Johnson Controls Ducted Systems
PERFORMANCE DATA - 3.5 TON
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
RHP14L42B24S
35
107
42.6
0.91
37.8
1.80
33.1
2.69
28.3
3.57
23.6
4.46
18.8
5.35
14.1
6.24
40
119
45.3
1.26
41.2
1.97
37.1
2.68
33.0
3.39
28.9
4.10
24.8
4.81
20.6
5.52
45
130
48.1
1.61
44.6
2.14
41.2
2.67
37.7
3.20
34.2
3.74
30.7
4.27
27.2
4.80
50
143
50.9
1.96
48.1
2.31
45.2
2.67
42.3
3.02
39.5
3.37
36.6
3.73
33.8
4.08
55
156
53.7
2.31
51.5
2.49
49.2
2.66
47.0
2.84
44.8
3.01
42.5
3.18
40.3
3.36
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15ºF subcooling and 15ºF superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2ºF increase in subcooling.
b. Decrease capacity by 1% for each 2ºF decrease in subcooling.
3. Maximum recommended condensing temperature is 140ºF.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
RHP14L42B24S
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
IDCFM
1150
1400
1650
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
37.5
40.7
41.2
45.6
50.7
39.9
42.1
42.8
47.2
52.2
42.3
43.5
44.4
48.7
53.6
S.C.
37.3
34.2
29.1
28.9
22.8
39.8
37.6
31.7
31.5
24.4
42.3
41.1
34.3
34.1
25.9
KW
2.48
2.48
2.48
2.49
2.50
2.57
2.57
2.58
2.58
2.59
2.66
2.65
2.67
2.67
2.68
75
T.C.
36.4
38.4
39.0
44.2
49.7
38.6
40.0
41.0
45.7
51.2
40.8
41.6
42.9
47.3
52.8
S.C.
36.2
33.0
28.2
28.3
22.4
38.5
36.7
31.1
31.1
24.1
40.8
40.4
33.9
33.9
25.9
KW
2.72
2.72
2.72
2.73
2.74
2.81
2.80
2.82
2.82
2.83
2.90
2.88
2.91
2.91
2.92
85
T.C.
35.0
36.8
37.3
41.9
47.0
37.1
38.2
38.9
43.3
48.5
39.2
39.6
40.5
44.6
49.9
S.C.
35.0
32.5
27.5
27.6
21.7
37.1
36.1
30.3
30.4
23.3
39.2
39.6
33.1
33.1
25.0
KW
3.05
3.05
3.06
3.06
3.06
3.14
3.14
3.14
3.14
3.15
3.23
3.22
3.23
3.23
3.24
95
T.C.
33.7
35.2
35.6
39.6
44.4
35.6
36.4
36.9
40.8
45.7
37.5
37.6
38.1
42.0
47.1
S.C.
33.7
32.1
26.8
26.9
21.0
35.6
35.5
29.5
29.7
22.5
37.5
37.6
32.2
32.4
24.1
KW
3.38
3.38
3.39
3.38
3.38
3.47
3.47
3.47
3.47
3.46
3.56
3.56
3.56
3.56
3.55
105
T.C.
32.0
33.5
33.7
37.6
42.4
33.7
34.7
34.9
38.7
43.6
35.5
35.9
36.1
39.9
44.9
S.C.
32.0
30.9
25.7
25.9
20.3
33.7
33.8
28.2
28.7
21.9
35.5
35.9
30.8
31.4
23.5
KW
3.76
3.76
3.76
3.76
3.75
3.85
3.84
3.85
3.84
3.84
3.94
3.93
3.94
3.93
3.93
115
T.C.
30.3
31.7
31.9
35.5
40.5
31.9
32.9
33.0
36.6
41.6
33.4
34.1
34.1
37.8
42.7
S.C.
30.3
29.7
24.6
24.9
19.6
31.9
32.2
27.0
27.7
21.2
33.4
34.1
29.4
30.4
22.8
KW
4.13
4.13
4.14
4.14
4.13
4.22
4.22
4.23
4.22
4.22
4.31
4.30
4.31
4.30
4.31
125
T.C.
28.7
30.0
30.1
33.4
38.5
30.0
31.2
31.1
34.6
39.5
31.3
32.4
32.0
35.7
40.5
S.C.
28.7
28.4
23.5
23.9
18.9
30.0
30.5
25.8
26.7
20.5
31.3
32.4
28.1
29.4
22.1
KW
4.51
4.50
4.52
4.52
4.50
4.59
4.59
4.60
4.60
4.59
4.68
4.68
4.69
4.68
4.68
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.