5612272-UTG-H-1221
4
Johnson Controls Ducted Systems
SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS - N COIL
Outdoor unit
RHP14L18
B23S
RHP14L24
B23S
RHP14L30
B23S
RHP14L35
B23S
RHP14L36
B23S
RHP14L42
B24S
RHP14L48
B23S
RHP14L60
B23S
Required indoor
metering device
1
,
2
BA1
BA1
BA1 or BB1
BA1 or BB1
BA1 or BF1
BC1
BC1
BG1 or BC1
Defrost jumper pin setting
2
2
2
3
3
2
4
2
Indoor unit
3,4,5
Additional charge (oz)
RFCX18BP
4
–
–
–
–
–
–
–
RFCX24BP
11
17
–
–
–
–
–
–
RFCX30BP
–
26
20
–
–
–
–
–
RFCX36BP
–
–
20
–
–
–
–
–
RFCX36CP
–
–
–
–
–
–
–
–
RFCX37CP
–
–
–
–
3
–
–
–
RFCX42CP
–
–
–
–
–
–
–
–
RFCX48(CP,DP)
–
–
–
–
–
27
–
–
RFCX60(CP,DP)
–
–
–
–
–
–
–
–
RFCX18BE
4
–
–
–
–
–
–
–
RFCX24BE
11
17
–
–
–
–
–
–
RFCX30BE
–
26
13
–
–
–
–
–
RFCX36(BE,CE)
–
–
20
0
–
–
–
–
RFCX42CE
–
–
23
7
3
27
–
–
RFCX48(CE,DE)
–
–
–
–
3
27
26
–
RFCX60CE
–
–
–
–
–
–
28
–
RFCX60DE
–
–
–
–
–
–
–
5
CF/CM/CU18(A,B)
4
–
–
–
–
–
–
–
CF/CM/CU24(A,B)
11
17
–
–
–
–
–
–
CF/CM/CU30(A,B,C)
–
26
13
–
–
–
–
–
CF/CM/CU36(A,B,C)
–
–
20
0
–
–
–
–
CF/CM/CU42(B,C,D)
–
–
23
8
–
–
–
–
CF/CM/CU48(C,D)
–
–
–
7
3
27
26
–
CF/CM/CU60(C,D)
–
–
–
–
–
–
28
–
CF/CM64D
–
–
–
–
–
–
–
5
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, see the “SYSTEM CAPACITY - Upflow, Downflow and Horizontal Furnaces and Coils” table.
1. For applications that require a TXV, use S1-1TVM*** series kit.
2. Approved orifice(s) are shipped with the outdoor unit.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower time delay.
4. Do not use CF coils in horizontal applications.
5. Charge adders shown above do not indicate that coils are rated for every application. See the performance data tables for actual performance for specified system
matches. Obtain certified system ratings from
www.ahridirectory.org.