5612272-UTG-H-1221
Johnson Controls Ducted Systems
45
PERFORMANCE DATA - 2 TON
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
AT COMPRESSOR
Outdoor Ambient Temperature
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
RHP14L24B23S
35
107
23.8
1.11
22.0
1.33
20.2
1.56
18.5
1.78
16.7
2.00
15.0
2.23
13.2
2.45
40
119
25.9
1.11
24.2
1.33
22.4
1.55
20.6
1.77
18.9
1.98
17.1
2.20
15.3
2.42
45
130
28.1
1.11
26.4
1.33
24.6
1.54
22.8
1.75
21.0
1.96
19.2
2.17
17.4
2.39
50
143
30.3
1.11
28.5
1.32
26.7
1.53
24.9
1.73
23.1
1.94
21.3
2.15
19.5
2.35
55
156
32.5
1.12
30.7
1.32
28.9
1.52
27.1
1.72
25.3
1.92
23.4
2.12
21.6
2.32
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15ºF subcooling and 15ºF superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2ºF increase in subcooling.
b. Decrease capacity by 1% for each 2ºF decrease in subcooling.
3. Maximum recommended condensing temperature is 140ºF.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
RHP14L24B23S
AIR TEMPERATURE
ENTERING
OUTDOOR UNIT (°F)
IDCFM
600
800
1000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
21.3
23.8
24.0
26.5
28.9
23.3
24.8
25.0
27.5
29.5
25.3
25.9
26.0
28.5
30.1
S.C.
20.7
18.9
16.3
16.1
13.0
22.8
21.8
18.5
18.3
14.0
24.9
24.8
20.8
20.5
15.1
KW
1.46
1.46
1.45
1.46
1.45
1.53
1.53
1.53
1.53
1.52
1.60
1.60
1.60
1.60
1.60
75
T.C.
20.6
22.7
23.0
25.4
28.2
22.5
23.8
24.0
26.5
29.3
24.4
24.9
24.9
27.5
30.3
S.C.
20.1
18.3
15.8
15.6
12.7
22.1
21.4
18.1
17.9
14.2
24.0
24.4
20.3
20.2
15.6
KW
1.60
1.60
1.59
1.60
1.59
1.67
1.67
1.67
1.67
1.66
1.74
1.74
1.74
1.74
1.73
85
T.C.
19.8
21.7
21.9
24.3
27.0
21.6
22.7
22.8
25.2
28.0
23.4
23.7
23.7
26.1
28.9
S.C.
19.4
17.9
15.3
15.2
12.3
21.2
20.7
17.5
17.5
13.7
23.1
23.5
19.8
19.7
15.1
KW
1.79
1.79
1.78
1.79
1.78
1.86
1.86
1.85
1.86
1.85
1.93
1.93
1.93
1.93
1.92
95
T.C.
19.0
20.6
20.8
23.1
25.8
20.7
21.6
21.7
23.9
26.7
22.3
22.5
22.5
24.7
27.5
S.C.
18.7
17.4
14.7
14.8
11.8
20.4
20.0
17.0
17.0
13.2
22.1
22.5
19.3
19.2
14.6
KW
1.97
1.97
1.97
1.98
1.97
2.04
2.05
2.04
2.05
2.04
2.12
2.12
2.12
2.12
2.11
105
T.C.
17.8
19.2
19.4
21.6
24.2
19.4
20.2
20.2
22.4
25.0
21.0
21.1
21.0
23.1
25.7
S.C.
17.6
16.8
14.1
14.2
11.2
19.2
19.0
16.4
16.3
12.6
20.8
21.1
18.6
18.5
14.0
KW
2.26
2.26
2.26
2.27
2.25
2.33
2.33
2.33
2.33
2.32
2.40
2.40
2.40
2.40
2.39
115
T.C.
16.7
17.9
18.1
20.2
22.6
18.2
18.9
18.8
20.9
23.3
19.7
19.8
19.5
21.5
24.0
S.C.
16.6
16.3
13.6
13.6
10.7
18.1
18.0
15.7
15.7
12.0
19.6
19.8
17.9
17.8
13.4
KW
2.55
2.54
2.54
2.54
2.52
2.61
2.61
2.61
2.61
2.59
2.68
2.67
2.68
2.68
2.67
125
T.C.
15.5
16.6
16.8
18.8
21.0
17.0
17.6
17.4
19.4
21.7
18.4
18.5
18.0
19.9
22.3
S.C.
15.5
15.7
13.0
13.0
10.1
17.0
17.1
15.1
15.1
11.5
18.4
18.5
17.2
17.1
12.8
KW
2.83
2.81
2.81
2.81
2.80
2.89
2.88
2.88
2.88
2.87
2.95
2.95
2.95
2.95
2.94
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.