ix
IM 05P01C31-01EN
Model and Suffix Codes of UT52A (for Detailed model)
[Style:S4]
Model
Suffix code
Optional
suffix
code
Description
UT52A
Digital Indicating Controller (provided with 3 DIs, and 3 DOs) (Power supply:
100-240 V AC)
Fixed code
-NNN
Always "-NNN”
Display language (*1)
-1
English
-2
German
-3
French
-4
Spanish
Case color
0
White (Lithg gray)
1
Black (Light charcoal gray)
Output 1 (*2) (*3) (*4)
-A
Analog output (current/voltage pulse)
-R
Relay output (c-contact)
-U
Universal output (current/voltage pulse/relay)
-T
Triac output
-P
Position proportional output
Output 2 (*2) (*3) (*4) (*5)
A
Analog output (current/voltage pulse)
R
Relay output (a-contact)
U
Universal output (current/voltage pulse/relay)
N
None
Retransmission output
/RT
Retransmission output or 15 V DC power supply
Heater break alarm (*3)
/HA
Heater break alarm
E1 terminal area (*5) (*6)
/R1
Remote (1 additional aux. analog) input and 1 additional DI
/U1
1 additional universal input (TC/RTD/DCV/mA)
/L1
24 V DC loop power supply
/CH1
RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)
/RCH1
Remote (1 additional aux. analog) input, 1 additional DI, and RS485
communication (Max.38.4 kbps, 2-wire)
/LCH1
24 V DC loop power supply and RS485 communication (Max. 38.4 kbps, 2-wire)
/X1
5 additional DIs
/Y1
5 additional DOs
/W1
2 additional DIs and 2 additional DOs
Power supply
/DC
Power supply 24 V AC/DC
Additional treatment (*7)
/CT
Coating
*1:
English, German, French, and Spanish can be displayed as the guide display.
*2:
For heating/cooling output, both Output 1 and Output 2 should be specified. Not available when Output 2 is “N.” For
position proportional output, specify “-P” for Output 1 and “N” for Output 2.
*3:
The /HA option can be specified only when the code for Output 1 and 2 is “-AN”, “-RN”, “-UN” or “-TN.”
*4:
When the code for Output 1 is "-R" or "-U" and Output 2 is "R" or "U", Output 1 is changed from the contact point c to
the contact point a. When the code for Output 1 is specified to "-T", only "A" or "N" is available for Output 2.
*5:
The /L1 or /LCH option can be specified only when the code for Output 2 is “N.”
*6:
Only one option is available for E1 terminal area.
*7:
When the /CT option is specified, the UT52A does not conform to the safety standards (UL and CSA) and CE marking.
Coating Treatment
(1) HumiSeal coating treatment
Apply HumiSeal coating to the printed circuit board assembly.
Do not apply HumiSeal coating to the following parts: connector, gold-plated contact
area, relay part, RJC device, and in the vicinity of the push switch/LED lamp.
(2) Apply terminal coating to the gold-plated contact area on the printed circuit board.
Notes
▪ There are two treatments as described above, but we do not guarantee their
effectiveness.
We do not supply any test data on these treatments.
▪ Do not apply any treatment to the screw terminal area on the back side of the
instrument.
Summary of Contents for UTAdvanced UT55A
Page 3: ......
Page 17: ...Blank Page ...
Page 25: ...Blank Page ...
Page 41: ...Blank Page ...
Page 51: ...Blank Page ...
Page 59: ...Blank Page ...
Page 107: ...Blank Page ...
Page 129: ...Blank Page ...
Page 139: ...8 10 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 143: ...8 14 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 151: ...8 22 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 30 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 38 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 46 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 189: ...8 60 IM 05P01C31 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 241: ...Blank Page ...
Page 315: ...Blank Page ...
Page 369: ...Blank Page ...
Page 411: ...Blank Page ...
Page 463: ...Blank Page ...
Page 473: ...Blank Page ...
Page 475: ...Blank Page ...