8. GENERAL SPECIFICATIONS
8.
GENERAL SPECIFICATIONS
8.1 Standard Specifications
Refer to IM 01C25T02-01E for FOUNDATION
Fieldbus communication type marked with “
”.
Performance Specifications
See General Specifications sheet, GS 01C25H01-01E and
GS 01C25J03-01E.
Functional Specifications
Span & Range Limits
EJX118A
Measurement
Span/Range
M
H
2 to 100
–
500 to 500
Span
Span
Range
Range
kPa
8 to 400
–
400 to 400
–
2000 to 2000
40 to 2000
–
100 to 100
10 to 500
inH
2
O(/D1)
mbar(/D3)
20 to 1000
–
5000 to 5000
–
1000 to 1000
100 to 5000
mmH
2
O(/D4)
200 to 10000
–
10000 to 10000
0.1 to 5 kgf/cm
2
–
5 to 5 kgf/cm
2
T0801.EPS
EJX438A
Span
Flush
type
*1
Extended
type
*1
–1 to 160
1.6 to 160
–1 to 35
23 to 1000
1.6 to 70
0.16 to 7
Span
Range
Range
0.16 to 16
–0.1 to 16
–0.1 to 3.5
–14.5 to 500
–14.5 to 2300
0.035 to 3.5
5 to 500
Span
23 to 2300
MPa
–0.1 to 7
–14.5 to 1000
Range
–1 to 70
1.6 to 160
–1 to 35
1.6 to 70
–1 to 70
–1 to 160
kgf/cm
2
(/D3)
psi (/D1)
bar (/D2)
0.35 to 35
0.35 to 35
B
Measurement
Span and Range
A
*1
T0802.EPS
*1: Measurement range is within the flange rating.
Output “
”
Two wire 4 to 20 mA DC output with digital communica-
tions, linear or square root programmable. BRAIN or
HART FSK protocol are superimposed on the 4 to 20 mA
signal.
Output range: 3.6 mA to 21.6 mA
Output limits conform to NAMUR NE43 can be pre-set by
option C2 or C3.
Failure Alarm
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: –5%, 3.2 mA DC or less
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
Amplifier damping time constant is adjustaTf-24 0 to
100.00 seconds and added to response time.
Note: For BRAIN protocol type, when amplifier
damping is set to less than 0.5 seconds, communi-
cation may occasionally be unavailaTf-during the
operation, especially whif-output changes
dynamically. The default setting of damping
ensures staTf-communication.
Update Period “
”
Differential Pressure: 45 msec
Static Pressure: 360 msec
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the lower
and upper range limits of the capsule.
External Zero Adjustment “
”
External Zero is continuously adjustaTf-with 0.01%
incremental resolution of span. Re-range can be done
locally using the digital indicator with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar
graph.
The indicator is configuraTf-to display one or up-to four of
the following variaTfs periodically.;
Differential pressure in %, Scaled Differential pressure,
Differential Pressure in Engineering unit, Static Pressure in
Engineering unit.
See “Setting When Shipped” for factory setting.
TaTf-8.1 Process temperature, Ambient temperature, and Working pressure
T0803.EPS
E
B
C
D
51 kPa abs (7.4 psi abs)
to flange rating
pressure*
5
–50 to 100
°
C
(–58 to 212
°
F)
A
–30 to 180
°
C
(–22 to 356
°
F)
10 to 310
°
C
(50 to 590
°
F)
–20 to 120
°
C
(–4 to 248
°
F)
–10 to 60
°
C
(14 to 140
°
F)
–15 to 60
°
C
(5 to 140
°
F)
–10 to 250
°
C
*4
(14 to 482
°
F)
10 to 60
°
C
(50 to 140
°
F)
–40 to 60
°
C
(–40 to 140
°
F)
–10 to 60
°
C
(14 to 140
°
F)
Specific gravity
*3
1.09
0.94
1.90 to 1.92
1.09
100 kPa abs
(atmospheric pressure)
to flange rating
pressure*
5
Process temperature
*1
Code
Ambient temperature
*2
2.7 kPa abs
(0.38 psi abs) to
flange rating pressure*
5
1.07
Working pressure
Fluorinated oil
(oil-prohibited use)
Ethylene glycol
(low temperature use)
Silicone oil (general use)
Silicone oil
(high temperature use)
Silicone oil (general use)
*1:
See figure 8.1 and 8.2 ‘Working Pressure and Process Temperature.’
*2:
This ambient temperature is the transmitter ambient temperature.
*3:
Approximate values at a temperature of 25
°
C (77
°
F)
*4:
In case of wetted parts material code TW (Tantalum), process temperature limit is up to 200
°
C (392
°
F).
*5:
Maximum measurement range value for EJX438W. The working pressure must be within the flange rating pressure.
Note: The differential pressure transmitter should be installed at least 600 mm below the high pressure (HP) process connection.
However, this value (600 mm) may be affected by ambient temperature, operating pressure, fill fluid or material of the wetted diaphragm.
Contact YOKOGAWA when the transmitter can not be installed at least 600 mm below the HP process connection.