<6. Maintenance>
6-1
IM 01C50B01-01E
6. Maintenance
6.1 General
Each component of this instrument is configured in
units to make maintenance easier.
This chapter contains disassembly and assembly
procedures associated with calibration, adjustment
and part replacement required for maintenance of
the affected instrument.
IMPORTANT
1. Maintenance of this instrument should be
performed in a service shop where the
necessary tools are provided.
2. Handling the CPU assembly
Some of the parts contained in the CPU
assembly are susceptible to static electricity
damage. Before performing maintenance,
use a ground wrist band or other antistatic
mea sures, and avoid touching the electronic
components and circuits with bare hands.
When removed from the instrument, keep
the CPU assembly in an antistatic bag.
6.2 Calibration
This instrument is fully factory-tested and is
guaranteed for the intended accuracy, eliminating
the need for calibration. When calibration needs to
be varified, the following equipment and calibration
procedure is recommended.
6.2.1 Selection of Equipment for
Calibration
Table 6.1 lists the equipment required for
calibration. The calibration equipment traceable to a
verifying agency standard should be used.
6.2.2 Calibration Procedure
To conduct calibration required to evaluate the
uncertainty while using the instrument, follow the
steps below:
1. In accordance with the example wiring shown in
Figure 6.1, connect each equipment and initiate
warm up. Lay wiring on the input side according
to the sensor to be used.
Table 6.1
Calibration Equipment List
Name
Recommended
Remark
Power
supply
SDBT, SDBS type
distributor
4 to 20mA DC
(Output voltage:
26.5±1.5V, drop
by internal 250Ω
resistance included)
Load
resistance
2792 type standard
resistor
(250Ω ±0.005%)
For 4 to 20mA DC
Voltmeter Model 1271
digital multimeter
(accuracy: ±0.002%)
For 4 to 20mA DC
signal
Universal
calibrator
Model 9100 type
For calibration of
DC voltage and
thermocouple
Variable
resistor
279301 type 6-dial
variable resistor
(accuracy: ±0.001%
±2mΩ)
For calibration
of thermometer
resistor (RTD) input
F0601.ai
1
2
3
4
5
1
2
3
4
5
(A)
(B)
(B)
(A)
a. Wiring of power supply and output
b. Example of wiring for thermocouple or DC voltage input
(when 1 input type is used)
+ Output signal
–
Load
resistance
DC voltage generator
Voltmeter
c. Example of wiring for thermometer resistor 4-core type
(when 1 input type is used)
Variable resistor
(+)
(–)
Figure 6.1
Example of Wiring for Calibration
Equipment
2. For DC voltage input
With a voltage generator, deliver input signals
corresponding to 0, 25, 75, or 100% of the input
span to the temperature transmitter. Measure
the resulting input signal with the voltmeter
(digital multimeter) and check the output value
relative to the input value.