<3. Function Specification>
All Rights Reserved Copyright © 2006, Yokogawa Electric Corporation
IM 01C25R51-01E
3.5
FSA120 DTM Function Detail
3.5.1
Transmitter Management
Transmitter management function is supported by EJX910 HART DTM and EJX910 FF
DTM.
EJX910FF DTM supports the following blocks in the EJX910: Resource Block, Sensor
Transducer Block, Flow Transducer Block, LCD Transducer block, and AI function blocks.
Parameters of other function blocks should be set and changed by other Fieldbus
configurators.
• Setting of Node Address and tag is not supported.
• Scheduling is not supported.
NOTE
Setting of Node Address and PD Tag and scheduling are not supported by FSA120. Use
general purpose Fieldbus setting tool to set these items. After using setting tool, finish the
program before starting FSA120.
(1)
Online Parameter
The Transmitter General parameters of the device can be edited directly in online
status.
(Process value monitoring, Tag, Range, Unit, Damping, Lowcut, Indicator display,
Maintenance, Adjustment, Status information display)
(2)
Offline Parameter
The Transmitter General parameters of the device can be edited and stored in offline
database.
(Process value monitoring, Tag, Range, Unit, Damping, Lowcut, Indicator display,
Maintenance, Adjustment, Status information display)
(3)
Downloads to or uploads from the transmitter
The Transmitter Flow and General Parameters stored in offline database are
downloaded the to device.
The parameters of the device is uploaded from the device and stored in offline
database.
Transmitter General Parameters:
HART or F
OUNDATION
Fieldbus parameters of the device, which can be modified with using
HART handheld terminal or Fieldbus Configuration Tool. e.g. range, damping, etc.
User Flow Parameters:
The parameters which users input on EJXMVTool for flow configuration.
This parameters are used to generate flow approximation and not downloaded to the
device.
Transmitter Flow Parameters:
The parameters which EJXMVTool calculates and generates with using the User Flow
Parameters and are downloaded to the device.