIN Thermostat Staging Staging Venting system is the proper size within the limitations of the chart in the installation instructions properly connected to the furnace and properly pitched Condensate drain is connected Intake Size Exhaust Size of 90 Degree Ells of 45 Degr...

Page 42: ...r Side Continuous Fan PSC Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle Test Operate the furnace through several heating cycles from the thermostat noting and correcting any problems Operate the furnace through continuous fan cycles from the thermostat noting and correcting any problems Operate the furnace through cooli...

Reviews: