5-11
IM 04P02B01-01E
Frequently Used Setup Operations (Setting Mode)
5
Note
For channels whose the leftmost value of the scale is set to –20000 (excluding the decimal),
the alarm value of –20000 is invalid. Set a value that is greater than or equal –19999.
• Difference High Limit Alarm/Difference Low Limit Alarm
Values in the measurable range can be specified. Measurable range refers to
“Selectable Span Range” in the table on page 5-4.
• High Limit on Rate-of-Change Alarm/Low Limit on Rate-of-Change Alarm
A value greater than or equal to 1 digit can be specified. For example, 1 digit
corresponds 0.001 for the 2 V range (measurable range: –2.000 to 2.000 V). The
maximum value that can be specified is the width of the measurable range (4.000 V
for 2 V range).
For ON/OFF input, only “1” can be specified.
Relay No.
The selectable relay numbers are listed below.
I01 and I02 on the /A1 option
I01 to I04 on the /A2 option
I01 to I06 on the /A3 option
I01 to I06 and I11 to I16 on the /A4 option
I01 to I06, I11 to I16, I21 to I26, I31 to I36 on the /A5 option
5.2 Setting the Alarm