<6. Functions>
6-28
IM 12K01B02-01E
2. Press [INIT CF.].
The screen to initialize the CF card appears.
[INIT CF.]
3. Confirm that the CF card is inserted, and press [YES].
When the initialization is complete, the screen returns to the CF CARD menu screen.
CAUTION
• When the CF card is initialized, all the data of CF card is deleted. Make sure to save the
contents before executing initialization.
• Execute initialization of the CF card using this unit.
• The file system of this unit is FAT. FAT32 and NTFS are not accepted.
• Use only genuine Yokogawa CF card (P/N K9436 CF). Otherwise, proper operation is not
guaranteed.
6.9 Alarm
An alarm is triggered when a malfunction occurs in the unit or the measurement value exceeds
the upper or lower limit.
Refer to “9.1 Table of Status and Operation”
Items regarding alarm are as follows:
Items of alarm
Description
Alarm Check (6.9.1)
Performs a check during the alarm.
Alarm Stop (6.9.2)
Stops all alarms during the alarm.
Alarm History Check (6.9.3)
Checks the alarm history of up to 511 records.
Alarm History Deletion (6.9.4) Deletes all of the alarm history.
CAUTION
As this unit calculates values using one digit under the least significant digit indicated as readings
or setting values, an alarm may not be triggered even if the displayed value is the same value set
for alarm.